Sanyo Quick Connect Guide
Indoor Unit Model
SPW 2:1 Inverter 255 H
Outdoor Unit Model
Standard PAC SPW CR 484 GVH56B / GVH8B
PIPING
| SUCTION |
|
| 5/8" |
|
|
|
|
|
| LIQUID |
| 3/8" | |
|
|
|
|
|
| GAS PRE CHARGE LENGTH |
|
| 30m |
|
|
|
|
|
| ADDITIONAL CHARGE |
|
| 40 g/m |
|
|
|
|
|
| MAXIMUM PIPING LENGTH |
|
| 50m |
|
|
|
|
|
|
| INTERCONNECTING WIRING | ||
|
|
|
|
|
| SUGGESTED CABLE SIZE |
|
| 0.75 mm (Shielded) |
|
|
|
|
|
| NUMBER OF CORES |
| 2 | |
|
|
| ||
|
| POWER SUPPLY WIRING | ||
|
|
|
|
|
| INDOOR UNIT POWER SUPPLY |
|
| 5a Single Phase |
|
|
|
|
|
| OUTDOOR UNIT POWER SUPPLY |
|
| GVH56B 32a Single Phase - GVH8B 16a Three Phase |
|
|
|
|
|
|
| REMOTE CONTROLLER WIRING | ||
|
|
|
|
|
| SUGGESTED CABLE SIZE |
|
| 0.75 mm (Shielded) |
|
|
|
|
|
| NUMBER OF CORES |
| 2 | |
|
|
|
|
|
|