Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
1.If equipped with a crankcase heater, energize a minimum of 24 hr before starting unit. To energize heater only, set thermostat OFF and close electrical disconnect to outdoor unit.
2.Fully open liquid and vapor service valves.
3.Unit is shipped with valve stem(s) front seated and caps installed. Replace stem caps after system is opened to refrig- erant flow. Replace caps finger tight and tighten additional 1/6 turn using a backup wrench on valve body flats to prevent distortion of sheet metal.
4.Close electrical disconnects to energize system.
5.Set room thermostat at desired temperature.
6.Set room thermostat to HEAT or COOL and fan to ON or AUTO mode, as desired. Operate unit for 15 minutes. Check system refrigerant charge.
7.Factory charge is shown on unit rating plate. Adjust charge in cooling mode by following procedure shown in charging table. Check charge in heating mode by following procedure shown on heating check chart. Both are located on unit.
•
•A flashing LED on phase monitor indicates reverse rotation. (See Fig. 8 and Table 2.)
•This will not allow contactor to be energized.
•Disconnect power to unit and interchange 2 field wiring leads on unit contactor.
SEQUENCE OF OPERATION — With power supplied to indoor and outdoor units, transformer is energized. Defrost control board is equipped with
Cooling
On a call for cooling, the thermostat makes circuits
NOTE: If the phasing is incorrect, the contactor will not be energized. To correct the phasing, interchange any two of the three power connections on the field side.
When thermostat is satisfied, its contacts open,
NOTE: If indoor unit is equipped with a
Heating
On a call for heating, the thermostat makes circuits
A00010
Fig. 8—Phase Monitor Control
Table 2—Phase Monitor LED Indicators
LED | STATUS | |
OFF | No call for compressor | |
operation | ||
| ||
FLASHING | Reversed phase | |
ON | Normal |
Should the temperature continue to fall,
When the thermostat is satisfied, its contacts open,
→Quiet Shift
Quiet Shift is a
When Quiet Shift switch is placed in ON position, and a defrost is initiated, the following sequence of operation will occur. Revers- ing valve will energize, compressor will turn off for 30 sec, then turn back on to complete defrost. At the start of heating cycle after conclusion of defrost mode, reversing valve will
→Defrost
The defrost control is a time/temperature control which includes a
To initiate a forced defrost, two options are available depending on the status of the defrost thermostat.
If defrost thermostat is closed, speedup pins (J1) must be shorted by placing a flat head screwdriver in between for 5 sec and releasing, to observe a complete defrost cycle. When the Quiet Shift switch is selected, compressor will be turned off for two 30 sec intervals during this complete defrost cycle as explained previously. When Quiet Shift switch is in factory default OFF position, a normal and complete defrost cycle will be observed.
6