Function List
A Group: Standard functions | [X:: AllowedNot allowed ] |
|
|
|
|
| Default |
|
| Run mode | |
Function Code |
| Name | Range | Unit |
| edit | |||
|
| Frequency upper limit setting |
|
| Lo | Hi | |||
| A061 | 0.0/Freq. lower limit setting to maximum freq. | 0.0 | 0.0 | 0.0 | Hz | X |
| |
| A261 | Frequency upper limit setting, 2nd motor | 0.0/Freq. lower limit setting (2nd) to maximum freq. (2nd) | 0.0 | 0.0 | 0.0 | Hz | X |
|
| A062 | Frequency lower limit setting | 0.0/Start freq. to freq. upper limit setting | 0.0 | 0.0 | 0.0 | Hz | X |
|
| A262 | Frequency lower limit setting, 2nd motor | 0.0/Start freq. (2nd) to freq. upper limit setting (2nd) | 0.0 | 0.0 | 0.0 | Hz | X |
|
PID Control | A063 | Jump (center) frequency setting 1 | 0.0 to 400. | 0.0 | 0.0 | 0.0 | Hz | X |
|
A064 | Jump (hysteresis) frequency setting 1 | 0.0 to 10.0 | 0.5 | 0.5 | 0.5 | Hz | X |
| |
|
| ||||||||
| A065 | Jump (center) frequency setting 2 | 0.0 to 400. | 0.0 | 0.0 | 0.0 | Hz | X |
|
| A066 | Jump (hysteresis) frequency setting 2 | 0.0 to 10.0 | 0.5 | 0.5 | 0.5 | Hz | X |
|
| A067 | Jump (center) frequency setting 3 | 0.0 to 400. | 0.0 | 0.0 | 0.0 | Hz | X |
|
| A068 | Jump (hysteresis) frequency setting 3PID Enable | 0.0 to 10.0 | 0.5 | 0.5 | 0.5 | Hz | X |
|
| A071 | PID Enable | 00(Disable)/01(Enable) | 00 | 00 | 00 | - | X |
|
| A072 | PID proportional gain | 0.2 to 5.0 | 1.0 | 1.0 | 1.0 | - |
|
|
| A073 | PID integral time constant | 0.0 to 150.0 | 1.0 | 1.0 | 1.0 | sec |
|
|
PID Control | A074 | PID derivative time constant | 0.00 to 100.0 | 0.00 | 0.00 | 0.00 | sec |
|
|
A075 | PV scale conversion | 0.01 to 99.99 | 1.00 | 1.00 | 1.00 | - | X |
| |
|
| ||||||||
| A076 | PV source setting | 00([OI] terminal)/01([O] terminal)/02(RS485)/10(Calculation result) | 00 | 00 | 00 | - | X |
|
| A077 | Reverse PID action | 00(OFF)/01(ON) | 00 | 00 | 00 | - | X |
|
| A078 | PID output limit | 0.0 to 100.0 | 0.0 | 0.0 | 0.0 | % | X |
|
| A081 | AVR function select | 00(Enable)/01(Disable)/02(Enabled except during deceleration) | 00 | 00 | 02 | - | X | X |
AVR function | A082 | AVR voltage select | 200V class: 200/215/220/230/240 | 200/400 | 200/400 | 200/400 | V | X | X |
| 400V class: 380/400/415/440/460/480 | ||||||||
|
|
|
|
|
|
|
|
| |
Automatic Energy | A085 | Operation mode selection | 00 | 00 | 00 | - | X | X | |
Saving | A086 | Energy saving mode tuning | 0.0 to 100.0 | 50.0 | 50.0 | 50.0 | % | X | X |
| A092 | Acceleration (2) time setting | 0.01 to 99.99/100.0 to 999.9/1000. to 3000. | 15.00 | 15.00 | 15.00 | sec |
|
|
| A292 | Acceleration (2) time setting, 2nd motor | 0.01 to 99.99/100.0 to 999.9/1000. to 3000. | 15.00 | 15.00 | 15.00 | sec |
|
|
| A093 | Deceleration (2) time setting | 0.01 to 99.99/100.0 to 999.9/1000. to 3000. | 15.00 | 15.00 | 15.00 | sec |
|
|
| A293 | Deceleration (2) time setting, 2nd motor | 0.01 to 99.99/100.0 to 999.9/1000. to 3000. | 15.00 | 15.00 | 15.00 | sec |
|
|
| A094 | Select method to switch to Acc2/Dec2 profile | 00(2CH from input terminal)/01(transition freq.) | 00 | 00 | 00 | - | X | X |
Operation mode and | A294 | Select method to switch to Acc2/Dec2 profile, 2nd motor | 00(2CH from input terminal)/01(transition freq.) | 00 | 00 | 00 | - | X | X |
acc./dec. function | A095 | Acc1 to Acc2 frequency transition point | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz | X | X |
| A295 | Acc1 to Acc2 frequency transition point, 2nd motor | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz | X | X |
| A096 | Dec1 to Dec2 frequency transition point | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz | X | X |
| A296 | Dec1 to Dec2 frequency transition point, 2nd motor | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz | X | X |
| A097 | Acceleration curve selection | 00 | 00 | 00 | - | X | X | |
| A098 | Deceleration curve selection | 00 | 00 | 00 | - | X | X | |
| A101 | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz | X |
| |
| A102 | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz | X |
| |
External freq. tuning | A103 | 0. to 100. | 0. | 0. | 0. | % | X |
