Installation and Configuration

Before you begin the installation, make sure that the site where you plan to install the expansion enclosure has standard power from an independent source or a rack power distribution unit with a UPS.

Safety Precautions

Always follow these safety precautions to avoid injury and damage to Storage Center equipment.

If equipment described in the document is used in a manner not specified by Dell, the protection provided by the equipment may be impaired. For your safety and protection, observe the rules described in the following sections.

NOTE: See the safety and regulatory information that shipped with each Storage Center component. Warranty information may be included within this document or as a separate document.

Installation Safety Precautions

Follow these safety precautions:

Dell recommends that only individuals with rack-mounting experience install an SC180 expansion enclosure in a rack.

You need at least two people to lift the expansion enclosure chassis from the shipping box and three people to install it in the rack. The empty chassis weighs approximately 62kg (137 lbs).

Make sure the expansion enclosure is fully grounded at all times to prevent damage from electrostatic discharge.

When handling the expansion enclosure hardware, you should use an electrostatic wrist guard (not included) or a similar form of protection.

The expansion enclosure chassis MUST be mounted in a rack; the following safety requirements must be considered when doing so:

The rack construction must be capable of supporting the total weight of the installed chassis and the design should incorporate stabilizing features suitable to prevent the rack tipping or being pushed over during installation or in normal use.

When loading a rack with chassis, fill from the bottom up; empty from the top down.

To avoid danger of the rack toppling over, do not slide more than one chassis out of the rack at a time.

The expansion enclosure must be operated with low-pressure rear exhaust installation [back pressure created by rack doors and obstacles not to exceed 5 Pascals (0.5 mm water gauge)].

The rack design should take into consideration the maximum operating ambient temperature for the unit, which is 35°C.

Unpacking Storage Center Equipment

Unpack the expansion enclosure and identify the items in your shipment.

4

Image 4
Contents Dell Storage Center Page Safety Warnings Other Information You May NeedSafety Precautions Installation and ConfigurationUnpacking Storage Center Equipment Installing the Expansion Enclosure in a Rack SC180 Expansion Enclosure ComponentsInstalling the Hard Drives Mount the Expansion Enclosure Chassis in the RackDdic Connecting the Power Cables Cabling the Expansion Enclosure to a Storage SystemPower Cables Turning on the Expansion EnclosureTechnical Specifications NOM Information Mexico OnlyDdic