Overtemperature protection
| Line no. | Operating line |
|
| 5051 | Storage tank temp max |
|
Storage tank temp max | If the storage tank reaches the maximum storage tank temperature set here, the | ||
| collector pump will be deactivated. It will be released again when the storage tank | ||
| temperature drops 1 °C below the maximum storage tank temperature. |
The protective collector overtemperature function can reactivate the collector pump until the storage tank’ s safety temperature is reached.
T
TSpMax
TSp
L 10
TSpMax | Storage tank temp max (operating line 5051) |
TSp | Actual value of the storage tank temperature |
L | Storage tank charging: 1 = on, 0 = off |
1°C
2354Z10
t
DHW push
Line no. | Operating line |
5070 | Automatic push |
| Off |
| On |
Automatic push | The DHW push can be triggered either manually or automatically. |
| With the DHW push, the DHW is heated up once until the nominal setpoint is reached. |
| Off |
| The DHW push must be triggered manually. |
| On |
| If the DHW temperature falls below the reduced setpoint (operating line 1612) by at |
| least 2 switching differentials (operating line 5024), |
| DHW setpoint (operating line 1610) will take place again. |
| The automatic DHW push only works when the DHW operating mode is activated. |
2.7 Configuration
Building and room model
| Line no. |
| Operating line |
|
|
| 6112 |
| Gradient room model |
|
|
Gradient room model | The room model gradient gives the period of time in minutes room heating needs to | ||||
| raise the temperature by 1 °C. The setting made applies to all circuits. |
|
| ||
|
|
|