Installing B68 Cabinets

8.3.5 Installing Racks

I. Installing expansion tubes and nuts

Prior to installation, clean dust inside and outside the holes with a dust collector and then measure the spacing of holes. If errors are not acceptable, you must measure and drill again.

Follow these steps to install an expansion bolt:

1)Take down the expansion tube and expansion nut, and insert the alignment rib on the expansion nut into the alignment groove of expansion tube.

2)Put them into a hole vertically.

3)Punch the expansion tube with rubber hammer until the expansion tube is completely buried into the floor.

Figure 8-25illustrates how to install an expansion nut to an expansion tube.

1)

Expansion tube

2)

Alignment groove

3)

Expansion nut

4)

Alignment rib

Figure 8-25Install an expansion nut onto an expansion tube

Caution:

You must insert the alignment rib of expansion nuts into the alignment grooves of expansion tubes, or you will be unable to install or fasten the expansion bolts.

II. Adjusting rack height

According to the floor height and the height silkscreen of the antistatic floor on the rack, adjust all racks to the estimated height and torque the retaining bolts to 45 Nm with a torque spanner, from middle to the two sides, as shown in Figure 8-26.

3Com Corporation

8-22

Image 82
Contents 3Com Router 6000 Family Installation Guide 3C13840 3C138803Com Corporation Campus Drive Marlborough, MA 01752-3064 Table of Contents Starting and Configuring the Router Components of Integrated Anchor Strips Introduction II. Ethernet accessRouter Overview Abundant FIC optionsData security and reliability VII. Abundant fault isolation methodsVI. Online software upgrading 1 3Com Router Router Model and StructureVIII. Regulatory compliance 2 3Com Router Front panel of the 3Com RouterSystem Description 6040 6080Generic Modules SpecificationsSpecifications 1 RPU2III. Interface II. LED and buttonLED and button Description Functions 2 PSUIV. Encryption daughter card II. AppearanceFAN module III. LEDFICs 11FAN module the 3Com RouterCleanness Preparing for InstallationTemperature and Humidity General Site RequirementsElectromagnetic Compatibility ESD PreventionGas Max. mg/m Lightning Protection Safety PrecautionsChecking the Rack Unpacking Check Name Quantity DescriptionInstallation Tools and Meters and Equipment Installing The Router Installation FlowMounting the Router Installing the Cabinet/RackModel Dimensions Rack-Mounting the RouterConnecting the Pgnd Installing the Generic ModulesMounting the Router on a Tabletop Connecting the AC-Input Power Cord Connecting the Power CordAC-input power supply III. Connecting the AC-input Power Cord Connecting the DC-Input Power CordII. AC power socket recommended DC-input power supplyPower source Router side Connecting the Console TerminalII. Connecting the DC-input power cord Console portEthernet interface Connecting the Router to a LANIII. Connecting the console cable II. Ethernet cableIII. Connecting the Ethernet cable Connecting the Router to a WAN AUX port Verifying InstallationIII. Connecting the AUX cable II. AUX cableConnecting the router to a console terminal Starting and Configuring the RouterSetting up a Configuration Environment II. Setting terminal parameters3Com Router 6000 Family Chapter Installation Manual 3Com Router 6000 Family Chapter Installation Manual 5Set the terminal type Checking before power-on Powering on the RouterBoot Process of the RPU2 II. Powering on the routerPress Enter. The console screen displays Command Line Interface Router Configuration BasicsBasic Configuration Procedures Characteristics of the command line interfaceII. Command line interface Arranging Slots and Numbering Interfaces3Com Router 6000 Family Chapter Installation Manual Overview Boot MenuMaintaining Software Maintaining Software of the RPU2=BACKUP =SECURE Set this file as Main Backup Exit Enter your choice1-3 Upgrading Software Using Xmodem Upgrading the application image 1Set Send File parametersThen, the system asks you to select a file type II. Upgrading the entire Boot ROM program III. Upgrading the extended segment of the Boot ROM imageEnter Y. The system displays Upgrading the Application Image Using Tftp Parameter DescriptionDealing with a Router Password Loss Preparing Tools Removing/Installing PSUsMaintaining Hardware Removing a PSUInstalling a PSU Removing/Installing the Fan ModuleRemoving the Fan Module Installing the Fan Module Removing/Installing the Main Control BoardRemoving the RPU2 Installing the RPU2 Replacing the SdramRemoving the RPU II. Removing the SdramIV. Installing the RPU Removing/Installing the Encryption Daughter CardIII. Installing an Sdram Removing the Encryption Daughter CardInstalling the Encryption Daughter Card 8Install the encryption daughter cardTroubleshooting the Power System TroubleshootingTroubleshooting the Configuration System Troubleshooting Application Image Upgrade DownLoad Program To Flash Through Net Port Boot Device 3Com Corporation Installation Requirements and Procedures Installing B68 CabinetsPlanning the Site General Installation Procedures 2Footprint of the combined cabinetsMounting Cabinets on the Concrete Floor Components of Integrated Anchor StripsInstallation Flow 5Installing the mounting fixtures onto the anchor stripPositioning Cabinets Marking8Layout of the mounting holes and cabinet feet two cabinets III. Installing expansion bolts II. Drilling holesAdjusting Cabinet Feet Combining Cabinets 10Lock cabinet feet11Remove/install the cover Installing anchor strips Fixing CabinetsTesting Insulation III. Fixing the retaining nuts of the anchor strips15Install a single cabinet on the concrete floor Mounting Cabinets on the Antistatic Floor Introduction to RacksNumber of racks in use II. Shape of racksIII. Installing rack components Component Height of antistatic floor mm19Dimensions of slide rail segments Introduction to Slide RailsPositioning Racks Determining where to install the cabinetII. Marking 21Layout of the installation holes on the H800 series racks 23Layout of the mounting holes and cabinet feet two cabinets III. Drilling holes Installing expansion tubes and nuts Installing RacksII. Adjusting rack height III. Installing and fixing racks Installing Slide RailsInstalling T-shape nuts II. Leveling and fixing rails 27 T-shape nutInstalling Antistatic Floor Supports 28Fix and level slide rails and racksII. Installing the supports for the antistatic floor Moving the cabinets to the position Leveling CabinetsII. Leveling the cabinets III. Locking cabinet feet 32Level cabinets33Fasten cabinet feet 34Remove/install the cover II. Installing anchor strips Installing the T-shape nutsIII. Installing insulating parts and fixing anchor strips IV. Fixing the retaining nuts of the anchor strips 37Fix anchor strips17illustrates how to install cabinets on the concrete floor Restoring the Floor39B68 cabinets installed on the antistatic floor
Related manuals
Manual 187 pages 50.8 Kb

