Carrier 040-420 specifications

Page 51

Code 30 Reset input failure (4 to 20 mA)

Code 31 Demand limit input failure (4 to 20 mA)

These codes apply only if unit is configured for these functions. If 4-20 mA signal is less than 4 or more than 20 mA, reset or demand limit function is disabled and unit functions normally. If mA signal returns to the acceptable range, function is automatically enabled.

Code 32 Loss of communication with compressor relay module (DISO-LV)

Code 33 Loss of communication with EXV relay module (DSIO-EXV)

If communication is lost with either of these modules, unit shuts down without pumpout. This alarm resets auto- matically when communication is restored. The unit starts up normally after alarm condition is reset. Probable cause of condition is a faulty or improperly connected plug, wir- ing error, or faulty module.

Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vat supplying the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the 12.5-vat transformer supplying the DSIO-EXV module; or the 24-vat transformer supplying PS 1 for the transformers. These transformers should not be grounded, or serious damage to controls can result. Check to be sure the transformers are not grounded.

NOTE: If a blank PSI0 module is downloaded without be- ing connected to the modules DSIO, this alarm is energized.

Code 34 Loss of communication with 4 In/4 Out module

This applies only if one or more of the following options are used:

0 external temperature reset

4-20 mA temperature reset

external switch controlled dual set point switch controlled demand limit

4-20 mA demand limit

hot gas bypass

If communication is lost with 4 IN/4 OUT module, the unit shuts off automatically, after finishing pumpout. Reset of alarm is automatic when communication is restored. Start-up after alarm is remedied follows a normal sequence. Proba- ble cause of condition is a faulty or improperly connected plug, wiring error, or faulty module.

Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vat supplying the PSIO, DSIO-LV, or 4 IN/4 OUT; the 12.5vat trans- former supplying the DSIO-EXV module, or the 24-vat trans- former supplying PS 1 for the transformers. These transformers should not be grounded, or serious damage to controls can result. Check to be sure the transformers are not grounded.

Code 36 Low refrigerant pressure, Circuit A Code 37 Low refrigerant pressure, Circuit B

If suction pressure transducer senses a pressure below set point for more than 5 minutes at start-up or more than 2 minutes during normal operation, affected circuit shuts down without going through the pumpout process. Reset is automatic when pressure reaches 10 psig above set point if there have been no previous occurrences of this fault on the same day. If this is a repeat occurrence on same day, then reset is manual, with LOCAL/ENABLE-STOP-CCN switch, Factory configured set point is 27 psig for standard chillers and 12 psig for brine chillers.

Possible causes of fault are low refrigerant charge, faulty EXV, plugged filter drier, or faulty transducer.

Code 38 Failure to pump out, Circuit A Code 39 Failure to pump out, Circuit B

The pumpout process is terminated when saturated suc- tion temperature is 10” F (5.5” C) below temperature at be-

ginning of pumpout, or 10” F (5.5” C) below leaving water temperature or reaches a saturated suction temperature of -15 F (-26 C). If appropriate saturated suction temperature is not met within 3 minutes (on 2 consecutive tries}, circuit

shuts down without pumpout. Reset is manual with LOCAL/ ENABLE-STOP-CCN Switch, and start-up follows normal sequence.

Possible causes for this alarm are a bad thermistor or trans- ducer or a faulty EXV.

Code 40 Low oil pressure, Circuit A Code 41 Low oil pressure, Circuit B

If oil pressure differential is less than set point for more than 2 minutes at start-up, or more than one minute during normal operation, affected circuit shuts down without go-

ing through pumpout process, Reset is manual with LOCAL/ ENABLE-STOP-CCN switch, and start-up follows normal sequence. Factory configured differential oil pressure is 6 psig.

Possible causes of fault are faulty compressor, EXV, crank- case heater or transducer, refrigerant overcharge, insuffi- cient oil charge, or tripped circuit breaker.

Code 42 Cooler freeze protection

If cooler entering or leaving water temperature is below 34 F (1.1 C) for water or more than 8” F (4.4” C) below set point for brine, unit shuts down without pumpout. Chilled water pump continues to run if controlled by chiller con- trols. Reset is automatic when leaving water temperature reaches 6” F (3” C) above set point, providing there has been no prior occurrence of this fault the same day. If fault has occurred previously the same day, reset is manual with LOCAL/ENABLE-STOP-CCN switch.

