ERROR CODES AND ALARM STATUS
Error | Maintenance |
| Problem | Control Board's Action | |
Code | ICON |
| |||
|
|
| |||
1 | Flash | Front Panel Button Stuck For More | Continue to monitor for "OPEN" (Unstuck) switch. Do not process switch | ||
Than 20 Seconds | input. ENSURE FRONT COVER DOES NOT DEPRESS BUTTONS | ||||
|
| ||||
|
|
|
| ||
2 | Flash | Input Voltage Out of Specification (103 | Stop.Open all relays until voltage is back within specs. Resume operation | ||
|
| - 127 / 187 - 253) |
| ||
3 | Flash | Indoor Temperature Sensor is Open or | Set temp to 75°F in COOLING or 68°F in HEATING. Unit continues to | ||
Shorted |
| operate | |||
|
|
| |||
4 | Flash | Indoor Coil Temperature Sensor is | Control Board sets temp to 40°F. Override sensor. Unit Continues to | ||
Open or Shorted | operate. | ||||
|
| ||||
|
| Outdoor Coil Temperature Sensor is | Sets temp to 20°F. Override sensor. Continue operation. Use Elec Heat if | ||
5 | Flash | available for HEATING. If not available use HEAT PUMP if outdoor temp | |||
Open or Shorted | |||||
|
| allows. | |||
|
|
|
| ||
|
|
|
| Shut down for 5 min. Resume operation for 3 min. Continues to monitor. If | |
6 | Flash | Outdoor Coil > (grater than) 175 F | test fails 3 times, the severity is increased and the unit operation is locked | ||
|
|
|
| out. | |
7 | Flash | Indoor Coil < (less than) 30 F for 2 | Turn compressor off. Run High Fan speed. When coil temp reachs 45°F | ||
consecutive minutes | resume operation after lockout time. | ||||
|
| ||||
8 | Log Only | Unit Cycles > (grater than) 9 Times per | Continue operation. Continue to monitor. Take no action. Log Only. | ||
|
| hour |
|
| |
9 | Log Only | Unit Cycles < (less than) 3 Times per | Continue operation. Continue to monitor. Take no action. Log Only. | ||
Hour |
| ||||
|
|
|
| ||
|
|
|
| Only used if Electric Heat is available. Run High Speed and Electric heat | |
10 | Log Only | Room Freeze Protection | until room temp reaches 46°F. Display "FRZ" during operation. Logged | ||
|
|
|
| Only | |
11 | On | WallStat Problem or Connection Issue | Severity 4 error is. Unit operates based on standard input mapping. | ||
|
|
|
| Severity 2 error opens all relays. Unit will not operate. | |
12 | Flash | Discharge Air > (greater than) 185 F | Shutdown heat pump and electric heater. Run high fan speed until temp is | ||
100°F. Resume operation. Third occurance in 1 hour locks unit out. | |||||
|
|
|
| ||
|
|
|
|
| |
13 | Flash | Prerssure Limit Switch Open | If unit is cooling or heat pump on,shut down compressor. Run high fan until | ||
switch closes. Resume operation. Third occurance in 1 hour locks unit out. | |||||
|
|
|
| ||
|
|
|
| ||
14 | Flash | Discharge Air Temperature Sensor is | Override Sensor. Set temp to 75°F. Continue to monitor. Set error code 14 | ||
Open or Shorted | ON. | ||||
|
| ||||
15 | Solid On | Heat Pump Error | If indoor coil temp < (Lesser than) ambient temp for 3 minutes. Unit uses | ||
electric heat to satisfy heating demand. | |||||
|
|
|
| ||
16 | Flash | Temperature Beyond Operating Limits | Ambient temp < (less than) 0°F and ambient temp > (greater than) 130°F. | ||
|
|
|
| Set error code 16 ON. When cleared return unit to normal. | |
17 | Flash | Equipment Doesn't Meet Minimum | Must have compressor enabled and at least 2 fan speeds | ||
Configuration |
| ||||
|
|
|
| ||
18 | Flash | Special Test 1 | Severity Level 1 | Unit shuts down. Inputs via front panel or | |
Technical Service required URGENT | |||||
|
|
|
| ||
19 | Flash | Special Test 2 | Severity Level 2 | Unit operates. Qualified Technical Service required | |
20 | Solid On | Special Test 3 | Severity Level 3 | Error is Logged Only. Unit operates. Severity 3 keeps unit running. | |
Attention is needed | |||||
|
|
|
| ||
21 | OFF, Log Only | Special Test 4 | Severity Level 4 | Error is Logged Only. Unit operates. Severity 4 keeps unit running. | |
22 | OFF, Log Only | Outdoor Coil Temperature < 30 F for 2 | Unit will use electric heat to satisfy heating demands until temp > 45°F. | ||
consecutive Minutes | Unit must be a Heat Pump. | ||||
23 | OFF, Log Only | Frost Protection (for Heat Pump Only | Unit will run active defrost for a minimum of 6 minutes when Heat Pump | ||
Unit- YS10M10) | run time is greater than 60 minutes and outdoor coil temp is 26 F or less. | ||||
|
|
|
| ||
24 | Flash | Outdoor Air Temperature Sensor is | Continue with normal operation. Continue to monitor sensor. | ||
Open or Shorted | |||||
|
|
|
Key Sequence
Enter Maintenance Menu
Reset Error Codes & Error History
Action Press SYSTEM + SCHEDULE + BACK + DISPLAY/ENTER for 6 secs or until double beep sounds() Press + for 3 secs or until double beep sounds ()