CERTIFIED DIMENSION PRINT
REQ'D CLEARANCES FOR SERVICING Ð in. (mm)
Duct Panel | . . . . . | 0. . . | ||
Unit Top | . . . 36 | (914.4) | ||
Side Opposite Ducts | . . . 36 | (914.4) | ||
Compressor Access | . . . 36 | (914.4) | ||
(Except for NEC requirements) |
|
|
| |
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L |
|
| ||
Ð in. (mm) |
|
|
|
|
Maximum Extension of Overhangs . . . | . . . 48 (1219.2) | |||
Unit Top | . . . 14 | (355.6) | ||
Duct Side of Unit | 2 (50.8) | |||
Side Opposite Ducts | . . . 14 | (355.6) | ||
Bottom of Unit | . . . . . | 0. . . | ||
Flue Panel | . . . 36 | (914.4) | ||
NEC (National Electrical Code) REQ'D CLEARANCES | ||||
|
|
|
| |
Ð in. (mm) |
|
|
| |
|
|
| ||
Between Units, Control Box Side . . . . | . . . 42 (1066.8) | |||
Unit and Ungrounded Surfaces, |
|
|
| |
Control Box Side | . . . 36 | (914.4) | ||
Unit and Block or Concrete Walls and Other |
|
| ||
Grounded Surfaces, Control Box Side | . . . 42 (1066.8) |
NOTE: Clearances must be maintained to prevent recircu- lation of air from outdoor fan discharge.
OUTDOOR COIL
UNIT |
| ELECTRICAL | UNIT | CORNER WEIGHT |
| |||
| WEIGHT |
| (lb/kg) |
| ||||
48SS | CHARACTERISTICS | lb | kg | A | B | C | D | |
|
|
| ||||||
048080 |
| 414 | 188 | 107/49 | 83/38 | 158/72 | 66/30 | |
048100/120/140 |
| 426 | 193 | 110/50 | 86/39 | 159/72 | 71/32 | |
060080 |
| 453 | 206 | 117/53 | 93/42 | 167/76 | 76/35 | |
INDOOR COIL |
| 465 | 211 120/55 96/44 167/76 82/37 | |||||
060100/120/140 |
| |||||||
UNIT |
|
| CENTER OF GRAVITY |
|
| |||
|
|
|
| (in./mm) |
|
|
| |
48SS |
| X |
|
| Y |
| Z |
|
|
|
|
|
|
| |||
048080 |
| 28.76/731 |
| 23.46/596 |
| 15.35/390 | ||
048100/120/140 | 28.42/722 |
| 23.42/595 |
| 15.35/390 | |||
060080 |
| 28.36/720 |
| 23.27/591 |
| 15.35/390 | ||
060100/120/140 | 27.95/710 |
| 23.23/590 |
| 15.35/390 |
INDOOR COIL ACCESS
5