Carrier 30XA080-500 Configure Unit for Minimum Load Control, OK button to confirm the input

Page 8

Configure Unit for Minimum Load Control —

The controls must be configured for the minimum load control operation. Use the Touch Pilot™ or the Navigator™ display to configure the system. Refer to the 30XA Controls, Start-Up, Operation, Service, and Troubleshooting manual for additional information.

Complete the following steps to configure minimum load con- trol with the Touch Pilot display:

1.Ensure the unit is in Local Off operating mode by looking at the upper left hand corner of the group display. If the

unit is not in Local Off mode, press the Start/Stop button

to switch to the Local Off operating mode.

2. Press the main menu button

on the bottom line of the

display, and then select Service→ Factory to navigate to the factory table.

3.Scroll down the screen by pressing the Scroll Down

button or the Page Down button until Hot Gas Bypass Select is displayed on the screen. Press Hot Gas Bypass Select to display the Point Data dialog.

4.Press the Modify button . If the login menu is dis- played, log in with the password. The default password is

3333. Press the OK button to confirm the input. The value of hgbp_sel will display. Select Yes and press

the OK button to confirm the input.

5.Press the Home button on the bottom line of the dis- play. A save confirmation menu will display. Press the

OK button to confirm the action.

6.Wait 10 seconds and cycle the control power using the Emergency On/Off switch (SW2).

The chiller is now configured for minimum load valve control.

Complete the following steps to configure minimum load con- trol with the Navigator display:

1.Set the Enable/Off/Remote switch to the Off position.

2.Press ESCAPE until the screen is blank and use the arrow key to select the Configuration mode LED.

3.Press ENTER , then use the arrow key to select the sub-mode ‘UNIT’, then press the ENTER key.

4.Press the down arrow key until ‘HGBP’ is displayed.

5.Press the ENTER key. If the login menu is displayed, log in with the password. The default password is 0 1 1 1. Use the arrow keys to change each number’s value. Press the ENTER key after each number until finished.

6.Press the ENTER key so that ‘No’ flashes.

7.Use the arrow keys to change the value to ‘Yes.’

8.Press the ENTER key.

9.Press the ESCAPE key until ‘DISP’ is displayed. Wait 10 seconds and cycle the control power using the Emer- gency On/Off switch (SW2).

The chiller is now configured for minimum load valve control.

Test Minimum Load Relay Output — Use the Touch Pilot or Navigator display’s service test mode and the instruc- tions given in their Controls, Start-Up, Operation, Service, and Troubleshooting manuals to verify proper operation of the solenoid(s).

For the Touch Pilot display:

1.Ensure the unit is in Local Off operating mode by looking at the upper left hand corner of the group display. If the

unit is not in the Local Off mode, press the Start/Stop but- ton to switch to the Local Off operating mode.

2. Press the Main Menu button on the bottom line of the display and then select Status→ Quick Test Enable.

3.Press the Force button . If the login menu is dis- played, log in with the password. The default password is

3333. Press the OK button to confirm the input.

4.The value of qck_test1 will display. Select On and press

the OK button to confirm the input.

5.Scroll down the screen by pressing the scroll down button

or the page down button until Cir. A Hot Gas Bypass is displayed on the screen. Press Cir. A Hot Gas Bypass Select to display the Point Data dialog.

6.Press the Force button . Select On and press the OK

button to confirm input.

7.Verify that the Cir. A minimum load valve (MLV) sole- noid is energized.

8.Proceed to Cir. B Hot Gas Bypass and Cir. C Hot Gas By- pass (30XA400-500 only) by pressing the page down

button . Repeat Steps 5-7 for Cir. B MLV and Cir. C MLV.

9.Use the page up button to return to the top of the ta- ble and select Quick Test Enable.

10.Press the Force button .

11.Select Off and press the OK button to disable Quick Test.

12.Once the outputs have been tested, the installation is com- plete. Return the Touch Pilot to Local Off operating mode.

