Carrier Essential Guidelines for 50JS Heat Pumps: Clearances and Specifications

Page 3

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

 

INCHES

[mm]

TOP OF UNIT

14.00

[355.6]

DUCT SIDE OF UNIT

2.00

[50.8]

SIDE OPPOSITE DUCTS

14.00

[355.6]

BOTTOM OF UNIT

0.50

[12.7]

ELECTRIC HEAT PANEL

36.00

[914.4]

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

 

INCHES

[mm]

 

EVAP. COIL ACCESS SIDE

36.00

[914.0]

 

POWER ENTRY SIDE

36.00

[914.0]

 

(EXCEPT FOR NEC REQUIREMENTS)

 

 

 

UNIT TOP

48.00

[1219.2]

 

SIDE OPPOSITE DUCTS

36.00

[914.0]

 

DUCT PANEL

12.00

[304.8]

*

NEC. REQUIRED CLEARANCES.

 

INCHES

[mm]

BETWEEN UNITS, POWER ENTRY SIDE

42.00

[1066.8]

UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00

[914.0]

UNIT AND BLOCK OR CONCRETE WALLS AND OTHER

 

 

GROUNDED SURFACES, POWER ENTRY SIDE

42.00

[1066.8]

*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.

C99006

 

 

UNIT WEIGHT

UNIT HEIGHT

 

CENTER OF GRAVITY

 

UNIT

ELECTRICAL CHARACTERISTICS

IN. [MM]

 

 

IN. [MM]

 

 

 

 

 

 

 

 

lb

kg

"A"

X

 

Y

 

Z

 

 

 

 

 

 

 

 

 

 

50JS048

208/230-1-60, 208/230-3-60, 460-3-60

353

160.1

38.98 [990.2]

20.5 [520.7]

 

20.6 [523.8]

 

17.0 [431.8]

 

 

 

 

 

 

 

 

 

 

50JS060

208/230-1-60, 208/230-3-60, 460-3-60

418

189.6

38.98 [990.2]

19.5 [495.3]

 

19.8 [501.7]

 

17.0 [431.8]

50JX042

208/230-1-60, 208/230-3-60, 460-3-60

350

158.8

40.98 [1040.9]

21.0 [533.4]

 

20.5 [520.7]

 

16.6 [421.6]

 

 

 

 

 

 

 

 

 

 

50JX048

208/230-1-60, 208/230-3-60, 460-3-60

355

161.0

40.98 [1040.9]

20.0 [508.0]

 

21.3 [539.8]

 

18.0 [457.2]

 

 

 

 

 

 

 

 

 

 

50JX060

208/230-1-60, 208/230-3-60, 460-3-60

428

194.1

42.98 [1091.7]

21.0 [533.4]

 

20.0 [508.0]

 

17.6 [447.0]

Fig. 3Ð50JS048-060/50JX042-060 Unit Dimensions

3

Image 3
Contents Safety Considerations Receiving and InstallationMaintenance TroubleshootingElectrical Characteristics Unit Weight Unit Height Center of Gravity50JX048 IN. MM 50JS04850JS060 50JX042Unit Size ODS Catalog Number Receiving and InstallationÐGeneral ÐCheck EquipmentÐRig and Place Unit InstallationÐProvide Unit Support ÐProvide ClearancesÐSelect and Install Ductwork Unit Maximum WeightÐProvide for Condensate Disposal BÐPhysical Data AÐPhysical DataC99013 ÐInstall Electrical ConnectionsC99061 C99030A00073 ÐWiring SchematicsA00074 A00075 TDR Time Delay Relay Thermostat Heating Tran TransformerAÐElectrical DataÐ50JS RLA LRA FLAMocp → BÐElectrical DataÐ50JX Rated Load Amps Full Load AmpsLocked Rotor Amps Minimum Circuit Amps Mocp Maximum Overcurrent ProtectionSTART-UP Special Procedures for 208-V OperationÐStart-Up Adjustments PRE-START-UPÐTypical Heat Pump Operation, Heating Mode Checking and Adjusting Refrigerant Charge AÐWet Coil Air Delivery Unit 50JS 018-060 Deduct 10% forUnit Motor Speed External Static Pressure IN. WG BÐWet Coil Air Delivery Unit 50JX 024-060 Deduct 10% for Speed Indoor Airflow and Airflow AdjustmentsC00031 MaintenanceC00030 C00032C99032 C99031C99033 C99035AIR Filter Indoor Blower and MotorOutdoor FAN System Information C99097C99029 Symptom Cause Remedy ÐCooling and Heating Troubleshooting ChartSTART-UP Checklist Remove and Store in JOB File Cooling and Heating Troubleshooting Chart contdPage Page Book Tab 5a 5a Catalog No Form 50JS,JX-1SI Replaces 50JX-2SI

50JS specifications

The Carrier 50JS is a high-performance rooftop unit designed for commercial applications, combining advanced technology with energy efficiency to deliver optimal heating and cooling performance. Its compact design allows for easy installation, making it an ideal choice for various settings such as retail spaces, schools, and office buildings.

One of the standout features of the Carrier 50JS is its innovative energy efficiency. Equipped with a high-efficiency scroll compressor, it significantly reduces energy consumption while providing reliable climate control. This model boasts a commendable SEER (Seasonal Energy Efficiency Ratio) rating, which translates to lower utility bills and a reduced carbon footprint, meeting modern energy efficiency standards.

The 50JS unit utilizes R-410A refrigerant, an environmentally friendly option that contributes to its low global warming potential compared to traditional refrigerants. This aligns with Carrier's commitment to sustainability and reducing environmental impact.

Another significant characteristic of the 50JS is its advanced controls and intelligent building integration capabilities. The unit comes with a microprocessor-based control system that allows for precise temperature management and can be easily integrated into building automation systems. This feature enhances user experience, providing real-time data and better management of HVAC operations.

Noise reduction technology is also a key design focus of the Carrier 50JS. The unit incorporates sound-attenuating materials and features that minimize operational noise, making it suitable for noise-sensitive environments like offices and educational institutions.

In terms of air quality, the 50JS offers various filtration options, including high-efficiency filters that remove airborne particulates. This results in cleaner, healthier indoor air, which is crucial for occupant comfort and well-being.

Furthermore, the rooftop unit is built to withstand harsh weather conditions, featuring a durable cabinet constructed from galvanized steel with a corrosion-resistant finish. This enhances the unit's longevity and reliability over time.

In conclusion, the Carrier 50JS rooftop unit stands out in the commercial HVAC market due to its energy efficiency, advanced controls, quiet operation, and robust design. It represents a blend of state-of-the-art technology and practical features, making it a preferred choice for those looking to invest in reliable and sustainable climate control solutions.