3C13840, 3C13880 specifications

The 3Com 3C13880 and 3C13840 are notable components within the realm of networking technology, primarily designed for enterprise-grade solutions. These devices belong to the 3Com family, which has long been recognized for its commitment to developing robust networking products tailored to facilitate efficient data transfers and improve connectivity across various platforms.

One of the standout features of the 3C13880 is its high-performance capabilities. This model supports advanced functions such as load balancing and fault tolerance, critical for maintaining optimum network performance in high-demand environments. Additionally, it supports various protocols, including Ethernet and Token Ring, making it versatile and adaptable to existing infrastructure. The device accommodates a wide range of network transmissions, ensuring seamless integration and operation within diverse network ecosystems.

In terms of connectivity, the 3C13880 is equipped with multiple ports, allowing for extensive device interconnectivity. This feature is particularly beneficial in large organization settings, where multiple devices, such as servers and workstations, need to communicate effectively. Coupled with high-speed data transmission rates, this model ensures minimal latency, enhancing overall network efficiency.

On the other hand, the 3C13840 is designed with a focus on cost-efficiency without sacrificing performance. This model provides essential networking features suitable for smaller business environments or those seeking budget-friendly options. It delivers reliable throughput and the ability to support a moderate number of users, making it ideal for small to mid-sized offices.

Both the 3C13880 and 3C13840 incorporate technologies that prioritize security and reliability. Features such as VLAN support and QoS settings help optimize network performance while ensuring the security and integrity of data are maintained. The devices also support management tools that allow administrators to monitor network performance in real time, facilitating quick troubleshooting and enhancing overall network management.

In summary, both the 3Com 3C13880 and 3C13840 devices stand out in networking technology by offering unique features tailored to different organizational needs. While the 3C13880 appeals to enterprises needing high performance and robust capabilities, the 3C13840 provides an accessible option for those requiring effective and budget-conscious networking solutions. The legacy of 3Com continues to be evident in these products, reflecting their innovative approach to addressing the dynamic demands of modern networking.