For the Navigator display:

1.Set the Enable/Off/Remote switch to the Off position.

2.Press ESCAPE until the screen is blank and use the arrow key to select the Service Test mode LED.

3.Press ENTER , then use the arrow key to select the sub-mode ‘QUIC’, then press the ENTER key.

4.Press the down arrow key until ‘HGP.A’ is displayed.

5.Press the ENTER key. If the login menu is displayed, log in with the password. The default password is 0 1 1 1. Use the arrow keys to change each number’s value. Press the ENTER key after each number until finished.

6.Press the ENTER key so that ‘Off’ flashes.

7.Use the arrow keys to change the value to ‘On.’

8.Press the ENTER key.

9.Verify that the Cir. A minimum load valve (MLV) solenoid is energized.

10.Proceed to ‘HGP.B’ and ‘HGP.C’ (30XA400-500 only) and repeat Steps 4-9 for Cir. B MLV and Cir. C. MLV.

11.Once the outputs have been tested, the installation is com- plete. Return the Enable/Off/Remote contact switch to the desired position.

Copyright 2006 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

2

Catalog No. 04-53300010-01

Printed in U.S.A.

Form 30XA-6SI

Pg 8

12-06

Replaces: New

Tab

5c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 8
Contents 30XA Unit Size Accessory Part no Install the Solenoid Valve Tube AssemblyAccessory Package Usage Contents of Accessory Kit, Part No EFN900002700A Contents of Accessory Kit, Part No EFN900002800AContents of Accessory Kit, Part No EFN900002900A Dimensions of Tube Assemblies Provided in Accessory KitTtttt Typical Solenoid Valve Tube Assembly Installation Install HGBP/Pump Board and Control Wiring CB14HGBP/Pump Board 24 v Power Wiring CB14Configure Unit for Minimum Load Control OK button to confirm the input
Related manuals
Manual 80 pages 61.28 Kb

30XA080-500 specifications

The Carrier 30XA080-500 is a sophisticated air-cooled chiller designed for large commercial and industrial applications, renowned for its energy efficiency and reliability. This model is part of Carrier's extensive range of chillers, providing an optimal solution for space cooling needs while supporting sustainability goals.

One of the main features of the 30XA080-500 is its advanced scroll compressor technology. This design not only enhances the chiller's efficiency but also ensures quieter operation. The compressors operate with a high efficiency at partial loads, making the 30XA080-500 ideal for buildings with varying cooling demands. The unit also incorporates multiple compressors, allowing for enhanced reliability through redundancy; if one compressor fails, others can maintain performance.

The 30XA080-500 is equipped with high-performance evaporators and condensers which facilitate superior heat exchange. The unit features a fin-and-tube heat exchanger design, optimized for maximum surface area and minimal air resistance, thus enhancing overall performance. Moreover, the chiller is built with microchannel technology, which significantly reduces the refrigerant charge while improving efficiency through better heat transfer.

In terms of controls, the Carrier 30XA080-500 utilizes advanced VFD (Variable Frequency Drive) technology. This allows the system to adjust motor speed to match building loads, further increasing efficiency and reducing energy consumption. The intuitive control options enable users to monitor performance and make adjustments easily, helping optimize system operations in real time.

Another highlight of the 30XA080-500 is its environmentally conscious refrigerant, R-410A, which is known for its low Global Warming Potential (GWP). This makes the unit compliant with current and future environmental regulations, ensuring that users can operate within legal limits while reducing their carbon footprint.

The durability of the 30XA080-500 is enhanced by a rugged construction designed to withstand various weather conditions, making it suitable for outdoor installation. Insulated panels and protective coatings guard against corrosion, extending the lifespan of components and reducing maintenance costs.

In conclusion, the Carrier 30XA080-500 is a high-efficiency chiller that offers advanced technology, reliable performance, and environmental consciousness, making it an excellent choice for modern commercial buildings seeking to balance cooling needs with sustainability and energy savings. Its combination of innovative features positions it as a leader in the chiller market.