Carrier 25HCB3, 25HCC5 Outdoor Unit Connected To Factory Approved Indoor Unit, Accessory Usage

Page 3

Table 1 – Accessory Usage

 

REQUIRED FOR LOW--- AMBIENT

REQUIRED FOR

REQUIRED FOR

Accessory

COOLING APPLICATIONS

SEA COAST APPLICATIONS

LONG LINE APPLICATIONS*

 

(Below 55°F / 12.8°C)

(Within 2 miles / 3.22 km)

 

 

 

 

 

 

Accumulator

Standard

Standard

Standard

Ball Bearing Fan Motor

Yes{

No

No

Compressor Start Assist Capacitor and

Yes

Yes

No

Relay

 

 

 

 

 

 

 

Crankcase Heater

Yes

Yes

No

 

 

 

 

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

Yes

Yes

Isolation Relay

Yes

No

No

Liquid Line Solenoid Valve

No

See Long--- Line Application

No

Guideline

 

 

 

 

 

 

 

Motor MasterControl or

Yes

No

No

Low Ambient Switch

 

 

 

 

 

 

 

Support Feet

Recommended

No

Recommended

*For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Piping and Longline Guideline. { Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.

Outdoor Unit Connected To Factory Approved Indoor Unit

Outdoor unit contains correct system refrigerant charge for operation with approved ARI rated indoor unit when connected by

15ft (4.57 m) of field-supplied or factory-accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.

Refrigerant Tubing and Sweat Connections

Connect vapor tube to fitting on outdoor unit vapor service valves (see Table 2). Connect liquid tubing to adapter tube on liquid service valve. Use refrigerant grade tubing.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Service valves must be wrapped in a heat-sinking material such as a wet cloth while brazing.

Remove plastic retainer holding outdoor piston in liquid service valve, leaving the piston and piston retainer inside the valve. Connect sweat/flare adapter provided, to valve. (See Fig. 4.) Connect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Do not use soft solder (materials which melt below 800°F/427°C). Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

Table 2 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

UNIT SIZE

LIQUID

RATED VAPOR*

Connection

Tube

Connection

Tube

 

Diameter

Diameter

Diameter

Diameter

 

 

 

 

 

018, 024

3/8

3/8

5/8

5/8

030, 036

3/8

3/8

3/4

3/4

042, 048

3/8

3/8

7/8

7/8

060, 061

3/8

3/8

7/8

1-1/8

*Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.

Notes:

1.Do not apply capillary tube indoor coils to these units.

2.For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.1 m) vertical differential, refer to the Residential Piping and Longline Guideline using Puron refrigerant.

Install Liquid Line Filter Drier Indoor

Refer to Fig. 5 and install filter drier as follows:

1.Braze 5 in. (127 mm) liquid tube to the indoor coil.

2.Wrap filter drier with damp cloth.

3.Braze filter drier to 5 in. (127 mm) long liquid tube from step 1.

4.Connect and braze liquid refrigerant tube to the filter drier.

A05227

Fig. 5 - Liquid Line Filter Drier

25HCB3 / 25HCC5

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Installation of filter drier in liquid line is required.

A05226

Fig. 4 - Liquid Service Valve

3

Image 3
Contents CUT Hazard Safety ConsiderationsInstallation Recommendations Electrical Shock HazardOperating Ambient Install on a Solid, Level Mounting PadCheck Equipment and Job Site Clearance RequirementsRefrigerant Tubing and Sweat Connections Install Liquid Line Filter Drier IndoorAccessory Usage Outdoor Unit Connected To Factory Approved Indoor UnitCompressor Crankcase Heater Make Electrical ConnectionsInstall Electrical Accessories Start-UpFollow these steps to properly start up system Final Checks Heating Check Chart ProcedureCare and Maintenance Check ChargePuronr R-410A Quick Reference Guide Catalog No 25HCB 3SI

25HCC5, 25HCB3 specifications

The Carrier 25HCB3 and 25HCC5 are technologically advanced HVAC systems designed to meet the needs of modern residential and commercial spaces. These models stand out for their efficiency, reliability, and eco-friendliness, making them excellent choices for anyone looking to enhance indoor comfort while minimizing energy consumption.

One of the main features of the Carrier 25HCB3 and 25HCC5 is their exceptional SEER (Seasonal Energy Efficiency Ratio) rating, which signifies a higher cooling efficiency compared to traditional air conditioning systems. These units leverage Carrier's innovative design to deliver cooling and heating solutions that are tailored to various climate conditions, ensuring optimal performance year-round.

Both models utilize a variable-speed compressor, which allows them to adjust their cooling output based on the specific needs of the space. This technology not only enhances comfort by providing consistent temperatures but also reduces energy consumption, contributing to lower utility bills. The variable-speed operation is particularly beneficial during transitional seasons, where less intensive cooling is required.

In addition to their variable-speed capabilities, the 25HCB3 and 25HCC5 offer advanced filtration systems designed to improve indoor air quality. These systems can effectively capture airborne allergens, dust, and particulates, creating a healthier living environment. Moreover, users can opt for enhanced filtration options, which utilize HEPA filters for even greater allergen removal.

Another key characteristic of these models is their quiet operation. The Carrier 25HCB3 and 25HCC5 are engineered with sound-dampening features that minimize operational noise. This is especially advantageous for residential applications where tranquility is valued.

Durability is also a hallmark of Carrier systems. The 25HCB3 and 25HCC5 are built with robust materials and advanced protective mechanisms, ensuring that they can withstand the rigors of various weather conditions and provide reliable service for years to come.

In terms of smart technology, these models are compatible with Carrier's smart thermostat solutions, allowing users to monitor and control their HVAC systems remotely. This connectivity enhances user convenience and promotes energy efficiency by enabling users to adjust settings based on their schedules and needs.

Overall, the Carrier 25HCB3 and 25HCC5 represent a significant advancement in HVAC technology, combining high efficiency, advanced features, and user-friendly operation. Whether for residential or commercial use, these systems provide a comprehensive solution for anyone seeking reliable and effective climate control.