Carrier 040-420 specifications Electronil c Expansion Valve EXV

Page 56

1.

Electronic Expansion Valve

EXV OPERATION - These valves control the flow of liq- uid refrigerant into the cooler. They are operated by pro- cessor to maintain a specified superheat at lead compressor entering gas thermistor (located between compressor motor and cylinders). There is one EXV per circuit. See Fig. 11.

High-pressure liquid refrigerant enters valve through bot- tom. A series of calibrated slots are located in side of ori- fice assembly. As refrigerant passes through orifice, pres- sure drops and refrigerant changes to a 2-phase condition (liquid and vapor). To control refrigerant flow for different operating conditions, sleeve moves up and down over ori- fice, thereby changing orifice size. Sleeve is moved by a linear stepper motor. Stepper motor moves in increments and is controlled directly by processor module. As stepper motor rotates, motion is transferred into linear movement by lead screw. Through stepper motor and lead screws, 760 discrete steps of motion are obtained. The large num- ber of steps and long stroke result in very accurate control of refrigerant flow.

The biF\ subfunction shows EXV valve position as

a percent of full open. Position should change constantly while unit operates. If a valve stops moving for any reason (mechanical or electrical) other than a processor or ther- mistor failure, the processor continues to attempt to open or close the valve to correct the superheat. Once the calcu- lated valve position reaches 60 (fully closed) for 040-210 and associated modular units, 145 (fully closed) for 225, 250, and 280 units, or 760 (fully open) it remains there. If EXV position reading remains at 60, 145 or 760, and the thermistors and pressure transducers are reading correctly, the EXV is not moving. Follow EXV checkout procedure below to determine cause.

The EXV is also used to limit cooler suction temperature to 50 F (10 C). This makes it possible for chiller to start at higher cooler water temperatures without overloading com- pressor. This is commonly referred to as MOP (maximum operating pressure), and serves as a load limiting device to prevent compressor motor overloading, This MOP or load limiting feature enables the 30G FlotronicT’ II chillers to operate with up to 95 F (35 C) entering water temperatures during start-up and subsequent pull-down.

STEPPER

‘DC)

CHECKOUT PROCEDURE - Follow steps below to di- agnose and correct EXV problems.

1, Check EXV driver outputs. Check EXV output signals at appropriate terminals on EXV driver module (see Fig. 12) as follows:

Connect positive test lead to terminal 1 on EXV driver. Set meter for approximately 20 vdc. Enter outputs

subfunction of test function by pressing riF[ , then advance to EXVA test by pressing q 8 times. Press

T;ip--p-&q*The driver should drive the circuit A EXV fully open. During next several seconds connect nega- tive test lead to pins 2, 3, 4 and 5 in succession. Voltage should rise and fall at each pin. If it remains constant at a voltage or at zero v, remove connector to valve and recheck.

Press m H to close circuit A EXV. If a problem still

exists, replace EXV driver module. If voltage reading is correct, expansion valve should be checked. Next, test EXVB. Connect positive test lead to pin 7 and the neg- ative test lead to pin 8, 9, 10, 11 in succession during EXVB test.

2.Check EXV wiring, Check wiring to electronic expan- sion valves from terminal strip on EXV driver. See Fig. 12.

a.Check color coding and wire connections. Make sure they are connected to correct terminals at driver and EXV plug connections.

b.Check for continuity and tight connection at all pin terminals.

c.Check plug connections at driver and at EXVs to be sure EXV cables are not crossed.

E X V D R I V E R

BOARD - J4

I

O R I F I C E

ASSEMBLY (INSIDE PISTON

SLEEVE)

Fig. 11 - Electronil c Expansion Valve (EXV)

T

EXV - Electronic Expansion Valve

Fig. 12 - EXV Cable Connections to

EXV Driver Module, DSIO (EXV)

3.Check resistance of EXV motor windings. Remove plug at 54 terminal strip and check resistance between com- mon lead (red wire, terminal D) and remaining leads, A, B , C, and E (see Fig. 12). Resistance should be 25 ohms -1- 2 ohms.

Control of valve is by microprocessor. A thermistor and a pressure transducer located in lead compressor are used to determine superheat. The thermistor measures tem- perature of the superheated gas entering the compressor cylinders. The pressure transducer measures refrigerant pressure in the suction manifold. The microprocessor con- verts pressure reading to a saturation temperature. The difference between temperature of superheated gas and saturation temperature is the superheat.

