INSTALLATION

Shut off all power to this equipment prior to installation. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed. Failure to disconnect power from equipment prior to installation could result in serious personal injury or death.

1.Inspect package contents for missing or damaged parts. File a claim with the shipping agency if parts are damaged and notify your local Carrier representative if any item is missing.

2.Determine the new location for the cooler. Ensure that the new location supports the cooler and economizers weights and that there is enough room for service access and tube removal. See Tables 4A and 4B to determine refrigeration line sizes. See Table 5 for cooler and economizers weights. See Fig. 4A-5B for cooler and economizers dimensions, tube removal clearances, and service areas.

3.Open and tag all electrical disconnects.

Cooler and Economizer Removal — The cooler and economizers are accessible from the cooler side of the unit. To remove the cooler and economizers from the unit, complete the following steps:

1.Remove refrigerant from all circuits using standard refrigeration practices. Refer to unit nameplate or installa- tion instructions for refrigerant quantities.

2.Disconnect the cooler heater wiring, and conduit if equipped.

3.Remove entering and leaving chilled water temperature thermistors. Make sure to label thermistors as they are removed. See Fig. 6.

4.Disconnect and label the chilled water flow switch cable from the chilled water flow switch located on the leaving water nozzle. See Fig. 6.

5.Disconnect the suction pressure transducer cables from the transducers. Make sure to label cables as they are removed. See Fig. 6.

NOTE: The suction pressure transducers (SPT) do not neces- sarily need to be removed. However, use care in protecting the

SPTs throughout the removal and remote installation processes, as the SPTs are an important part of the remote installation.

6.Disconnect the electronic expansion valve (EXV) cables from the EXVs at each economizer. Make sure to label cables as they are removed. See Fig. 6.

NOTE: The 30XA080 units do not utilize an economizer. In this case, only the EXVs are present.

7.Unbolt the cooler suction flanges from the cooler. Tempo- rary supports may be needed to support the suction pipes. See Fig 6.

8.At each circuit’s economizer, cut the liquid lines going to the economizer assembly before the manual shutoff valve (see Fig. 6, cut 1, circuits A and B). Cut the cooler liquid lines between the manual shutoff valve and the cooler (see Fig. 6, cut 2, circuits A and B). Cut the economizer lines between the manual shutoff valve and the sensors (see Fig. 6, cut 3, circuits A and B).

9.Remove the screws from the feet of each economizer. Save all of the screws. Remove the economizers by care- fully sliding them out the cooler side of the unit.

10.Remove the screws from the cooler feet. Save all of the screws. Slide the cooler slightly to the left to clear the refrigerant tubing.

11.Remove the cooler by carefully sliding the cooler out the cooler side of the unit.

Because 30XA systems use polyolester oil, which can ab- sorb moisture, it is important to minimize the amount of time that the refrigeration system is left exposed to the at- mosphere. Minimizing the exposure time will reduce the amount of moisture that could possibly damage the unit. The removal instructions minimize the exposure time to prevent this type of damage. The remote installation in- structions outline a dehydration process to counteract any exposure that might have occurred.

Before installation of the field-supplied piping, the piping must be thoroughly cleaned and free of dirt, debris, oil, and welding residue. Presence of these objects will cause severe damage to the compressors or other components of the re- frigeration system.

4

Image 4
Contents Installation Instructions Refrigeration Piping Connections Material English Accessory Package ContentsRefrigeration Piping Connections Material SI Liquid Line Economizer Line Suction LineInstallation Refrigeration Line Sizes English Cooler and Economizer WeightsRefrigeration Line Sizes SI 30XA080-120 Cooler Dimensions 30XA180-240 Cooler Dimensions 30XA090-160 Economizer Dimensions Typical Cooler Piping-Cooler Side View 30XA140, 160 Shown Remote Cooler and Economizers Installa Page Materials Required for Steel Piping Flange Connections Circuit a Circuit B 140Circuit a Circuit B 280 Additional Refrigerant Charges Required134a Refrigerant 30XA080-120 All Circuits Construction Detail 30XA140-160 Circuit BRED. TEE Reducing Tee STR ELLS- Street ElbowsFlange and Gasket Mounting Locations Thermistor Connections

00EFN900003000A specifications

The Carrier 00EFN900003000A is a cutting-edge heating, ventilation, and air conditioning (HVAC) unit designed to meet the varying demands of both residential and commercial applications. Its innovative features and advanced technologies make it a leader in energy efficiency and performance.

One of the main features of the Carrier 00EFN900003000A is its variable-speed compressor, which allows for precise temperature control. This technology enables the unit to adjust its output based on the specific cooling or heating needs of the space, ensuring optimal comfort and minimizing energy consumption. The variable-speed operation results in quieter performance as the system smoothly ramps up or down rather than operating at a constant speed.

This model is equipped with advanced refrigerant technology, utilizing environmentally friendly R-410A refrigerant. This hydrofluorocarbon (HFC) refrigerant is designed to reduce ozone depletion potential while maintaining high energy efficiency. The Carrier 00EFN900003000A includes high-efficiency coils that enhance heat exchange, boosting the system's overall performance and durability.

Another notable characteristic of the Carrier 00EFN900003000A is its integrated smart technology. This unit can be connected to modern smart home systems, allowing users to monitor and control their HVAC system from anywhere via smartphone applications. The ability to receive alerts for maintenance needs and system performance helps ensure that the unit operates at peak efficiency over its lifespan.

Design-wise, the Carrier 00EFN900003000A boasts a compact and lightweight structure, making it suitable for various installation scenarios, from tight residential spaces to larger commercial environments. Its robust build quality ensures longevity and reliability, even in harsh weather conditions.

Furthermore, the unit features a user-friendly interface that simplifies operation and programming. With programmable settings and adjustable fan speeds, users can easily customize their comfort levels while maximizing energy efficiency.

In summary, the Carrier 00EFN900003000A represents a significant advancement in HVAC technology, offering variable-speed operation, eco-friendly refrigerants, smart connectivity, and user-centric design. This model stands out as an ideal choice for consumers seeking energy efficiency and superior comfort in their indoor environments.