Carrier 30RB060-390 installation instructions Install the Solenoid Valve

Page 1

30RB060-390 Minimum Load Control Accessory

Installation Instructions

Part No: 00EFN900000100A

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equip- ment can be hazardous due to system pressures, electrical com- ponents and equipment location.

Only trained, qualified installers and service technicians should install, start up, and service this equipment.

When working on air-conditioning equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment.

Follow all safety codes. Wear safety glasses and work gloves. Use care in handling equipment.

WARNING

Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon- nect locations to alert others not to restore power until work is completed.

GENERAL

IMPORTANT: This accessory can only be used on units configured for Cooler Fluid Type (Configuration SERVFLUD = 1 [Water]). The minimum load control accessory (HGBP) is not allowed on units configured for Cooler Fluid Type (Configuration SERVFLUD = 2 [Brine]).

This control accessory reduces 30RB chiller capacities be- low the standard lowest capacity step. This capacity reduction provides more precise control of leaving fluid temperature during light load conditions.

The solenoid valve limits the amount of gas that can be bypassed from the condenser without impacting oil return.

One accessory package is required for 30RB060-190 units and for each module of duplex units 30RB315-390. Two accessory packages are required for 30RB210-300 units to accommodate connections for all three refrigerant circuits. See Table 1 for modular unit combinations.

Table 1 — Modular Unit Combinations

UNIT SIZE

MODULE A

MODULE B

30RBA315

30RBA160

30RBA160

30RBA330

30RBA170

30RBA160

30RBA345

30RBA170

30RBA170

30RBA360

30RBA190

30RBA170

30RBA390

30RBA190

30RBA190

NOTE: An “A” in the model number indicates the design series.

INSTALLATION

Examine the package contents for correct part numbers. If any of the components are damaged, file a claim with the shipping company and notify a Carrier representative.

See Table 2 for package contents. See Fig. 1 for dimensional drawings of tubes included in the kit.

The following material is field supplied:

1/2 in. OD copper tubing

standard 1/2 in. copper tube elbows and couplings as required

Install the Solenoid Valve

WARNING

Shut off all power to the unit. Lock out and safety-tag all disconnects. Remove refrigerant charge from the circuits using an approved refrigerant recovery device before proceeding with this installation. Follow good piping practices. Severe personal injury could result.

1.Shut off power to the unit.

2.Remove refrigerant charge from the unit.

3.Locate the factory-supplied stub on the discharge line for each circuit. Locate the 1/2 in. NPT pipe plugs at the blank end of the cooler for 30RB110 circuit B and for both circuits A and B on 30RB060-300 units. See Fig. 2.

4.Remove the 1/2 in. NPT pipe plugs from the blank end of the cooler. Use an appropriate thread sealing compound and install one 1 in. — 14 O-ring seal adapter for each circuit. Lightly lubricate each O-ring and attach a 5/8 in. O-ring seal tube assembly to each adapter. This nut should be torqued to 30 ft-lb (40 N- m). For 30RB110 circuit A size only, use a tubing cut- ter to cut off the end of the stub tube. See Fig. 3.

5.Assemble the hot gas bypass line in the following order:

a.Remove the discharge stub tube and braze the cor- rect beaded tube in place.

b.Braze the ball valve to the beaded tube.

c.Braze the solenoid valve into the line.

d.Using field-supplied tubing, connect the solenoid valve to the low side connection, either the cooler or the liquid line.

e.Clamp the 5/8-in. tube to the rail. See Fig. 4 and 5.

Use field-supplied 1/2 in. OD copper tubing and fit- tings (as required) to plumb from the solenoid valve outlet to either the adapter tube in the cooler or stub tube in the liquid line depending on unit size. Tube support brackets and 1/2 in. tubing clamps are provided with the kit. Install brackets to the bottom of the coil bases to support tubing.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53300047-01

Printed in U.S.A.

Form 30RB-16SI

Pg 1

3-10

Replaces: 30RB-4SI

Image 1
Contents Modular Unit Combinations Install the Solenoid ValveUnit Size Module a Module B Dimensions of Tubes Provided in Accessory Kit Contents of Accessory KitConfigure Unit for Minimum Load Control Install Control Wiring SeeConfigurationdescription 30RB110 30RB060-10030RB210-300 30RB120-190Main Base Board Wiring for Circuits a and B, 30RB060-300 Page Copyright 2010 Carrier Corporation

30RB060-390 specifications

The Carrier 30RB060-390 is a highly efficient rooftop air conditioning unit designed for commercial applications. This model is part of Carrier's comprehensive range of packaged rooftop units, recognized for their reliability, energy efficiency, and advanced technology features. Specifically engineered to meet diverse indoor air quality needs, the 30RB series provides an ideal solution for businesses seeking comfort cooling and heating in a single package.

One of the standout features of the 30RB060-390 is its energy efficiency. The unit is designed with an energy-efficient compressor and advanced heat exchange technology, often achieving high Seasonal Energy Efficiency Ratio (SEER) ratings. This means that businesses can benefit from lower energy bills while contributing to environmental sustainability. The unit can be configured to run on various electrical power sources, making it adaptable to different installation requirements.

The unit is equipped with a sophisticated microprocessor-based control system, allowing for precise temperature control and operation scheduling. This feature enhances user control, enabling adjustments to be made based on specific environmental needs. Additionally, the unit can be seamlessly integrated with advanced building management systems, which can optimize energy use and improve overall operational efficiency.

The Carrier 30RB060-390 also prioritizes durability and ease of maintenance. The unit's construction incorporates robust materials that withstand harsh weather conditions, ensuring long-term performance. Maintenance access is streamlined, with components strategically designed for easy serviceability, reducing downtime and service costs.

Another key characteristic of the 30RB series is its quiet operation. Engineered with sound-dampening technology and precise motor design, this unit minimizes noise levels, making it ideal for settings where a comfortable and distraction-free atmosphere is crucial, such as offices, schools, and hospitals.

In summary, the Carrier 30RB060-390 embodies a harmonious blend of efficiency, technology, and reliability. With features tailored for commercial use and considerations made for environmental impact, it stands out as a leading choice for rooftop air conditioning solutions. Investing in the 30RB060-390 ensures that businesses can enjoy optimal comfort while maintaining control over energy consumption and operational costs.