56

Image 56
Contents Contrc Unit Sizes and Modular Combinations Unit ModelKeypaddisplay Ground Fault Interrupter Source PSIRELAY, B FieldLOCAL/ENABLE-STOP-CCN Switch Positions and Operation Compressor Protection Control Module CpcsThermistor and Transducer Locations ThermistorsCapacity Control StepsLoading Sequence a Loading Sequence B Unit Control StepsLoading Sequence a Loading Sequence B Unit Capacity Control Steps, 040-070 cant060A\~**Hz FBI Capacity Control Steps, 040-070 cantOy&ya A4l&pi’ Aiti08Aqy,y Steps BP’Loading Loading Sequence B Unit Control Altt Bitt Wtf2Z$’Altt Loading Sequence a Loading Equence B Unit$-t&Z3 Amrox’tt Alt,Blv Displacement Compressors UWrW Arwox A2.p $#l 110 50 HzLoading Sequence a Quence B Unit Control Equence B Displacement Compressors MvroxLoading Equence a Awrox Drt,t 130, 24OA130,24OA 130, 240AAttll’ Loading Equence a UnitLoading Sequence a Sequence B Unit A2.pT3g $$V LOAD11 Control Size StepsLoadin Sequence B Unit Displacement Compressors UVvW PWprox 8514wB2,B3 Al% Al’,BILoading Sequence B Unit Loac \IG Sequence a Loading Sequence B Unit 30GT Displacement Compressors AwoxCapacity Control Steps, 225, 250,280 30GT Capacity Control Steps, 225, 250,280 cantLoac Capacity Control Steps, 225, 250, 280 cant 2501G Sequence a Loading Sequence B Unit ControlCondenser Fan Sequence FAN Arrangement FAN Numbers Contactor ControlledCondenser Fan Sequence cant FAN Arrangement FAN Numbers~jACToR 30GT250 60 HzKeypad and Display Module Also Called Hsio Keypad and Display Module UsageAccessing Functions and Subfunctions Functions and SubfunctionsFunctions Operation Keypad Display Description Entry ResponseKeypad Directory Keypad Directory cant Status cant Subfunction Keypadentry Display CommentPressure AnalogSubfunction Outputs Display Subfunction Keypad Entry Display Comment OutputsOutputs HgbraKeypad Directory cant Test cant Subfunction Keypad Entry Display Comment OverrideClock Select QzqKeypad Directory Schedule cant Keypad Directory cant Service cord Keypad Directory cant Example 1 Reading Alarm Codes Operationat and Mode Display CodesKeypad Display Local on Cool Alarms Modes Local on M O D EExample 2 Reading Current Operating Modes Keypad Display Comments Entry Response Example 3 Using Test FunctionExample 4 Reading and Changing Chilled Water Set Point Example 5 Using Return Water Temperature Reset Keypad Display CommentsCRST2 CrstiExample 6 Changing Reset Type Reset Reference Temperature Outdoor AIR 1OR Space TempEKE Ppiq Keypad Display Entry ResponseFLD CFG Ertyp Lstyp Demand MAX Demand Kimax = Example 8 Setting Time of Day Day of WeekDemand Limiting Factory Configuration Keystrokes Adjustable Field ConfigurationsExample 9 Using the Schedule Function DisplayExample 9 Using the Schedule Function cant Example 10 Holiday Schedule FunctionTypical Stoppage Faults and Reset Types Complete Unit Stoppage Complete unit stopAlarm Codes Action Taken Probable Cause N T R O LPage Page ’ Sl R ’ STnanz Switch CGFCompressor Contactor Relay SNBFig. IOD 24-V Safety Circuit Wiring 225, 250, and 280 Units Electronil c Expansion Valve EXV Page Thermistor and Pressure Transducer Locations Associated Modular Units Refrigerant Temperature Sensor T7, T8 040-210Suction Pressure Transducer 2i.b Voltage Drop Voltage Resistance DropEqualizer OIL Pressure Suction Pressure Sight Glass Line Transducer Each CompressorControl Modules PSIO, SIO Address SelectorSensor Bus Wiring Communications Processor Module PsioComm Troubleshooting Circuit Circuit B Or2 30GN190-210 3OGT225,250,280 Standard and Accessory Unloaders1NO. of Accessory Accessory Unloader Control Wiring 080-110 SO/SO Hz and 130 60 HzHgbpr TLNContactor Switch Circuit Breaker Transformer LmyTEF4Module STAGE2Module J7-15Thermistor ElJ7-16Installation Remote Dual Set Point ControlPage Page Copyright 1994 Carrier Corporation

040-420 specifications

The Carrier 040-420 is a highly regarded commercial HVAC unit specifically designed for efficient heating and cooling in medium- to large-sized buildings. Known for its reliability and advanced technology, this system is ideal for a variety of applications ranging from offices to industrial spaces.

One of the main features of the Carrier 040-420 is its energy efficiency. The unit utilizes advanced compressors and a high-efficiency heat exchanger, which work together to minimize energy consumption while maximizing performance. This is crucial in today’s energy-conscious environment, as businesses strive to reduce operational costs and their carbon footprint. The unit also boasts a high SEER (Seasonal Energy Efficiency Ratio) rating, making it an attractive option for those looking to lower their utility bills.

Equipped with advanced inverter-driven technology, the Carrier 040-420 allows for precise control of indoor climate conditions. This means that the system can adjust its output according to the actual cooling or heating demand of the space, resulting in enhanced comfort and reduced energy waste. The inverter technology also contributes to quieter operation, allowing for a more pleasant indoor environment.

Another feature that sets the Carrier 040-420 apart is its smart controls. The unit can be integrated with Carrier’s Building Automation Systems, enabling remote monitoring and management. This allows facility managers to optimize energy use and immediately respond to any performance issues. Additionally, the unit is compatible with various control interfaces, making it easy for users to adjust settings or schedule operations according to the building's occupancy patterns.

The robust design of the Carrier 040-420 ensures longevity and durability, even in harsh environmental conditions. Its weatherproof casing protects the internal components, enhancing the unit's performance and reliability over time. Maintenance is simplified with accessible design features, allowing technicians to conduct service checks and repairs without extensive downtime.

Overall, the Carrier 040-420 stands out as a modern HVAC solution that combines energy efficiency, advanced technologies, and user-friendly features. Its commitment to performance and sustainability makes it an ideal choice for businesses looking to enhance comfort while being mindful of their energy consumption. With its blend of innovation and reliability, the Carrier 040-420 continues to be a preferred option in the commercial HVAC market.