Sanyo Quick Connect Guide
Indoor Unit Model
SPW 4:1 Inverter 165 H
Outdoor Unit Model
Standard PAC SPW CR 604 GVH56B / GVH8B
PIPING
| SUCTION |
|
| 5/8" to joint 1/2" from joint to indoor |
|
|
|
|
|
| LIQUID |
| 3/8" to joint 1/4" from joint to indoor | |
|
|
|
|
|
| GAS PRE CHARGE LENGTH |
|
| 30m |
|
|
|
|
|
| ADDITIONAL CHARGE |
|
| 3/8" = 40 g/m & 1/4" = 20 g/m |
|
|
|
|
|
| MAXIMUM PIPING LENGTH |
|
| 50m |
|
|
|
|
|
|
| INTERCONNECTING WIRING | ||
|
|
|
|
|
| SUGGESTED CABLE SIZE |
|
| 0.75 mm (Shielded) |
|
|
|
|
|
| NUMBER OF CORES |
| 2 | |
|
|
| ||
|
| POWER SUPPLY WIRING | ||
|
|
|
|
|
| INDOOR UNIT POWER SUPPLY |
|
| 5a Single Phase |
|
|
|
|
|
| OUTDOOR UNIT POWER SUPPLY |
|
| GVH56B 40a Single Phase - GVH8B 16a Three Phase |
|
|
|
|
|
|
| REMOTE CONTROLLER WIRING | ||
|
|
|
|
|
| SUGGESTED CABLE SIZE |
|
| 0.75 mm (Shielded) |
|
|
|
|
|
| NUMBER OF CORES |
| 2 | |
|
|
|
|
|
|
| WIRING DIAGRAM | ||
DOWNLOADS
Installation Manual | Technical Data & Service Manual |
|
|
|
|