Carrier 38AKS013-024 specifications Ð Refrigerant Piping Sizes Ð 60 Hz Units

Page 9

Table 4A Ð Refrigerant Piping Sizes Ð 60 Hz Units

 

LENGTH OF INTERCONNECTING PIPING, FT (M)

UNIT

0-15

15-25

25-50

50-75

75-100

(0-4.5)

(4.5-7.5)

(7.5-15)

(15-23)

(23-30)

38AKS

 

 

 

Line Size (in. OD)

 

 

 

 

 

 

 

 

 

 

 

L

S

L

S

L

S

L

S

L

S

013

1¤2

11¤8

1¤2

11¤8

5¤8

13¤8

5¤8

13¤8

5¤8

15¤8*

014

1¤2

11¤8

1¤2

13¤8

5¤8

13¤8

5¤8

15¤8*

7¤8

15¤8*

016

1¤2

13¤8

5¤8

13¤8

5¤8

15¤8

7¤8

15¤8

7¤8

21¤8*

024

5¤8

15¤8

5¤8

15¤8

7¤8

15¤8

7¤8

21¤8

7¤8

21¤8

LEGEND

L Ð Liquid

S Ð Suction

Close-coupled.

*Requires a double suction riser if 2 unloaders are used and the evaporator is below the condensing unit. See Table 4B and Fig. 4 for more information.

NOTES:

1.Pipe sizes are based on a 2 F (1.1 C) loss for liquid lines and a 1.5 F (0.8 C) loss for suction lines.

2.Pipe sizes are based on an equivalent length equal to the maxi- mum length of interconnecting piping plus 50% for ®ttings. A more accurate estimate may result in smaller sizes.

3.Line size conversion to mm:

in.mm

1¤2

12.7

5¤8

15.9

7¤8

22.2

11¤8

28.6

13¤8

34.9

15¤8

41.3

21¤8

54.0

Table 4B Ð Refrigerant Piping Sizes,

Double Suction Risers Ð 60 Hz Units

 

LENGTH OF INTERCONNECTING PIPING, FT (M)

UNIT

 

50-75

 

 

 

75-100

 

 

(15-23)

 

 

 

(23-30)

 

38AKS

 

 

 

 

 

 

 

Line Size (in. OD)

 

 

 

 

 

 

 

 

A

B

C

 

A

B

C

013

Ð

Ð

Ð

1

1¤8

13¤8

15¤8

014

11¤8

13¤8

15¤8

 

11¤8

13¤8

15¤8

016

Ð

Ð

Ð

1

3¤8

15¤8

21¤8

NOTES:

1.See Fig. 4 for ``A,'' ``B,'' and ``C'' dimensions.

2.No double suction risers are needed for unit size 024.

3.See Table 4A for line size conversion to mm.

Table 5A Ð Refrigerant Piping Sizes Ð 50 Hz Units

LENGTH OF INTERCONNECTING PIPING, FT (M)

COND

0-15

15-25

25-50

50-75

75-100

UNIT

(0-4.5)

(4.5-7.5)

(7.5-15)

(15-23)

(23-30)

38AKS

 

 

 

Line Size (in. OD)

 

 

 

 

L

S

L

S

L

S

L

S

L

S

013

1¤2

11¤8

1¤2

11¤8

5¤8

13¤8

5¤8

13¤8

5¤8

13¤8*

014

1¤2

11¤8

5¤8

13¤8

5¤8

13¤8

7¤8

15¤8*

7¤8

15¤8*

016

5¤8

13¤8

5¤8

13¤8

5¤8

15¤8*

7¤8

15¤8*

7¤8

15¤8*

024

5¤8

13¤8

5¤8

13¤8

5¤8

15¤8

7¤8

15¤8

7¤8

15¤8

*Requires a double suction riser if 2 unloaders are used and the evapo- rator is below the condensing unit. See Table 5B and Fig. 4 for more information.

NOTES:

1.Pipe sizes are based on 2 F (1.1 C) max loss for liquid lines and 1.5 F (0.8 C) max loss for suction lines, selected at maximum length for each interval and for matched systems at nominal rating con- ditions, nominal air¯ow.

2.Pipe sizes are based on an equivalent length equal to the maxi- mum length of interconnecting piping plus 50% for ®ttings. A more accurate estimate may result in smaller sizes.

3.See Table 4A for line size conversion to mm.