Possible causes of fault are low water flow or faulty thermistor.

Code 43 Low water flow

If any compressors are operating and entering water tem- perature is 3” F (1.7” C) or more below leaving water tem- perature for more than one minute, unit shuts down without pumpout. Chilled water pump also shuts down. Reset is manual with LOCAL/ENABLE-STOP-CCN switch, and start-up follows normal sequence.

This is a suitable method for sensing low water flow be- cause entering water thermistor is in the cooler shell and responds more quickly to compressor operation than the leav- ing water thermistor in the leaving water nozzle, Possible

causes of fault are faulty chilled water pump, control or thermistor.

Code 44 Low cooler suction temperature, Circuit A Code 45 Low cooler suction temperature, Circuit B

If saturated suction temperature is less than 32 F (0°C) and is 20” F (11” C) for water or 30” F (16” C) for brine or more below leaving fluid temperature, mode 14 is dis- played. Unit continues to run, but additional compressors are not allowed to start, If condition persists for more than 10 minutes, fault code is displayed, and unit shuts down without pumpout. Reset is manual with LOCAL/ENABLE- STOP-CCN switch, and start-up follows normal sequence.

Possible causes of fault are low refrigerant charge, plugged filter drier, or a faulty EXV or thermistor.

Code 46 High suction superheat, Circuit A Code 47 High suction superheat, Circuit B

If EXV is fully open, suction superheat is greater than 75 F (42 C) and saturated evaporator temperature is less than MOP (maximum operating pressure) for more than 5 minutes, unit shuts down after normal pumpout process. Reset is manual with LOCAL/ENABLE-STOP-CCN switch, and start-up follows normal sequence.

51

Image 51
Contents Contrc Unit Model Unit Sizes and Modular CombinationsField Keypaddisplay Ground Fault InterrupterSource PSI RELAY, BThermistors LOCAL/ENABLE-STOP-CCN Switch Positions and OperationCompressor Protection Control Module Cpcs Thermistor and Transducer LocationsSteps CapacityControl Steps Loading Sequence a Loading Sequence B Unit ControlCapacity Control Steps, 040-070 cant 060A\~**HzLoading Sequence a Loading Sequence B Unit Capacity Control Steps, 040-070 cant Oy&yaFBI Aiti 08Aqy,yA4l&pi’ BP’ StepsLoading Loading Sequence B Unit Control Loading Sequence a Loading Equence B Unit Altt BittWtf2Z$’ AlttAmrox ’tt$-t&Z3 Displacement Compressors UWrW Arwox A2.p $#l 110 50 Hz Loading Sequence a Quence B Unit ControlAlt,Blv Displacement Compressors Mvrox Loading Equence aEquence B 130, 240A Awrox Drt,t130, 24OA 130,24OALoading Equence a Unit Attll’A2.p T3gLoading Sequence a Sequence B Unit $$V Control Size Steps LOAD11Loadin Sequence B Unit Al% Al’,BI Displacement Compressors UVvW PWprox8514w B2,B3Loading Sequence B Unit 30GT Displacement Compressors Awox Capacity Control Steps, 225, 250,280Loac \IG Sequence a Loading Sequence B Unit Capacity Control Steps, 225, 250,280 cant Loac30GT Loading Sequence B Unit Control Capacity Control Steps, 225, 250, 280 cant250 1G Sequence aFAN Arrangement FAN Numbers Contactor Controlled Condenser Fan Sequence30GT250 60 Hz Condenser Fan Sequence cantFAN Arrangement FAN Numbers ~jACToRKeypad and Display Module Usage Keypad and Display Module Also Called HsioOperation Keypad Display Description Entry Response Accessing Functions and SubfunctionsFunctions and Subfunctions FunctionsKeypad Directory Analog Keypad Directory cant Status cantSubfunction Keypadentry Display Comment PressureHgbra Subfunction Outputs DisplaySubfunction Keypad Entry Display Comment Outputs OutputsQzq Keypad Directory cant Test cantSubfunction Keypad Entry Display Comment Override Clock SelectKeypad Directory Schedule cant Keypad Directory cant Service cord Keypad Directory cant Operationat and Mode Display Codes Example 1 Reading Alarm CodesLocal on Cool Alarms Modes Local on M O D E Example 2 Reading Current Operating ModesKeypad Display Example 3 Using Test Function Example 4 Reading and Changing Chilled Water Set PointKeypad Display Comments Entry Response Crsti Example 5 Using Return Water Temperature ResetKeypad Display Comments CRST2Reset Reference Temperature Outdoor AIR 1OR Space Temp Example 6 Changing Reset TypeEKE Keypad Display Entry Response FLD CFG Ertyp Lstyp DemandPpiq Example 8 Setting Time of Day Day of Week Demand LimitingMAX Demand Kimax = Adjustable Field Configurations Factory Configuration KeystrokesDisplay Example 9 Using the Schedule FunctionExample 10 Holiday Schedule Function Example 9 Using the Schedule Function cantComplete Unit Stoppage Complete unit stop Typical Stoppage Faults and Reset TypesAction Taken Probable Cause N T R O L Alarm CodesPage Page R ’ S ’ SlTnanz SNB SwitchCGF Compressor Contactor RelayFig. IOD 24-V Safety Circuit Wiring 225, 250, and 280 Units Electronil c Expansion Valve EXV Page Thermistor and Pressure Transducer Locations Refrigerant Temperature Sensor T7, T8 040-210 SuctionAssociated Modular Units Pressure Transducer 2i.b Voltage Resistance Drop Voltage DropLine Transducer Each Compressor Equalizer OIL Pressure Suction Pressure Sight GlassPSIO, SIO Address Selector Control ModulesProcessor Module Psio Sensor Bus Wiring CommunicationsComm Troubleshooting Standard and Accessory Unloaders 1NO. of AccessoryCircuit Circuit B Or2 30GN190-210 3OGT225,250,280 080-110 SO/SO Hz and 130 60 Hz Accessory Unloader Control WiringTLN HgbprSTAGE2 Contactor Switch Circuit Breaker TransformerLmyTEF4 ModuleElJ7-16 ModuleJ7-15 ThermistorRemote Dual Set Point Control InstallationPage Page Copyright 1994 Carrier Corporation

