Overtemperature protection

 

Line no.

Operating line

 

 

5051

Storage tank temp max

 

Storage tank temp max

If the storage tank reaches the maximum storage tank temperature set here, the

 

collector pump will be deactivated. It will be released again when the storage tank

 

temperature drops 1 °C below the maximum storage tank temperature.

The protective collector overtemperature function can reactivate the collector pump until the storage tanks safety temperature is reached.

T

TSpMax

TSp

L 10

TSpMax

Storage tank temp max (operating line 5051)

TSp

Actual value of the storage tank temperature

L

Storage tank charging: 1 = on, 0 = off

1°C

2354Z10

t

DHW push

Line no.

Operating line

5070

Automatic push

 

Off

 

On

Automatic push

The DHW push can be triggered either manually or automatically.

 

With the DHW push, the DHW is heated up once until the nominal setpoint is reached.

 

Off

 

The DHW push must be triggered manually.

 

On

 

If the DHW temperature falls below the reduced setpoint (operating line 1612) by at

 

least 2 switching differentials (operating line 5024), one-time charging to the nominal

 

DHW setpoint (operating line 1610) will take place again.

 

The automatic DHW push only works when the DHW operating mode is activated.

2.7 Configuration

Building and room model

 

Line no.

 

Operating line

 

 

 

6112

 

Gradient room model

 

 

Gradient room model

The room model gradient gives the period of time in minutes room heating needs to

 

raise the temperature by 1 °C. The setting made applies to all circuits.

 

 

 

 

 

 

21/26

 

 

 

 

 

 

Siemens Schweiz AG

User Manual OEM

 

CE1U2353en01a

HVAC Products

The settings in detail

22. November 2006

Image 21
Contents Edition 1.0 Controller series a CE1U2353en01a 22. November Zone controlerSiemens Schweiz AG CE1U2353en01a Hvac Products Table of contents Overview of OEM settings 138 Delete all devices 135 Service unitTime prog heating circuit 500 Preselection Mo Su Time prog heating circuit 520 Preselection Mo SuHolidays heating circuit 651 Preselection Periode Holidays heating circuit 641 Preselection PeriodeHolidays heating circuit P 661 Preselection Periode 730 Summer/winter heating limit851 Floor curing setp manually 861 Excess heat draw Always 900 Optg mode changeover Protection872 With prim contr/system pump Yes 1030 Summer/winter heating limitHeating circuit P 1300 Operating mode Automatic 1200 Optg mode changeover Protection1500 Optg mode changeover Protection 1172 With prim contr/system pump Yes1644 Legionella funct time 1640 Legionella function Fixed weekday360 Min 1647 Legionella funct circ pump 1660 Release of the circulating pump DHW release5060 Electric immersion heateroperating mode Substitute 5024 Switching diff 5030 Charging time limitation 150Configuration 5710 Heating circuit 600 Min 5040 Discharging protection AutomaticHCs+DHW Optg mode change6020 Function extension module No function 6021 Function extension module No function6605 Bus power supply state 6205 Reset to default parameters6612 Alarm delay System 6640 Clock mode Autonomous7846 Contact state H2 Open Maintenance/service 7140 Manual control Off8732 Heat circ mix valve cl Y2 8731 Heat circ mix valve op Y18761 Heat circ mix valve op Y5 8762 Heat circ mix valve cl Y6Settings in detail Operator sectionHeating circuits Setpoints Domestic hot waterRelease 24h/dayPrimary controller / system pump Pump H1/H2 80 90 100 C DHW storage tank 5030 Charging time limitation Charging time limitationDischarging protection 5040 Discharging protectionConfiguration Parameters 6222 Device hours runRange of action of changeover Diagnostics consumers Error6820 Reset history Room temperature 1 / 2 / P modelIndex ResetProof of change Subject to alteration