| |
| A104 | 0. to 100. | 100. | 100. | 100. | % | X |
| |
| A105 | 00(Use setting value)/01(0Hz) | 01 | 01 | 01 | - | X |
| |
| A141 | A input select for calculate function | 00(Digital operator)/01(Keypad potentiometer) | 01 | 01 | 01 | - | X |
|
| A142 | B input select for calculate function | 02(O input)/03(OI input)/04(RS485) | 02 | 02 | 02 | - | X |
|
| A143 | Calculation symbol | 00 | 00 | 00 | - | X |
| |
| A145 | ADD frequency | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz |
|
|
Frequency | A146 | ADD direction select | 00(Plus)/01(Minus) | 00 | 00 | 00 | - | X |
|
caluculation | A151 | Pot. input active range start frequency | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz | X |
|
| A152 | Pot. input active range end frequency | 0.0 to 400.0 | 0.0 | 0.0 | 0.0 | Hz | X |
|
| A153 | Pot. input active range start current | 0.0 to 100.0 | 0.0 | 0.0 | 0.0 | % | X |
|
| A154 | Pot. input active range end current | 0.0 to 100.0 | 100. | 100. | 100. | % | X |
|
| A155 | Pot.input start frequency enable | 00(Use offect (A151 value))/01(Use 0Hz) | 01 | 01 | 01 | - | X |
|
b Group: | [X:: AllowedNot allowed ] |
|
|
|
|
| Default |
|
| Run mode | ||
Function Code |
| Name | Range |
| Unit |
| edit | |||
|
|
|
|
| Lo | Hi | ||||
| b001 | Selection of automatic restart mode | 00(Alarm output)/01(Restart at 0Hz)/ | 00 | 00 | 00 | - | X |
| |
| 02(Resume after freq. matching)/03(Resume freq. matching then trip) |
| ||||||||
|
|
|
|
|
|
|
|
| ||
| b002 | Allowable | 0.3 to 25.0 | 1.0 | 1.0 | 1.0 | sec | X |
| |
| b003 | Retry wait time before motor restart | 0.3 to 100.0 | 1.0 | 1.0 | 1.0 | sec | X |
| |
| b004 | Instantaneous power failure / | 00(Disable)/01(Enable) | 00 | 00 | 00 | - | X |
| |
| alarm enable |
| ||||||||
|
|
|
|
|
|
|
|
| ||
Restart after | b005 | Number of restarts on power failure / | 00(Restart 16 times)/01(Always restart) | 00 | 00 | 00 | - | X |
| |
trip events |
| |||||||||
instantaneous power |
|
|
|
|
|
|
|
| ||
| Start frequency to be used in case of frequency |
|
|
|
|
|
|
| ||
failure | b011 | 00(frequency at previous shutoff)/01(Max. Hz)/02(Set frequency) | 00 | 00 | 00 | - | X | X | ||
|
|
|
|
|
|
|
|
| ||
| b012 | Electronic thermal setting |
| Rated current | A | X |
| |||
|
|
| 0.2*Rated current to 1.0*Rated current |
|
|
|
|
|
| |
| b212 | Electronic thermal setting, 2nd motor |
| Rated current | A | X |
| |||
| b013 | Electronic thermal characteristic | 00(Reduced torque)/01(Constant torque)/02(Reduced torque 2) | 01 | 01 | 00 | - | X |
| |
| b213 | Electronic thermal characteristic, 2nd motor | 01 | 01 | 00 | - | X |
| ||
|
|
| ||||||||
| b021 | Overload restriction operation mode | 00(Disable)/01(Enable)/02(Enable for during acceleration) | 01 | 01 | 01 | - | X |
| |
| b221 | Overload restriction operation mode, 2nd motor | 01 | 01 | 01 | - | X |
| ||
|
|
| ||||||||
| b022 | Overload restriction setting | 0.2*Rated current to 1.5*Rated current | 1.5*Rated current | A | X |
| |||
| b222 | Overload restriction setting, 2nd motor | A | X |
| |||||
|
|
|
|
|
| |||||
| b023 | Deceleration rate at overload restriction | 0.1 to 3000.0 | 1.0 | 30.0 | 1.0 | sec | X |
| |
Overload restriction | b223 | Deceleration rate at overload restriction, 2nd motor | 1.0 | 30.0 | 1.0 | sec | X |
| ||
|
| |||||||||
| b028 | Overload restriction source selection | 00(b022/b222 setting | 00 | 00 | 00 | - | X |
| |
| b228 | Overload restriction source selection, 2nd motor | 00 | 00 | 00 | - | X |
| ||
|
|
| ||||||||
| b029 | Deceleration rate of frequency | 0.1 to 3000.0 | 0.5 | 0.5 | 0.5 | sec | X | X | |
| b030 | Current level of frequency | 0.2*Rated current to 2.0*Rated current | Rated current | A | X | X | |||
|
|
| 00([SFT] input blocks all edits)/01([SFT] input blocks edits except |
|
|
|
|
|
| |
Lock | b031 | Software lock mode selection | F001 and Multispeed parameters/02(No access to edits)/03(No | 01 | 01 | 01 | - | X |
| |
access to edits except F001 and |
| |||||||||
|
|
|
|
|
|
|
|
| ||
|
|
| level access,including b031) |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|