Toshiba CEILING TYPE Item No. DN table Selection of function, Description At shipment

Page 72

Item No. (DN) table (Selection of function)

DN

Item

 

 

 

Description

 

 

 

 

At shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

Filter sign lighting time}

0000

: None

 

 

 

 

 

 

 

 

0002

: 2500H

 

 

0002

: 2500H (4-Way/Duct/Ceiling Type)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

Dirty state of filter

0000

: Standard

 

0001 : High degree of dirt

 

 

0000

: Standard

 

 

 

 

 

 

 

 

(Half of standard time)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

Central control address

0001

: No.1 unit

to

0064 : No.64 unit

 

 

0099

: Unfixed

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

Heating suction temp shift

0000

: No shift

 

0001 : +1°C

 

 

 

0002

: +2°C

 

 

0002

: +2°C

to

0010 : –10°C

 

 

 

 

 

 

 

 

 

 

 

(Up to recommendation + 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0F

Cooling only

0000

: Heat pump

 

0001 : Cooling only

 

 

0000

: Heat pump

 

 

 

 

 

 

(No display of [AUTO] [HEAT])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Type

0004

: Concealed duct type

0007 : Ceiling type

 

 

According to model type

 

 

0014

: Compact 4-way cassette type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Indoor unit capacity

0000

: Unfixed

 

0006 :

40 type

 

 

 

According to capacity type

 

 

0007

: 45 type

 

0009 :

56 type

 

 

 

 

 

 

 

0012

: 80 type

 

0015 : 110 type

 

 

 

 

 

 

 

0017

: 140 type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Line address

0001

: No.1 unit

to

0030 : No.30 unit

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

13

Indoor unit address

0001

: No.1 unit

to

0064 : No.64 unit

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

14

Group address

0000

: Individual

 

0001 : Master of group

 

 

0099

: Unfixed

 

 

0002

: Follower of group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

Louver type

0000

: No louver

 

0001 : Swing only

 

 

According to model type

 

(Air direction adjustment)

0002

: 1-way

 

0003 : 2-way

 

 

 

 

 

 

None for concealed duct

0004

: 4-way

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1E

Temp difference of

0000

: 0 deg to

 

0010 :

10 deg

 

 

 

0003

: 3 deg (Ts±1.5)

 

automatic cooling/heating

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

 

 

 

mode selection COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT, HEAT COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

Auto restart after power

0000

: None

 

0001 : Auto restart

 

 

0000

: None

 

failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A

Option

 

 

 

 

 

 

 

 

 

 

 

0002

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2b

Thermo output selection

0000

: Indoor thermo ON

 

 

 

 

 

 

 

0000: Thermo. ON

 

(T10 ƒ)

0001

: Output of outdoor comp-ON receiving

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2E

Option

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

Option

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

Option

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

32

Sensor selection

0000

: Body TA sensor

0001 : Remote controller sensor

0000 : Body sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

33

Temperature indication

0000

: °C (celsius)

 

0001 : °F (Fahrenheit)

 

 

0000

:°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

Option

 

 

 

 

 

 

 

 

 

 

 

0003

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

5d

High ceiling selection

0000

: Standard

 

0001 : High ceiling 1

 

 

0000

: Standard

 

(External static pressure

0002

: High ceiling 2

 

0003 : High ceiling 3

 

 

 

 

 

selection)

<Concealed Duct type>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set data

0000

 

 

0001

 

0003

0006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External static

40 Pa

 

70 Pa*1

 

100 Pa*2

20 Pa

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

Standard

High static

 

High static

Low static

 

 

 

 

 

 

 

 

(At shipment)

pressure 1

 

pressure 2

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: SM140 become to 65Pa.

