An adjustment of the integral action time changes the valve’s rate of response. The longer the integral action time Tn, the slower the response of the controlled system.
y
1 Xp
Tn
x
@
2.3 Domestic hot water
Setpoints
Line no. | Operating line |
1614 | Nominal setpoint max |
2392Z08
t
t
This operating line is used to limit the “Nominal setpoint“ (operating line 1610) at the top.
Release
Line no. | Operating line |
1620 | Release |
| 24h/day |
| Time programs HCs |
| Time program 4 / DHW |
24h/day
The DHW temperature is constantly maintained at the nominal DHW setpoint, independent of any time programs.
Example:
|
|
|
|
|
|
|
|
|
|
| 2371Z18 |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
0 | 6 | 12 | 18 | 24 h | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Time programs HCs
The DHW setpoint is switched between the nominal DHW setpoint and the reduced DHW setpoint according to the heating circuits’ time programs. The first