bearing brazing material. Consult local code requirements. Refrig- erant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
Step 5ÐMake Electrical Connections
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device. (See Fig. 2.)
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate.
NOTE: Use only copper wire between disconnect switch and unit.
NOTE: Install branch circuit disconnect per NEC of adequate size to handle unit starting current, but not larger than maximum fuse size shown on unit rating plate. Locate disconnect within sight from and readily accessible from unit, per Section
ROUTE GROUND AND POWER WIRES Ð Remove access panel and control box cover to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box. (See Fig. 2.) Size wires per NEC but not smaller than minimum wire size shown in presale literature.
The cabinet must have an uninterrupted or unbroken ground according to NEC, ANSI/NFPA
To avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed.
CONNECT GROUND AND POWER WIRES Ð Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 5.
Use No. 18 AWG
Use furnace transformer, fan coil transformer, or accessory trans- former for control power,
NOTE: Use of available
Step 6ÐInstall Electrical Accessories
Refer to the individual instructions packaged with the kits or accessories when installing.
Step 7ÐStart-up
1.Fully back seat (open) liquid and vapor service valves.
2.Unit is shipped with valve stem(s) front seated and caps installed. Replace stem caps after system is opened to refrig- erant flow (back seated). Replace caps finger tight and tighten additional 1/6 turn with wrench.
3.Close electrical disconnects to energize system.
4.Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature.
5.Set room thermostat at COOL and fan switch at FAN or AUTO, as desired. Operate unit for 15 minutes. Check system refrigerant charge. (See Step 8ÐChecking Charge.)
Step 8ÐChecking Charge
Factory charge is shown on unit rating plate. (See Fig. 2.)
Do not disable
Compressor damage may occur if system is overcharged.
Service valve gage ports are not equipped with Schrader valves. To prevent personal injury, make sure valves are fully back seated before removing gage port caps. Wear safety glasses and gloves when handling refrigerant.
DISCONNECT
PER N. E. C. AND/OR LOCAL CODES
FIELD POWER
WIRING
FIELD GROUND
WIRING
CONTACTOR
GROUND
LUG
A91056
Adjust charge by following procedure shown on the superheat charging tables located on unit information plate.
Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip- ment failure, it is essential that periodic maintenance be performed on this equipment. Consult your servicing contractor or User's Manual for the proper frequency of maintenance. Frequency of maintenance may vary depending upon geographic areas, such as
Fig. 5ÐLine Power Connections
CONNECT CONTROL WIRING Ð Route
coastal applications.
Step 1ÐLeave User's Manual With Homeowner
Explain system operation and maintenance procedures outlined in User's Manual.
4