Toshiba CONCEALED DUCK TYPE Indoor P.C. Board Optional Connector Specifications MCC-1402

Page 41

Indoor P.C. Board Optional Connector Specifications (MCC-1402)

Function

Connector

Pin

Specifications

Remarks

No.

No.

 

 

 

 

 

 

 

 

Option output

CN60

1

DC12V (COM)

 

 

 

 

 

 

 

 

2

Defrost output

ON during defrost operation of outdoor unit

 

 

 

 

 

 

 

3

Thermo. ON output

ON during Real thermo-ON (Comp ON)

 

 

 

 

 

 

 

4

Cooling output

ON when operation mode is in cooling system

 

 

 

 

(COOL, DRY, COOL in AUTO cooling/heating)

 

 

 

 

 

 

 

5

Heating output

ON when operation mode is in heating system

 

 

 

 

(HEAT, HEAT in AUTO cooling/heating)

 

 

 

 

 

 

 

6

Fan output

ON during indoor fan ON

 

 

 

 

(Air purifier is used/Interlock cable)

 

 

 

 

 

Outside error input

CN80

1

DC12V (COM)

(When continued for 1 minute)

 

 

 

 

Check code “L30” is output and forced operation stops.

 

 

2

DC12V (COM)

 

 

 

 

 

 

 

 

 

 

3

Outside error input

 

 

 

 

 

 

CHK

CN71

1

Check mode input

Used for operation check of indoor unit.

Operation check

 

 

 

(Communication with outdoor unit or remote controller

 

 

 

 

 

2

0V

is not performed, but the specified operation such as

 

 

 

 

indoor fan “H” or drain pump ON is output.)

DISP display mode

CN72

1

Display mode input

 

 

 

 

 

 

 

 

2

0V

Display mode enables indoor unit and remote controller

 

 

 

 

to communicate. (When power is turned on)

EXCT demand

CN73

1

Demand input

 

 

 

 

 

 

 

 

2

0V

Forced thermo-OFF operation in indoor unit

 

 

 

 

 

– 41 –

Image 41
Contents Split Type Contents Indoort Unit TroubleshootingOriginal instruction Explanation of illustrated marks Explanation of indicationsWork undertaken Protective gear worn Indication ExplanationDescription Confirmation of warning label on the main unitPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Declaration of Conformity Explanations given to userRelocation Specifications Copper pipe Piping Safety Caution Concerned to New RefrigerantFlare nut JointGeneral tools Conventional tools can be used ToolsSM56 type Round duct Concealed Duct typeSM110 type Round duct RAV-SM404MUT∗, RAV-SM454MUT∗, RAV-SM564MUT∗ Space required for Installation and servicingRAV-SM564BT∗, RAV-SM804BT∗, RAV-SM1104BT∗, RAV-SM1404BT∗ DimensionRAV-SM564CT∗, RAV-SM804CT∗, RAV-SM1104CT∗, RAV-SM1404CT∗ Compact 4-way Cassette Type RAV-SM564BT ∗, RAV-SM804BT ∗, RAV-SM1104BT ∗, RAV-SM1404BT ∗ RAV-SM564CT ∗, RAV-SM804CT ∗, RAV-SM1104CT ∗, RAV-SM1404CT ∗ Ceiling TypeParts name Type Specifications Specifications of Electrical PartsCase of Connection of Wired Simple Remote Controller Indoor Controller Block DiagramWireless remote controller Case of Connection of Wireless Remote ControllerMax units Control outline Command Outline of specifications RemarksTemperature in heating Heat Ceiling type Outline of specificationsTcn TcjTc n ConditionsSetup at shipment All operations Cooling/dry operation Heating/fan operationAll modes AlarmCase of wired remote controller LCD Figure if To 28C Setup AT Local Outline of specifications Remarks TCJ Exct Disp CHK MCC-1402Indoor P.C. Board Optional Connector Specifications MCC-1402 Before troubleshooting Summary of TroubleshootingTroubleshooting procedure Wired remote controller typeWireless remote controller type Lamp indication Check code Cause of trouble occurrence Outline of judgmentLamp indication Check code Others Other than Check Code Central control devices detected Remote controller detectedIndoor unit detected Error mode detected by indoor unit Check Code ListAir conditioner Error mode detected by outdoor unitOperation of diagnostic function Check Status Power supply error of remote controller, Indoor E09 error Check code E01 errorE10 error E04 errorL09 error E18 errorE08, L03, L07, L08 error P30 error Central controller L20 errorL30 error F10 error P10 errorP12 error Check by tester P19 errorExchange to cooling cycle Exchange to heating cycleF01 error F02 errorC06 error 11 model connection interface P31 error Follower indoor unit E03 error Master indoor unitF29 error TA, TC, TCJ, TE, TS, to sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE,TS, to sensor TD, TL sensorPosition Resistance value Part name Checking procedureCase Replacement proceduresCode No. required at least Contents Setting data read out from EepromC. Board for indoor unit servicing replacement procedures MCC-1402 Writing the setting data to EepromSetting data Type Type name abb Setting data Factory-set valueSetting data Type Type Code NoCompact 4-way Cassette Type and Concealed Duct Type Test Run Setup on Remote Controller Wired remote controllerTest cooling operation Test heating operation Procedure DescriptionD203 Red Practical operationLED Display on Indoor P.C. Board D002 Red Using the set temperature Function Selection SetupTo change the selected indoor unit, proceed to Procedure To change item to be set up, proceed to ProcedureDescription At shipment Item No. DN table Selection of functionDescription At shipment When connected 2 remote controllers operate an idoor unit Wireless remote controllerWhen connected 2 remote controllers operate the twin Setup methodContents Pushing Test button returns the display to usual display Calling of error history ContentsGroup control operation System exampleUsual regular communication Indoor unit power-ON sequenceInitial communication Model connection interface wiring connection Microprocessor block diagramModel Connection Interface TCC-LINK adapter Model name TCB-PCNT30TLEC. Board Switch SW01 Setup Wiring SpecificationsExternal view of P.C. board assembly How to set up from indoor unit side by remote controllerAddress setup Push Test + Vent buttons for 4 seconds or moreDuring unset time, At shipment from factory is displayed Address setup procedure Address SetupAddress Setup & Group Control Terminology System configurationExample Only turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringPush SET + CL + Test buttons Using timer time Buttons, set the line addressSimultaneously for 4 seconds or more ButtonButton if the unit stops ProcedureTo know the position of indoor unit body by address Ceiling panel RBC-UM11PGWE Preparing work Part name ProcedureDetachment AttachmentPart name Procedure Remarks Panel has directionality Part name Procedure Remarks Ceiling panelNo. Part name Procedure RemarksElectric parts box No. Part name Procedure Fan motor 1. Detachment Drain pump 1. Detachment Drain pan 1. DetachmentDetails of sensor lead wire drawing Part name Procedure Remarks HeatExchanger Recover refrigerant gas RAV-SM∗∗∗BT ∗ Part name Procedure RemarksFan motor Remove the Multi blade fan † Drain pump Remove the drain pan and float switch 100 No. Part name Procedure Remarks101 102 103 104 209404MUT-E 454MUT-E 564MUT-E 105Location Description Model name 404MUT-TR 454MUT-TR 564MUT-TR 106401 Electric parts107 Location Model name108 RAV-SM564BT-E RAV-SM564BT-TR 109110 RAV-SM804BT-E RAV-SM804BT-TR 111112 1104BT-TR 113564BT-E 804BT-E 1104BT-E 1404BT-E 114Location Model name RAV-SM Description 115 264220 Location 116Description Model name RAV-SM 117 Description 564CT-E 804CT-E 1104CT-E 1404CT-E 118Check of Concentration Limit Toshiba Carrier Corporation

