Soleus Air SG-DEH-70EIP-6 Troubleshooting, Dehumidifier Operaton, Problem, Possible Causes

Page 7
TROUBLESHOOTING

TROUBLESHOOTING

DEHUMIDIFIER OPERATON

Problem

Possible Causes

Solutions

 

 

 

Dehumidifier does not

The dehumidifier is un-

Make sure the dehumidifier’s plug is pushed

start.

plugged.

completely into the outlet.

 

 

 

 

The fuse is blown / cir-

Check the house fuse / circuit breaker box and

 

cuit breaker is tripped.

replace fuse or reset breaker.

 

 

 

 

Dehumidifier has

The dehumidifier automatically turns off when

 

reached the user set

either condition occurs. Change to a lower

 

humidity level or the

setting or empty the water bucket and replace

 

bucket is full.

properly.

 

 

 

 

Bucket is not in the prop-

The bucket must be in place and securely

 

er position.

seated for the dehumidifier to operate.

 

 

 

 

Power Failure.

There is a protective time delay (up to 3 min.)

 

 

to prevent tripping of the compressor overload.

 

 

For this reason, the unit may not start normal

 

 

dehumidification for 3 min. after it is powered

 

 

back on.

 

 

 

Dehumidifier is not

Not enough time allowed

When first installed, allow at least 24 hours to

operating as

for unit to remove mois-

achieve the desired humidity level.

Intended.

ture.

 

 

 

 

 

Airflow is restricted.

Make sure there are no curtains, blinds, or

 

 

furniture blocking the side or back of the de-

 

 

humidifier.

 

 

 

 

Dirty filter.

See the Cleaning The Air Filter section on

 

 

page 13.

 

 

 

 

The user set Humidity

To reduce moisture, press the down arrow

 

Level may not be set low

button to lower the percent humidity desired in

 

enough.

the room, or set the dehumidifier to CO for

 

 

continuous operation.

 

 

 

 

Doors and windows may

Check that all doors, windows, and other

 

not be closed tightly.

openings are securely closed.

 

 

 

 

Water is not draining

Make sure the drain is placed below the drain

 

through drain hose

connector nozzle to allow gravity to drain the

 

 

water (Refer to Gravity Drain Hose section in

 

 

this manual).

 

 

 

 

Room temperature is too

Moisture removal is best at higher room tem-

 

low.

peratures. Lower room temperatures will re-

 

 

duce the moisture removal rate. This model is

 

 

designed to operate at temperatures above

 

 

41°F.

 

 

 

Filter Indicator is lit.

Filter needs to be

Once filter has been cleaned, press the FIL-

 

cleaned every 250 hours

TER button for 3 seconds to turn the filter

 

of use.

indicator off.

 

 

 

POWER ON/OFF (1)

Once the unit is plugged in, the POWER INDICA- TOR (10) will light. Pressing the POWER button once will turn the unit ON and illuminate the digi- tal display (13). The fan will operate for 3 minutes to draw air through the dehumidifier to properly sense relative humidity. The display will show the humidity level of the room in 1% incre- ments, down to a minimum of 30%. Pressing the Power button again will turn the display OFF and the unit will cease operating.

HUMIDITY LEVEL (2)

The humidity level can be set in 5% increments in a range from 35% to 80%. The humidity setting is shown in the digital display (13). When the hu- midity level of the room reaches the set level, the compressor will stop, but the fan will continue operating for 3 minutes. To set the unit to continu- ous operation, press the down arrow button until the display shows 35%. Press again and the display (13) will show CO. The Continuous indi- cator (15) will light up on the control panel. To leave continuous operation, press the UP arrow. To check the current humidity setting, press the up or down arrow. The display will show and set 5% above or below the current settings.

FAN SPEED (3)

Press Fan Speed to toggle between Low, Med, and High fan speeds. Speed will be shown in FAN

SPEED INDICATOR (9)

BUCKET FULL INDICATOR (14)

When the collection bucket is full, the BUCKET FULL indicator (14) will light up and you will hear an audible alarm. The audible alarm will last up to ten seconds The dehumidifier will not run until the bucket is removed, emptied and replaced.

AUTO MODE (7)

Press the AUTO button (7) to select AUTO Mode. When AUTO MODE is selected the unit will auto- matically choose settings according to the current room humidity level. The AUTO indicator (8) will light up when selected. The set humidity level is not able to be changed in this mode.

PUMP MODE (6)

Press the PUMP button (6) to select Pump Mode. When PUMP MODE is selected the unit will pump the collected water out of the unit. Make sure the pump accessories are connected (refer to pages 10 & 11) prior to using pump mode. When select- ed the PUMP indicator (16) will light up.

TIMER - DELAY START/AUTO ON (4)

When the dehumidifier is off, it can be set to auto- matically turn on in 30 minutes to 24 hours at the previous set mode and fan setting. To set the Auto-on Timer, press the TIMER (4) button on the

control panel. Each touch of the +/- buttons on the control panel will change the timer setting in 30 min increments (.5 hours). After 10 hours each press of the + button will increase the timer in 1 hour increments. Once the timer is set, press the TIM- ER (4) button once more to save the setting. The TIMER indicator (11) will light up at this time.

TIMER - AUTO SHUT-OFF (4)

When the dehumidifier is on, it can be set to auto- matically turn off in 30 minutes to 24 hours. To set the Auto-off Timer, press the TIMER (4) button on

the control panel. Each touch of the +/- buttons on the control panel will change the timer setting in 30 minute increments (.5 hours). After 10 hours each press of the + button will increase the timer in 1 hour increments. Once the timer is set, press the TIMER (4) button once more to save the setting. The TIMER indicator (11) will light up at this time.

FILTER RESET (17)

The FILTER RESET indicator (17) will light up when the filter needs cleaning. Remove the filter and clean accordingly. Replace the filter when finished and press FILTER (5) to reset the filter indicator.

CONTROL PANEL LOCK (12)

To lock the control panel, press the “+” and “-

(2) keys at the same time for 3 seconds. Locking the control panel prevents someone from acci- dentally changing the settings. When locked, the LOCK indicator (12) will light up. Hold the “+” and “-” (2) keys at the same time again for 3 seconds to unlock the control panel.

NOTE:

Once the set humidity level is reached, the compressor will shut off. The fan will contin- ue to run for up to 3 minutes.

Anytime the compressor stops running for any reason, it will not restart for a minimum of 3 minutes. This is a design feature to pro- tect the compressor from damage.

14

7

Image 7
Contents V.121030 SG-DEH-70EIP-6Portable Dehumidifier with Internal Pump Operating InstructionsPACKAGE CONTENTS TABLE OF CONTENTS1 YEAR LIMITED WARRANTY SAFETY INSTRUCTIONS ELECTRICAL REQUIREMENTS INSTALLING YOUR DEHUMIDIFIERDehumidifier Facts Error Type ERROR CODESPRODUCT SPECIFICATIONS PLACEMENTwarm air TROUBLESHOOTING ContCONTROL PANEL Unit is dischargingSolutions TROUBLESHOOTINGDEHUMIDIFIER OPERATON ProblemCLEANING THE EXTERIOR CARE AND MAINTENANCEWATER DISPOSING OPTIONS CLEANING THE AIR FILTERWATER DISPOSING OPTIONS USING THE DEHUMIDIFIERINSTALLING THE PUMP HOSE INSTALLING THE PUMP HOSEINSTALLING THE INTERNAL PUMP HOSE