NOTE: Install
ROUTE GROUND AND POWER WIRES
Remove access panel and control box to gain access to unit wiring. Extend wires from disconnect through
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning can result in an electric shock, fire, or death.
CONNECT GROUND AND POWER WIRES
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 5.
DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES
CONTACTOR
FIELD POWER
WIRING
3 PHASE ONLY | BLUE |
FIELD GROUND
WIRING
GROUND
LUG
A94025
Fig. 5—Line Power Connections
CONNECT CONTROL WIRING
Route 24v control wires through
Use No. 18 AWG
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer,
NOTE: Use of available 24v accessories may exceed the mini- mum 40va power requirement. Determine total transformer load- ing and increase the transformer capacity or split the load with an accessory transformer as required.
FINAL WIRING CHECK
IMPORTANT: Check factory wiring and
Step 10—Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to outdoor unit. A crankcase heater is required if refrigerant tubing is longer than 50 ft.
Step 11—Install Electrical Accessories
Refer to the individual instructions packaged with kits or acces- sories when installing.
Step 12—Start-Up
To prevent compressor damage or personal injury, observe the following:
•Do not overcharge system with refrigerant.
•Do not operate unit in a vacuum or at negative pressure. •Do not disable
In scroll compressor applications: •Dome temperatures may be hot.
To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
Follow these steps to properly start up the system:
1.Fully back seat (open) liquid- and
2.Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps
3.Close electrical disconnects to energize system.
4.Set room thermostat to desired temperature. Be sure set point is below indoor ambient temperature.
5.Set room thermostat to HEAT or COOL and fan control to ON or AUTO, as desired. Operate unit for a minimum of 15 minutes. Check system refrigerant charge.
•A flashing LED on phase monitor indicates reverse rotation. (See Fig. 7 and Table 2.)
This will not allow contactor to be energized.
•Disconnect power to unit and interchange 2
Step 13—Check Charge
Factory charge is shown on
4