Philips ICS2G9LS120SO, ICS2G9LS26U Ordering Information, Options/Accessories, Specifications

Page 2

Louver IC Series

Page 2 of 2

Model No. ICS2G9LS26U120SO

LER = FP - 53.4 IW - 57.2 BF - 0.87 Comparative yearly lighting energy cost per

1000 lumens = $4.49

Report Number: G00027

Catalog Number: ICS2G9LS26U120S0

Lamp: (2) F32 T8

Luminaire: IC 2' X 2' Troffer with 3X3 Spectular Louver

Ballast: M2-RN-T81LL-D-120

Report is based on 2750 Lumens per lamp. Efficiency: 66.2%

CIE Type-Direct-Indirect

 

 

 

 

Plane:

 

 

 

 

0-Deg

 

90-Deg

Spacing Criteria:

 

 

1.2

 

 

1.2

Shielding Angles:

 

 

23

 

 

23

Plane:

 

 

 

 

0-Deg

 

90-Deg

Luminous Length:

 

21.720

 

21.720

COEFFICIENTS OF UTILIZATION –

 

 

ZONAL CAVITY METHOD. EFFECTIVE

 

FLOOR CAVITY REFLECTANCE 0.20

 

 

 

 

 

 

 

 

 

 

 

RC

 

80

 

 

50

 

 

30

 

RW

70

50

30

50

30

10

50

30

10

1

73

71

69

67

65

63

64

63

61

2

68

63

59

60

57

54

57

55

53

3

62

56

51

53

49

46

51

48

46

4

57

50

45

48

43

40

46

43

40

5

53

45

40

43

38

35

42

38

35

6

49

41

35

39

34

31

38

34

31

7

45

37

31

35

31

27

35

30

27

8

42

34

28

32

28

25

32

27

24

9

40

31

26

30

25

22

29

25

22

10

37

29

24

28

23

20

27

23

20

LUMINANCE DATA IN CANDELA/SQ. METER

AVERAGE AVERAGE AVERAGE AVERAGE

IN DEG.

0-DEG. 45-DEG. 90-DEG.

45

4686.

4497.

5416.

55

4147.

4557.

5917.

65

1779.

2378.

2502.

75

312.

353.

367.

85

161.

202.

161.

2' x 2' Recessed Fluorescent, 3" 9 or 16 Cell Parabolic Louver Static, 2-6" U Lamp T8

CANDELA DISTRIBUTION

 

0.0

45.0

90.0

FLUX

0

1552

1552

1552

 

5

1545

1546

1556

147

15

1465

1501

1530

423

25

1341

1353

1369

625

35

1165

1132

1146

716

45

943

905

1090

743

55

677

744

966

683

65

214

286

301

271

75

23

26

27

30

85

4

5

4

5

90

0

0

0

 

 

 

 

 

 

TYPICAL V.C.P.'s

 

 

Mounting Height

 

 

 

Lengthwise

Crosswise

 

 

 

Room

Luminaires

Luminaires

Size

0 Deg Plane

90 Deg Plane

 

8.5

10

13

16

8.5

10

13

16

30x30

75

69

60

57

72

66

57

53

40x40

80

74

67

60

77

71

64

57

60x30

79

74

67

61

76

71

64

58

60x60

82

78

72

65

80

75

70

63

100x100

85

82

78

72

84

80

76

70

 

 

 

 

ZONAL LUMEN SUMMARY

 

 

 

 

 

 

 

 

ZONE

LUMENS

% LAMP

 

% FIXT

00-030

 

1195

 

 

21.7

 

32.8

00-040

 

1911

 

 

34.7

 

52.5

00-060

 

3336

 

 

60.7

 

91.6

00-090

 

3643

 

 

66.2

 

100.0

90-180

 

0000

 

 

0.0

 

000.0

00-180

 

3643

 

 

66.2

 

100.0

Ordering Information

Explanation of Catalog Number. Example: ICS2G9LS26UUNVHI

S

2

S

2

6U

-

IC Series:

Body Style:

Fixture

Ceiling Type:

Number of

Recessed

S=Static

Width

G= Grid

Cells:

Parabolic

 

 

(lay-in T bar)

9=3 rows

 

 

suitable for

 

 

T= Slot grid

of 3

Thermal

 

 

 

16=4 rows

Insulation

 

 

 

of 4

Contact

 

 

 

 

 

 

 

 

 

IC

Standard IC Parabolic

 

 

 

 

 

 

IY

For NYC Code – I.B.E.W. Manufactured

 

 

 

 

IX

For NYC Code – Local 3 Manufactured

 

5½" Deep Body

 

 

 

 

 

 

 

 

 

Louver Finish:

Single "V"

Lamp

 

L = Low iridescence

Reflector

Quantity

 

Semi-specular

 

 

2=2 lamps

 

(standard)

 

 

 

 

 

P =Low iridescence

 

 

 

 

 

Specular

 

 

 

 

 

 

 

 

Lamp Type/

W =White Baked

 

 

 

 

 

 

Fixture Length:

Enamel

 

 

 

 

 

 

6"U T8

 

 

 

 

 

 

 

 

 

 

2 Lamp Only

 

 

 

 

 

(Nominal 24")

 

 

 

 

Options:

 

 

 

 

Lamps

Voltage:

 

 

 

 

Flex

120, 277 or

 

 

EM Pack

UNV=120-277

 

 

Fuse

 

Ballast

Type:

 

(Consult your

1-2 Lamp Elec. T8

<20THD <10THD representative)

SO *

H

*

LOL T8 Dimming

PS

 

I

*Instant Start Standard

Other dimming options, consult factory.

NOTE:I

For T8 UNV, you must use H Ballast Code.

Options/Accessories

Plaster Frame: Catalog Number: PF24.

Radio Interference Filter: To order one RIF per fixture; SUFFIX: R. To order one RIF per ballast; SUFFIX: B.

Fusing: Internal fast-blow fusing. SUFFIX A. Internal slow-blow fusing. SUFFIX C.

Electrical Wiring Options: Consult factory.

Drywall Kit: Order Catalog Number: FK92X4. (Request Folio OA30-10 Rev. A).

Chicago Plenum: SUFFIX: C.

Specifications

Specifications (continued)

Finish: Chassis exterior–black baked polyester enamel. Cavity–white baked polyester enamel minimum 86% reflectance. Rust preventative undercoating. Louver–low iridescence semi-specular anodized vertical grain alu- minum reflector sheet is standard.

Electrical: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°.

Labels: I.B.E.W. UL and ULc Listed.

This product may have a mercury containing lamp. Manage in accord with Disposal Laws.

See: www.lamprecycle.org

Performance: In an installation of 2 lamp 31W luminaires in a room cavity ratio of 1, reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .71. To prevent glare the VCP shall be not less than 63 either lengthwise or crosswise (at 100fc level) and the average brightness at 65° shall not exceed 2502 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 67.2%. Materials: Chassis parts are die-formed code gauge cold rolled steel. Housing is ribbed for rigidity with side rails hemmed over and housing ends turned-in for safe handling. Louver is pre-anodized aluminum.

Job Information Type:

For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish.

www.lightolier.com © 2008 a Philips Group

SECTION 7/Folio Q80-15

Lightolier is a Philips group brand

Image 2
Contents Exposed T-grid ceiling DimensionsMounting Methods Drywall kitOrdering Information Options/AccessoriesSpecifications