 

 

 

 

 

 

 

 

 

 

 

2: SM140 become to 90Pa.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 72 –

Image 72
Contents Split Type Contents Troubleshooting Indoort UnitOriginal instruction Explanation of indications Explanation of illustrated marksWork undertaken Protective gear worn Indication ExplanationConfirmation of warning label on the main unit DescriptionPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Explanations given to user RelocationDeclaration of Conformity Specifications Safety Caution Concerned to New Refrigerant Copper pipe PipingFlare nut JointTools General tools Conventional tools can be usedConcealed Duct type SM56 type Round ductSM110 type Round duct Space required for Installation and servicing RAV-SM404MUT∗, RAV-SM454MUT∗, RAV-SM564MUT∗Dimension RAV-SM564BT∗, RAV-SM804BT∗, RAV-SM1104BT∗, RAV-SM1404BT∗RAV-SM564CT∗, RAV-SM804CT∗, RAV-SM1104CT∗, RAV-SM1404CT∗ Compact 4-way Cassette Type RAV-SM564BT ∗, RAV-SM804BT ∗, RAV-SM1104BT ∗, RAV-SM1404BT ∗ Ceiling Type RAV-SM564CT ∗, RAV-SM804CT ∗, RAV-SM1104CT ∗, RAV-SM1404CT ∗Specifications of Electrical Parts Parts name Type SpecificationsIndoor Controller Block Diagram Case of Connection of Wired Simple Remote ControllerCase of Connection of Wireless Remote Controller Wireless remote controllerMax units Outline of specifications Remarks Control outline CommandTemperature in heating Heat Outline of specifications Ceiling typeTcj TcnTc n ConditionsSetup at shipment Cooling/dry operation Heating/fan operation All operationsAlarm All modesCase of wired remote controller LCD Figure if To 28C Setup AT Local Outline of specifications Remarks MCC-1402 TCJ Exct Disp CHKIndoor P.C. Board Optional Connector Specifications MCC-1402 Summary of Troubleshooting Before troubleshootingTroubleshooting procedure Wired remote controller typeWireless remote controller type Outline of judgment Lamp indication Check code Cause of trouble occurrenceLamp indication Check code Others Other than Check Code Remote controller detected Indoor unit detectedCentral control devices detected Check Code List Error mode detected by indoor unitError mode detected by outdoor unit Air conditionerOperation of diagnostic function Check Status Power supply error of remote controller, Indoor Check code E01 error E09 errorE04 error E10 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller P10 error F10 errorP12 error P19 error Check by testerExchange to cooling cycle Exchange to heating cycleF02 error F01 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit Temperature Resistance value characteristic table TA, TC, TCJ, TE, TS, to sensorTA, TC, TCJ, TE,TS, to sensor TD, TL sensorPart name Checking procedure Position Resistance valueReplacement procedures CaseSetting data read out from Eeprom C. Board for indoor unit servicing replacement proceduresCode No. required at least Contents Writing the setting data to Eeprom MCC-1402Setting data Factory-set value Setting data Type Type name abbSetting data Type Type Code NoTest Run Setup on Remote Controller Wired remote controller Compact 4-way Cassette Type and Concealed Duct TypeProcedure Description Test cooling operation Test heating operationPractical operation LED Display on Indoor P.C. Board D002 RedD203 Red Function Selection Setup Using the set temperatureTo change the selected indoor unit, proceed to Procedure To change item to be set up, proceed to ProcedureItem No. DN table Selection of function Description At shipmentDescription At shipment Wireless remote controller When connected 2 remote controllers operate an idoor unitWhen connected 2 remote controllers operate the twin Setup methodContents Calling of error history Contents Pushing Test button returns the display to usual displayGroup control operation System exampleIndoor unit power-ON sequence Initial communicationUsual regular communication Microprocessor block diagram Model connection interface wiring connectionModel Connection Interface TCC-LINK adapter Model name TCB-PCNT30TLEWiring Specifications C. Board Switch SW01 SetupHow to set up from indoor unit side by remote controller External view of P.C. board assemblyAddress setup Push Test + Vent buttons for 4 seconds or moreDuring unset time, At shipment from factory is displayed Address Setup Address setup procedureSystem configuration Address Setup & Group Control TerminologyExample Automatic Address Example from Unset Address No miswiring Only turning on source power supply Automatic completionUsing timer time Buttons, set the line address Push SET + CL + Test buttonsSimultaneously for 4 seconds or more ButtonProcedure To know the position of indoor unit body by addressButton if the unit stops Part name Procedure Ceiling panel RBC-UM11PGWE Preparing workDetachment AttachmentPart name Procedure Remarks Part name Procedure Remarks Ceiling panel Panel has directionalityProcedure Remarks No. Part nameElectric parts box No. Part name Procedure Fan motor 1. Detachment Drain pan 1. Detachment Drain pump 1. DetachmentPart name Procedure Remarks Heat Exchanger Recover refrigerant gasDetails of sensor lead wire drawing Part name Procedure Remarks RAV-SM∗∗∗BT ∗Fan motor Remove the Multi blade fan † Drain pump Remove the drain pan and float switch No. Part name Procedure Remarks 100101 102 103 209 104105 Location Description Model name404MUT-E 454MUT-E 564MUT-E 106 404MUT-TR 454MUT-TR 564MUT-TRElectric parts 401107 Location Model name108 109 RAV-SM564BT-E RAV-SM564BT-TR110 111 RAV-SM804BT-E RAV-SM804BT-TR112 113 1104BT-TR114 Location Model name RAV-SM Description564BT-E 804BT-E 1104BT-E 1404BT-E 264 220115 116 Description Model name RAV-SMLocation 117 118 Description 564CT-E 804CT-E 1104CT-E 1404CT-ECheck of Concentration Limit Toshiba Carrier Corporation

