Condensed Operating Manual for Door Control Unit AT18
12.Connect the light barrier to X6 (see illustration 1 or lid imprint).
Insofar as the light barrier input is not used, X6 must be wired to X4 according to the lines on the connection layout.
13.Plug in clip plugs X6 and X4.
CAREFUL
The control is operative after the next
14.Switch control on (plug in mains current plug, or plug X3).
The four LEDs next to the
15.At a presented control signal “CLOSE” the door closes with the initial speed in the “CLOSE” position. At a presented control signal “OPEN” the door opens with the initial speed in the “OPEN” position.
16.If the control has recognized the final door positions “OPEN” and “CLOSE”, the subsequent opening and closing movements are performed in the normal speed.
17.For special applications the movement values can be specifically adapted to the door. However, for that the terminal module (option), the user terminal HT18 (HT25) must be connected to a PC, or be connected via a USB adapter (option), on which the operating program AT Frontend has been started. The operation is described in attachment 11 of the operating instructions.
Simple settings can also be executed with the three buttons and the
WARNING
The service staff should test the acceptable energies and forces after the putting into operation of the elevator door on the heaviest door in the complete system (elevator) and to adjust it to the critical limits in case of an exceeding of the values.
5 Electrical configuration with the “MinimalEditor”
The simple adjustability of the profile and of the closing forces is indicated as minimal editor via the three internal buttons with the aid of the
Configuration:
1.Start of the minimal editor: press service button – “OPEN” and – “CLOSE” (S5001 and S5002) immediately at the same time as supplying the mains current and keep pushed in.
The LED display (H5000) displays an “8” for approximately 5 seconds.
2.Let go of both buttons after
3.After approximately 3s a “C” (movement profile) and a numerical value is displayed alternatively. The displayed numerical value represents the profile number deposited in the AT18.
4.The desired profile can be selected with the service buttons – “OPEN” and – “CLOSE” (S5001, or S5002).
5.The set value is saved by a long pressing of (>2s) of the parameter button (S5000). A dot appears