Table 5B Ð Refrigerant Piping Sizes,

Double Suction Risers Ð 50 Hz Units

 

LENGTH OF INTERCONNECTING PIPING FT (M)

COND

 

25-50

 

 

 

50-75

 

 

75-100

 

UNIT

 

(7.5-15)

 

 

(15-23)

 

 

(23-30)

 

38AKS

 

 

 

 

 

Line Size (in. OD)

 

 

 

 

 

A

 

B

 

C

A

 

B

C

A

 

B

C

013

Ð

 

Ð

Ð

Ð

Ð

 

Ð

1

1¤8

 

13¤8

15¤8

014

Ð

 

Ð

Ð

1

1¤8

 

13¤8

15¤8

11¤8

 

13¤8

15¤8

016

11¤8

 

13¤8

 

15¤8

11¤8

 

13¤8

15¤8

11¤8

 

13¤8

15¤8

NOTES:

1.See Fig. 4 for ``A,'' ``B,'' and ``C'' dimensions.

2.Double suction risers are not required for unit size 024.

3.See Table 4A for line size conversion to mm.

LEGEND

Suction Riser Without Trap

Suction Riser With Trap

Suction Line to Condensing Unit

Short Vertical Riser Into Condensing Unit:

38AKS013 Ð 1 1¤8 in. OD 38AKS014,016 Ð 1 3¤8 in. OD

38AKS024 Ð 1 5¤8 in. OD

Fig. 4 Ð Suction Line Piping

9

Image 9
Contents Contents Safety ConsiderationsInstallation Dimensions Component Locations Typical Ð Physical Data English, 60 Hz OIL Charge L Condenser Fans Ð Physical Data SI, 60 HzÐ Physical Data English, 50 Hz Ð Physical Data SI, 50 Hz Rig and Mount the Unit Weight DistributionComplete Refrigerant Piping Connections Liquid Line DataLength of Interconnecting PIPING, FT M Cond Length of Interconnecting PIPING, FT MLength of Interconnecting Piping FT M Ð Refrigerant Piping Sizes Ð 60 Hz UnitsLocation of Sight Glasses Filter Driers IFC NECLLSV2 Ð Unit ComprSystem Check PRE-START-UPÐ Electrical Data 3 Ph/50 Hz MCA ICFAdjust Refrigerant Charge START-UPPreliminary Checks 38AKS013 and 38AKS024 Charging Chart 38AKS014 Charging Chart 38AKS016 Charging Chart Operating Sequence ServiceLubrication Compressor ProtectionOutdoor Fan Problem Solution Compressor does not RUN TroubleshootingCompressor Stops on HIGH-PRESSURE Switch Compressor Cycles on LOW-PRESSURE SwitchTroubleshooting Copyright 1998 Carrier Corporation START-UP Checklist Preliminary InformationPre-Start-Up Start-Up

38AKS013-024 specifications

The Carrier 38AKS013-024 is a prominent series of packaged air conditioning units designed to achieve optimal performance across various applications. Engineered with advanced technologies, these units are ideal for both residential and light commercial spaces, offering reliable climate control in a compact design.

The main features of the Carrier 38AKS series include high-efficiency cooling and heating capabilities. With SEER ratings that meet or exceed industry standards, these units offer reduced energy consumption, making them an environmentally friendly choice. Furthermore, the Carrier 38AKS013-024 is equipped with a scroll compressor, which enhances reliability and reduces operating noise, creating a more comfortable indoor environment.

One of the standout technologies incorporated in the Carrier 38AKS series is its advanced microprocessor control system. This technology provides precise temperature control and allows for easy integration with smart home systems. Users can conveniently manage their indoor climate through remote access, ensuring comfort at all times.

Additionally, the 38AKS series boasts durable construction materials, ensuring longevity and sustained performance even in challenging environmental conditions. The units feature a galvanized steel cabinet with a rust-resistant finish, providing protection from the elements. This design also allows for easy access to internal components during maintenance, simplifying servicing.

In terms of characteristics, the Carrier 38AKS013-024 offers a range of cooling capacities, making it suitable for various space sizes and applications. The lightweight design facilitates easy installation, while the low noise levels ensure minimal disruption in residential settings. These units also come with environmentally friendly refrigerants, aligning with modern sustainability goals.

Carrier's commitment to quality and performance is evident in the 38AKS series. With their combination of innovative technology, energy efficiency, and robust construction, the Carrier 38AKS013-024 units represent an excellent choice for those seeking a reliable and efficient air conditioning solution. Whether for home or light commercial use, these units promise consistent comfort and satisfaction.