040-420 specifications

The Carrier 040-420 is a highly regarded commercial HVAC unit specifically designed for efficient heating and cooling in medium- to large-sized buildings. Known for its reliability and advanced technology, this system is ideal for a variety of applications ranging from offices to industrial spaces.

One of the main features of the Carrier 040-420 is its energy efficiency. The unit utilizes advanced compressors and a high-efficiency heat exchanger, which work together to minimize energy consumption while maximizing performance. This is crucial in today’s energy-conscious environment, as businesses strive to reduce operational costs and their carbon footprint. The unit also boasts a high SEER (Seasonal Energy Efficiency Ratio) rating, making it an attractive option for those looking to lower their utility bills.

Equipped with advanced inverter-driven technology, the Carrier 040-420 allows for precise control of indoor climate conditions. This means that the system can adjust its output according to the actual cooling or heating demand of the space, resulting in enhanced comfort and reduced energy waste. The inverter technology also contributes to quieter operation, allowing for a more pleasant indoor environment.

Another feature that sets the Carrier 040-420 apart is its smart controls. The unit can be integrated with Carrier’s Building Automation Systems, enabling remote monitoring and management. This allows facility managers to optimize energy use and immediately respond to any performance issues. Additionally, the unit is compatible with various control interfaces, making it easy for users to adjust settings or schedule operations according to the building's occupancy patterns.

The robust design of the Carrier 040-420 ensures longevity and durability, even in harsh environmental conditions. Its weatherproof casing protects the internal components, enhancing the unit's performance and reliability over time. Maintenance is simplified with accessible design features, allowing technicians to conduct service checks and repairs without extensive downtime.

Overall, the Carrier 040-420 stands out as a modern HVAC solution that combines energy efficiency, advanced technologies, and user-friendly features. Its commitment to performance and sustainability makes it an ideal choice for businesses looking to enhance comfort while being mindful of their energy consumption. With its blend of innovation and reliability, the Carrier 040-420 continues to be a preferred option in the commercial HVAC market.