Carrier 38YSA instruction manual Accessory Usage, Make Electrical Connections

Page 4

Table 1—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)

UNIT

LIQUID

 

VAPOR

 

VAPOR (LONG LINE)

SIZE

Connection Diameter

 

Tube Diameter

Connection Diameter

 

Tube Diameter

Connection Diameter

Tube Diameter

024

3/8

 

3/8

5/8

 

5/8

5/8

3/4

030, 036

3/8

 

3/8

3/4

 

3/4

3/4

7/8

042, 048

3/8

 

3/8

7/8

 

7/8

7/8

7/8

NOTES:

1.Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult Residential Split System Long-Line Application Guideline.

2.Do not apply capillary tube indoor coils to these units.

For buried-line applications greater than 36 in., consult your local distributor.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED INDOOR UNIT

Outdoor unit contains correct system refrigerant charge for opera- tion with indoor unit of same size when connected by 15 ft of field-supplied or factory-accessory tubing. Check refrigerant charge for maximum efficiency.

REFRIGERANT TUBING

Connect tubing to fittings on outdoor unit vapor and liquid service valves. (See Table 1.) Use refrigerant grade tubing.

SWEAT CONNECTION

To avoid valve damage while brazing, service valves must be wrapped in a heat-sinking material such as a wet cloth.

Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

Step 9—Make Electrical Connections

To avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed.

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.

NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.

NOTE: Use copper wire only between disconnect switch and unit.

NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.

ROUTE GROUND AND POWER WIRES

Remove access panel and control box cover to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

Table 2—Accessory Usage

 

REQUIRED FOR

REQUIRED FOR

ACCESSORY

LOW-AMBIENT

LONG-LINE

APPLICATIONS

APPLICATIONS*

 

 

(BELOW 55°F)

(OVER 50 FT)

Crankcase Heater

Yes

Yes

Evaporator Freeze Thermostat

Yes

No

Accumulator

No

No

Compressor Start Assist

Yes

Yes

Capacitor and Relay

 

 

MotorMaster® Control,

 

 

or

Yes

No

Low-Ambient Pressure Switch

 

 

Wind Baffle

See Low-Ambient Instructions

No

Support Feet

Recommended

No

Liquid-Line Solenoid Valve

 

See Long-Line

or

No

Application

Hard Shutoff TXV

 

Guideline

Ball Bearing Fan Motor

Yes‡

No

 

 

 

*For tubing line sets between 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline.

‡ Required for Low-Ambient Controller (full modulation feature) and MotorMaster Control only.

4

Image 4
Contents Check Equipment and Job Site Unpack UnitDimensions Install on a Solid, Level Mounting PadClearance Requirements Operating AmbientsCheck Defrost Thermostat Thermostatic Expansion ValveMake Piping Connections Accessory Usage Make Electrical ConnectionsStart-Up Install Electrical AccessoriesCompressor Crankcase Heater Programmable Other HP Thermostat VAC COM Not Used Trouble Optional Outdoor Sensor Connection Smart Heat Pump W2D W2T JW1 Wiring Diagram Notes Heating only Procedure Cooling only Procedure ExampleCheck Charge Required Liquid-Line Temperature F Final Checks

38YSA specifications

The Carrier 38YSA is a cutting-edge cooling solution designed to meet the demands of modern residential and commercial applications. Renowned for its energy efficiency and reliable performance, the 38YSA series represents the pinnacle of Carrier’s commitment to innovation in HVAC technology.

One of the standout features of the Carrier 38YSA is its energy efficiency. It utilizes advanced inverter technology, allowing it to adjust its cooling output based on the specific needs of the indoor environment. This technology not only reduces energy consumption but also minimizes fluctuations in temperature, providing a more consistent and comfortable living or working space. The unit achieves impressive SEER (Seasonal Energy Efficiency Ratio) ratings, making it an environmentally friendly choice.

The 38YSA is equipped with a variable-speed compressor, which optimizes performance by operating at different speeds. This capability allows the system to ramp up or down in accordance with the cooling load, ensuring optimal comfort and minimizing energy usage. This technology also translates to quieter operation, making the 38YSA ideal for residential neighborhoods and low-noise environments.

In terms of features, the Carrier 38YSA incorporates smart controls that can be operated remotely via mobile devices. This feature provides users with the flexibility to manage their cooling systems from anywhere, optimizing comfort while on the go. The user-friendly interface allows for easy programming of temperature schedules, further enhancing energy savings and comfort.

Durability is another characteristic that sets the Carrier 38YSA apart. The unit is engineered with robust materials and components designed to withstand harsh weather conditions. Its corrosion-resistant casing and high-quality condenser coils ensure longevity and reliable performance over the years.

Furthermore, the 38YSA is designed with eco-friendly refrigerants, contributing to a reduction in global warming potential, which aligns with increasing environmental regulations. The commitment towards sustainability is evident in Carrier’s entire product line, emphasizing the importance of creating energy-efficient and eco-conscious cooling systems.

Overall, the Carrier 38YSA is a sophisticated and efficient cooling solution, integrating advanced technologies to deliver optimal comfort, reliability, and energy savings. Its blend of innovative features, durable design, and environmental responsibility makes it a top choice for anyone seeking effective air conditioning solutions.