AIR DISCHARGE | AIR IN |
AIR IN
C
L
3/8" DIA TIEDOWN KNOCKOUTS
(2) PLACES IN BASEPAN
NOTES:
1.ALLOW 30″ CLEARANCE TO SERVICE END OF UNIT, 48″ ABOVE UNIT, 6″ ON ONE SIDE, 12″
ON REMAINING SIDE, AND 24″ BETWEEN UNITS FOR PROPER AIRFLOW.
D | 2. | MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS | |
|
|
| 55° F (UNLESS LOW AMBIENT CONTROL IS USED) MAX 125° F. |
|
| 5. | SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT |
|
| E | MODEL NUMBER. |
|
| ||
|
| 6. | CENTER OF GRAVITY |
|
|
C
SERIAL |
|
|
PROD |
|
|
MODEL |
|
|
PISTON | ID | OD |
FACTORY CHARGED |
AIR DISCHARGE | AIR IN |
|
|
| |
VAPOR LINE CONN |
| |
| A | FIELD POWER SUPPLY CONN |
| 7/8″ DIA HOLE WITH | |
AIR DISCHARGE | 1 1/8″ DIA KNOCKOUT | |
|
| AND |
|
| 1 3/8″ DIA KNOCKOUT |
|
| FIELD CONTROL |
|
| SUPPLY CONN |
|
| 7/8″ DIA HOLE |
|
| 3/8″ DIA LIQUID |
|
| LINE CONN |
UNIT RATING
PLATE
B
ACCESS
PANEL
|
|
| LBS |
|
| Kg |
POWER SUPPLY |
|
| VOLTS | |||
|
|
| PH |
|
| HZ |
| PERMISSIBLE VOLTAGE AT UNIT | |||||
|
|
| MAX |
|
| MIN |
| SUITABLE FOR OUTDOOR USE | |||||
|
|
| COMPRESSOR | |||
VOLTS AC |
|
|
|
| ||
PH |
|
|
|
|
|
|
HZ |
|
|
|
|
|
|
RLA |
|
|
|
| ||
LRA |
|
|
|
| ||
|
|
| FAN MOTOR | |||
VOLTS AC |
|
|
|
| ||
PH |
|
|
|
|
|
|
HZ |
|
|
|
|
|
|
FLA |
|
|
|
|
|
|
| DESIGN/TEST PRESSURE GAGE | |||||
HI | PSI |
|
| kPa |
| |
LO | PSI |
|
| kPa |
| |
MINIMUM CIRCUIT AMPS | ||||||
MAX OVERCURRENT PROTECTIVE DEVICE | ||||||
| TYPE | USA | CANADA | |||
MAX FUSE |
|
|
| |||
MAX HACR |
|
| N/A | |||
MAX | N/A |
| ||||
| ® |
|
|
|
| |
|
| ® |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CARRIER CORP INDIANAPOLIS IN
46206 |
A92471
| UNIT | A | B | C | D | E |
| SIZE | In. | In. | In. | In. | In. |
| 018 | |||||
| 30 | 4 | ||||
060 | (301 Series) | 45 | ||||
060 | (311 Series) | 30 | 4 | |||
|
|
|
|
|
|
|
Fig. 2ÐUnit Reference Drawing
DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT TUBING IN GROUND. If any section of tubing is buried, there must be a
Step 4ÐMake Piping Connections
Outdoor units may be connected to indoor sections using accessory tubing package or field−supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft, consult
In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.
INSTALLATION RECOMMENDATIONS
1.Locate the unit away from windows.
2.Ensure that vapor and liquid line diameters are appropriate to the capacity of the unit. (See Table 1.)
3.Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4.Leave some slack between the structure and the unit to absorb vibration.
5.When passing refrigerant tubes through the wall, seal the opening with RTV or other pliable
6.Avoid direct lineset contact with water pipes, ductwork, floor joists, wall studs, floors, and walls.
7.Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with the tubing. (See Fig. 3.)
8.Ensure that tubing insulation is pliable and completely sur- rounds the vapor line.
9.When necessary, use hangar straps which are 1 in. wide and conform to the shape of the tubing insulation. (See Fig. 3.)
10.Isolate the hangar straps from the insulation by using metal sleeves bent to conform to the shape of the insulation.
If refrigerant tubes or indoor coil is exposed to atmospheric conditions for longer than 5 minutes, it must be evacuated to 500 microns to eliminate contamination and moisture in the system.
OUTDOOR UNITS CONNECTED TO
2