Carrier 25HCC5, 25HCB3 Make Electrical Connections, Compressor Crankcase Heater

Page 4

25HCB3 / 25HCC5

Evacuate Refrigerant Tubing and Indoor Coil

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 6.

5000

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

LEAK IN

3500

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM

3000

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

MICRONS2000

 

 

 

 

 

VACUUM TIGHT

1500

 

 

 

 

 

 

 

 

 

 

TOO WET

1000

 

 

 

 

 

TIGHT

500

 

 

 

 

 

 

 

 

 

 

DRY SYSTEM

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

MINUTES

 

 

 

A95424

Fig. 6 - Deep Vacuum Graph

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, makings sure wire ties on feeder tubes are secure and tight.

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.

NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.

Make Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Do not supply power to unit with compressor terminal box cover removed.

NOTE: Use copper wire only between disconnect switch and unit.

NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 7.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 7.

DISCONNECT￿

PER N.E.C. AND/OR￿

LOCAL CODES

 

CONTACTOR

FIELD POWER

 

WIRING

 

3 PHASE ONLY

BLUE

FIELD GROUND

 

WIRING

GROUND￿

 

 

LUG

A94025

Fig. 7 - Line Connections

Connect Control Wiring

Route 24v control wires through control wiring grommet and connect leads to control wiring. See Thermostat Installation Instructions for wiring specific unit combinations. (See Fig. 8.)

Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft (30.5 m) from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from incoming power leads.

Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24v/40va minimum.

NOTE: Use of available 24v accessories may exceed the minimum 40va power requirement. Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required.

Final Wiring Check

IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.

A crankcase heater is required if refrigerant tubing is longer than 80 ft. (24.4 m), or when outdoor unit is 20 ft. (6.1 m) below the indoor unit. Refer to the Residential Piping and Long Line Guideline.

4

Image 4
Contents Safety Considerations Installation RecommendationsElectrical Shock Hazard CUT HazardInstall on a Solid, Level Mounting Pad Check Equipment and Job SiteClearance Requirements Operating AmbientInstall Liquid Line Filter Drier Indoor Accessory UsageOutdoor Unit Connected To Factory Approved Indoor Unit Refrigerant Tubing and Sweat ConnectionsMake Electrical Connections Compressor Crankcase HeaterStart-Up Install Electrical AccessoriesFollow these steps to properly start up system Heating Check Chart Procedure Care and MaintenanceCheck Charge Final ChecksPuronr R-410A Quick Reference Guide Catalog No 25HCB 3SI

25HCC5, 25HCB3 specifications

The Carrier 25HCB3 and 25HCC5 are technologically advanced HVAC systems designed to meet the needs of modern residential and commercial spaces. These models stand out for their efficiency, reliability, and eco-friendliness, making them excellent choices for anyone looking to enhance indoor comfort while minimizing energy consumption.

One of the main features of the Carrier 25HCB3 and 25HCC5 is their exceptional SEER (Seasonal Energy Efficiency Ratio) rating, which signifies a higher cooling efficiency compared to traditional air conditioning systems. These units leverage Carrier's innovative design to deliver cooling and heating solutions that are tailored to various climate conditions, ensuring optimal performance year-round.

Both models utilize a variable-speed compressor, which allows them to adjust their cooling output based on the specific needs of the space. This technology not only enhances comfort by providing consistent temperatures but also reduces energy consumption, contributing to lower utility bills. The variable-speed operation is particularly beneficial during transitional seasons, where less intensive cooling is required.

In addition to their variable-speed capabilities, the 25HCB3 and 25HCC5 offer advanced filtration systems designed to improve indoor air quality. These systems can effectively capture airborne allergens, dust, and particulates, creating a healthier living environment. Moreover, users can opt for enhanced filtration options, which utilize HEPA filters for even greater allergen removal.

Another key characteristic of these models is their quiet operation. The Carrier 25HCB3 and 25HCC5 are engineered with sound-dampening features that minimize operational noise. This is especially advantageous for residential applications where tranquility is valued.

Durability is also a hallmark of Carrier systems. The 25HCB3 and 25HCC5 are built with robust materials and advanced protective mechanisms, ensuring that they can withstand the rigors of various weather conditions and provide reliable service for years to come.

In terms of smart technology, these models are compatible with Carrier's smart thermostat solutions, allowing users to monitor and control their HVAC systems remotely. This connectivity enhances user convenience and promotes energy efficiency by enabling users to adjust settings based on their schedules and needs.

Overall, the Carrier 25HCB3 and 25HCC5 represent a significant advancement in HVAC technology, combining high efficiency, advanced features, and user-friendly operation. Whether for residential or commercial use, these systems provide a comprehensive solution for anyone seeking reliable and effective climate control.