Roberts Gorden 250 Standard Vented Heaters Models Uhax 150, Horizontal Venting, Vertical Venting

Page 20

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

7.2.1Standard Vented Heaters (Models UHA[X] 150 - 400)

The vent must be fitted with a low resistance terminal. See Page 13, Figure 6 through Page 14, Figure 7. Standard vented heaters do not allow outdoor air intake for combustion air.

7.2.2Separated Combustion Heaters (Models UHA[X]S 150 - 400)

The heaters are designed to be installed as separated combustion heaters. The vent and air intake are run as separate pipes to the wall or roof terminals. See Page 16, Figure 9. As an option, the vent and air intake are run as separate pipes to a concentric vent box and a concentric vent/air intake pipe penetrates the wall or roof. See Page 16, Figure 10 and Page 17, Figure 11.

For separated combustion installation, the vent and air intake must be fitted with an individual and correctly sized sealed system and the vent and air intake must terminate at approved wall and roof terminals.

Separated combustion units may not be common vented. See Page 11, Section 7.

7.3 Unvented Operation

WARNING

Carbon Monoxide Hazard

Heaters may be installed vented or unvented.

Vented heaters must be vented outdoors.

Unvented heaters must be installed according to the installation manual.

Failure to follow these instructions can result in death or injury.

This heater is not approved to be installed in residential buildings.

For unvented operation in commercial installations, sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).

7.4 Horizontal Venting

Horizontally vented heaters must be individually vented.

Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3 m). For vent lengths greater than 5' (1.5 m),

12 of 51

condensation will form. Insulation is recommended and condensation drains may be desired. For vents pitched up toward the vent terminal, place the condensation drain within 5' (1.5 m) of the heater.

In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.

For 4'' (10 cm) vents in either combustible or noncombustible walls, use vent terminal (P/N 90502100) or equivalent insulated vent terminal. Follow the manufacturer's instructions for proper installation.

Instead of an insulated vent terminal, a listed thimble with 2" (5 cm) air gap, may be used with a 4" (10 cm) vent cap (P/N 90502102).

7.5 Vertical Venting

Vertically-vented standard-vented heaters can be common vented (up to 4 heaters).

For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired. Vent from the rear of the heater cabinet then run the vent vertically and use a condensate drain at the bottom of the vertical vent.

Vent pipe must be sloped 1/4'' (.6 cm) for every 1' (.3 m).

For 4'' (10 cm), an approved vent cap (P/N 90502102) must be used.

For 6'' (15 cm) common vent, an approved vent cap (P/N 90502103) must be used.

For common vertical venting of more than two heaters, See Page 15, Figure 8.

A vent shall not extend less than 2' (.6m) above the highest point where it passes through a flat roof of a building.

7.6 Length Requirements

If using vent lengths greater than 5' (1.5 m), condensation will form in the vent pipe. Insulation and additional sealing measures (high temperature silicone at all seams) are required.

The entire vent should be insulated with foil faced fiberglass insulation (1/2" thick, 1-1/2# density minimum).

