All installations and services must be performed by qualified service personnel.
When the oil tank is located below the level of the burner, it is necessary to “lift” the oil to the burner. A return line should be connected between the fuel pump and tank. This requires insertion of the
Underground tanks should be located outside the building. Installation of above ground tanks is permitted inside buildings, under certain conditions, as well as outside. Consult the Standard for Installation of
If the oil supplier does not already use oil additives, it is recommended that additives be used to emulsify any water accumulation in the oil.
F. Oil Filter
It is strongly recommended that an oil filter assembly be installed in the oil supply line to the unit. The OPB has been shipped with a
The filter cartridge should be replaced at least once a year. The filter body should be thoroughly cleaned before installing a new cartridge.
G. Burner Specifications And Performance
The model OPB has been factory equipped with the Beckett AFG oil burner. A
.60 gal. X 80° A nozzle has been factory installed to provide
Note:
17