CONCEALED DUCK TYPE, CEILING TYPE specifications

Toshiba has long been a name associated with innovative and efficient HVAC solutions, and their Concealed Duck Type, Ceiling Type air conditioning units exemplify this legacy. These units are designed to provide exceptional comfort while seamlessly integrating into a variety of interior spaces.

One of the main features of the Toshiba Concealed Duck Type, Ceiling Type system is its discreet installation method. Unlike traditional wall-mounted units, this system is installed within the ceiling, allowing for an unobtrusive appearance. The result is a clean and modern aesthetic, ideal for residential and commercial settings where design is a priority. With only the supply and return grilles visible, the units maintain the integrity of the interior decor.

The technology employed in Toshiba's air conditioning systems revolves around energy efficiency and user comfort. The units are equipped with inverter technology, which allows for precise temperature control and reduces energy consumption. The inverter adjusts the compressor speed to meet the cooling or heating demand, ensuring not only optimal comfort but also reduced operational costs.

Another significant characteristic of the Toshiba Concealed Duck Type units is their quiet operation. Designed with sound-dampening features, they operate at low noise levels, making them suitable for environments where noise can be a concern, such as offices, hotels, or residential spaces.

Toshiba's advanced air filtration system further enhances indoor air quality. Integrated filters capture dust and allergens, creating a healthier indoor environment. This is particularly beneficial for individuals with allergies or respiratory concerns, as the system works to reduce airborne pollutants.

The units also offer flexible control options. With the availability of remote control or smart home integration, users can easily adjust settings to suit their preferences. Additionally, some models come with programmable timers, allowing for energy savings when the space is unoccupied.

Furthermore, these units are designed for reliability and ease of maintenance. Toshiba emphasizes durability in their construction, and the concealed installation not only enhances aesthetics but also protects the unit from potential damage. Routine maintenance can be performed efficiently, ensuring longevity and sustained performance.

In summary, Toshiba's Concealed Duck Type, Ceiling Type air conditioning units deliver a blend of innovative technology, energy efficiency, and contemporary design. With features like inverter technology, quiet operation, advanced air filtration, and flexible control options, they offer a compelling choice for those seeking comfort without compromising style. These units stand as a testament to Toshiba's commitment to quality and customer satisfaction in the HVAC industry.