Image 20
Contents Combat Page Gamme standard Page Roberts-Gordon LLC Page Table of Figures Page Heater Safety Manpower RequirementsSafety Labels and Their Placement California PropositionUHAXS150 175 Label Placement UHAXS200 250 Label Placement UHAXS300 400 Label Placement National Standards and Applicable Codes Installer ResponsibilityWall Tag Minimum Required Installation Clearances Critical Considerations 3.1 Basic InformationManufactured Units VentilationInstallation Clearances and Clearances to Combustibles Clearances To CombustiblesNational Standards and Applicable Codes High Altitude Heater Installation 6.1 General Suspension MethodsVent Installation VentingUnited States Requirements Canadian RequirementsStandard Vented Heaters Models Uhax 150 Horizontal VentingVertical Venting Length RequirementsReplacing an Existing Heater in a Venting System Maximum Vent Lengths TableVent Material Model Standard Vented Heater Common Vertical Vent Termination Concentric Vent Box Vertical Unvented Installation AIR SupplyBuilding Ventilation Outside Combustion Air SupplyGAS Piping ConnectionsDo not bend flexible gas connector Wiring Low Voltage Thermostat with One HeaterPositioning Thermostats Fan ControlLow Voltage Thermostat with Multiple Heaters Models UHAXS150 Low Voltage Thermostat with Multiple Heaters Models UHAXS300 Uhaxs Series Internal Wiring Diagram TransformerUhaxs Series Ladder Wiring Diagram FlameElectrical Connection to the Heater Operation and Maintenance Electrical ChecksLouvers Mechanical ChecksBegin Start-Up Before Operating the Heater Automatic Burner Control SequenceTurning Off the Heater Pressure SwitchCheck Gas Rate Instruction to the User External ControlsComplete the Start-Up User Instructions Servicing Maintenance Checklist Venting and Air Intake PipeAnnual Fall Start-Up Vicinity of the HeaterWhen installed Wall Tag Heat ExchangerGas Line and Shut-off Valves Burner ObservationTroubleshooting General Troubleshooting For Automatic Ignition Burner Systems Conduct start-up procedure as shown on Page 27, SectionTroubleshooting for Flame Supervision System StartTroubleshooting for Gas Valves Troubleshooting for Flue BlowerReplacement Parts Burner ComponentsBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Louvers and Louver Spring Horizontal Louvers LouversUhaxs Axial Fan/Guard/Motor Assembly Ignition ControlTo Replace the Fan Assembly Specifications 16.1 Dimension Data General Technical Data Table Technical Data TableWarranty is Void if ROBERTS-GORDON LLC will PAY forROBERTS-GORDON LLC will not PAY for Limitations on Authority RepresentativesPage Owner Warranty Registration Card Mail or Fax toPage
Related manuals
Manual 52 pages 19.42 Kb Manual 48 pages 52.86 Kb

175, 225, 300, 250, 400 specifications

Roberts Gorden is a recognized leader in the field of heating solutions, particularly renowned for the development of its innovative radiant heating systems. The lineup of models including the Roberts Gorden 250, 300, 400, 150, and 225 features a blend of advanced technology, exceptional efficiency, and versatile applications that cater to various industrial and commercial needs.

At the core of Roberts Gorden products is their radiant heating technology. Unlike conventional heating systems that warm the air, radiant heaters emit infrared radiation, which directly heats objects and people within a space. This method not only provides a comfortable environment but also reduces energy consumption and minimizes the loss of heat, making it an environmentally friendly choice.

The Roberts Gorden 250 model is specifically designed for smaller spaces, offering compact efficiency without sacrificing power. It features an adjustable output, allowing for tailored heating based on specific requirements. The advanced burner technology ensures optimum combustion efficiency, translating to cost savings on fuel consumption.

Moving on to the Roberts Gorden 300, this unit is well-suited for medium-sized facilities. With enhanced capabilities, the 300 model offers improved heating distribution, making it ideal for warehouses and production floors. The ease of installation and maintenance further enhances its appeal, allowing businesses to focus on their operations rather than on complicated heating systems.

The Roberts Gorden 400 is a powerhouse in the lineup, engineered for larger spaces that demand high-performance heating. Its robust construction and powerful output provide effective warmth even in challenging environments. The unit is equipped with sophisticated controls that promote energy efficiency while maintaining optimum comfort levels.

In the mid-range spectrum, the Roberts Gorden 150 and 225 models cater to businesses needing versatile heating solutions. Both models are designed with user-friendly interfaces and include safety features that comply with industry standards. Their lightweight design allows for easy installation and mobility, making them suitable for temporary or permanent heating applications.

Overall, Roberts Gorden's commitment to innovation and efficiency is evident across its product range. With a focus on sustainability and advanced heating technologies, the Roberts Gorden 250, 300, 400, 150, and 225 models provide reliable heating solutions that meet the diverse preferences of industrial and commercial users. These products are not just about warmth; they are about creating a comfortable and productive environment while minimizing energy costs and environmental impact.