Mars Air Systems L-2254 manual MCP Mechanical Control Panel Troubleshooting

Page 14

2.Damaged jack/socket in display head or on circuit board.

Visually check to see that pins inside socket are not bent or corroded. Repair or replace display or circuit board if needed.

Fault: “PLF” is displayed (Elite Digital Control only).

Possible Reason/Correction

1.Indicates that seawater flow through the con- denser coil is insufficient.

Check for adequate seawater flow. Verify pump operation. Inspect the condenser coil, it may need cleaning (see maintenance section). Sensor may be faulty, replaced if necessary. Call for service tech.

MCP Mechanical Control Panel Troubleshooting

Fault: Fan is not running.

Possible Reason/Correction

1.MCP system switch is not set properly.

Set MCP system switch to “START” for fan only or “RUN” for cooling and heating (if reverse cycle).

2.MCP fuse blown.

Replace 10 amp fuse behind MCP panel

3.Wire became disconnected or loosened during installation.

Reconnect or tighten, verify with wring diagram in this manual.

Fault: System runs continuously.

Possible Reason/Correction

1.Improper MCP air sensor location.

Verify return air sensing bulb location with criteria found in this manual.

L-2254 Troubleshooting

14

English

Image 14
Contents Vector compact Page Table of Contents Marine Air Systems Clean Air Act Amendments of 1990 Title VI C-1Introduction How It WorksPlacement of System InstallationSafety Considerations Unpacking and InspectionMounting Brackets Blower AssemblyCondensate Drains Supply & Return Air Grilles and Transition BoxesFailure to install a seawater strainer will void Seawater Pump and PlumbingElectrical Connections, Grounding and Bonding Manual Control Panel MCP InstallationPhase Notice Circuit breaker before opening electric box. See Figures 9Mounting Installation ChecklistSeawater Cooling System ElectricalMechanical Control Panel MCP Operation Quick Start Operations ChecklistOperation Troubleshooting General TroubleshootingDigital Controls Troubleshooting Fault HPF is displayed Fault No heatFault Unit switches to heat while in cool mode Fault LPF is displayedMCP Mechanical Control Panel Troubleshooting Fault PLF is displayed Elite Digital Control onlyMaintenance Warranty with MCP Mechanical Control Panel control Manufacturers Limited Warranty AgreementWarranty with the Elite or Passport I/O digital con Description of Figures Overview of Vector Compact Placement of Vector Compact M1020049 Knob Control Model 10K 12K 16K 18K 24K Wiring Diagrams for Mechanical Controls VCM5-16 & 24K 2254 Wiring Diagrams for Digital Controls VCD5-16 & VCD/VHD 24K 2254 Wiring Diagrams for Digital Controls VCD18K-HV & VCM18K-HV Page Page Page Page Page Dometic Environmental Corporation