CONCEALED DUCK TYPE, CEILING TYPE specifications

Toshiba has long been a name associated with innovative and efficient HVAC solutions, and their Concealed Duck Type, Ceiling Type air conditioning units exemplify this legacy. These units are designed to provide exceptional comfort while seamlessly integrating into a variety of interior spaces.

One of the main features of the Toshiba Concealed Duck Type, Ceiling Type system is its discreet installation method. Unlike traditional wall-mounted units, this system is installed within the ceiling, allowing for an unobtrusive appearance. The result is a clean and modern aesthetic, ideal for residential and commercial settings where design is a priority. With only the supply and return grilles visible, the units maintain the integrity of the interior decor.

The technology employed in Toshiba's air conditioning systems revolves around energy efficiency and user comfort. The units are equipped with inverter technology, which allows for precise temperature control and reduces energy consumption. The inverter adjusts the compressor speed to meet the cooling or heating demand, ensuring not only optimal comfort but also reduced operational costs.

Another significant characteristic of the Toshiba Concealed Duck Type units is their quiet operation. Designed with sound-dampening features, they operate at low noise levels, making them suitable for environments where noise can be a concern, such as offices, hotels, or residential spaces.

Toshiba's advanced air filtration system further enhances indoor air quality. Integrated filters capture dust and allergens, creating a healthier indoor environment. This is particularly beneficial for individuals with allergies or respiratory concerns, as the system works to reduce airborne pollutants.

The units also offer flexible control options. With the availability of remote control or smart home integration, users can easily adjust settings to suit their preferences. Additionally, some models come with programmable timers, allowing for energy savings when the space is unoccupied.

Furthermore, these units are designed for reliability and ease of maintenance. Toshiba emphasizes durability in their construction, and the concealed installation not only enhances aesthetics but also protects the unit from potential damage. Routine maintenance can be performed efficiently, ensuring longevity and sustained performance.

In summary, Toshiba's Concealed Duck Type, Ceiling Type air conditioning units deliver a blend of innovative technology, energy efficiency, and contemporary design. With features like inverter technology, quiet operation, advanced air filtration, and flexible control options, they offer a compelling choice for those seeking comfort without compromising style. These units stand as a testament to Toshiba's commitment to quality and customer satisfaction in the HVAC industry.