York DNP060, DNP048, DNP030 Additional Static Pressure Resistance 2, 2-1/2, 3 TON, Resistance, Iwg

Page 18

036-21366-007-A-1205

TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON

 

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

600

700

800

900

1,000

 

1,100

1,200

1,300

1,400

1,500

1,600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WET EVAPORATOR COIL

.01

.01

.01

.02

.03

.04

 

.05

.06

.07

.08

.09

.09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1

.00

.00

.00

.01

.01

.01

 

.01

.02

.03

.04

.05

.06

FILTER FRAME KIT

.01

.02

.04

.06

.08

.10

 

.13

.16

.17

.18

.19

.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2, 4 AND 5 TON

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1,100

1,200

1,300

1,400

1,500

 

1,600

1,700

1,800

1,900

2,000

 

 

 

 

 

 

 

 

 

 

 

 

WET EVAPORATOR COIL

.02

.03

.04

.05

.06

 

.07

.07

.08

.09

.09

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1

.02

.02

.02

.03

.03

 

.04

.04

.04

.05

.05

FILTER FRAME KIT

.04

.04

.05

.05

.06

 

.07

.08

.09

.10

.11

 

 

 

 

 

 

 

 

 

 

 

 

1.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

THERMOSTAT

UNIT TERMINAL STRIP

** = Minimum wire size of 18 AWG

R

**

R

wire should be used for all

 

 

 

field installed 24 volt wire.

G

 

G

 

 

 

Y

 

Y

 

W

 

W

 

C

 

C

PROGRAMMABLE

THERMOSTAT ONLY

FIGURE 3 - FIELD WIRING DIAGRAM CONTROL WIRING

NOTE:

HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.

24VOLT TRANSFORMER

18

Unitary Products Group

Image 18
Contents Description FeaturingTable of Contents Standard FEATURES/BENEFITS FIELD-INSTALLED Accessories 036-21366-007-A-1205 Unit Component Location Physical Data Model DNPRatings COOLING/GAS Heating MBH Burners RangeDNP024 Cooling Capacities 2 TON Temperature of AIR on Condenser CoilNET Power Sensible CAPACITY1 EvaporatorAIR on Temperature of AIR on Condenser Coil DNP024 Cooling Capacities 2 TON CONT’DTemperature AIR on Evaporator Coil DNP030 Cooling Capacities 2-1/2 TONAIR on WB F DNP036 Cooling Capacities 3 TON AIR onCondenser Coil DNP042 Cooling Capacities 3-1/2 TON DNP048 Cooling Capacities 4 TON DNP060 Cooling Capacities 5 TON WB F Condenser CoilTWO TON AIR Performance SPDSide Supply AIR Blower Performance 208/230 VOLTS1 Bottom Supply AIR Blower Performance 208/230 VOLTS1 RESISTANCE, IWG Additional Static Pressure Resistance 2, 2-1/2, 3 TONAdditional Static Pressure Resistance 3-1/2, 4 and 5 TON WET Evaporator Coil ECONOMIZER1 Filter Frame KITPower Wiring Field Diagram Electrical Data Unit Dimensions Front Unit Minimum CLEARANCES1Knockout Typical Slab on Ground Installation Economizer Roof WeightUnit Shipping Operating SizeRoof Curb DIMENSIONS1 Typical Wiring Diagram D*NP 024 208/230-1-60 Power Supply Typical Wiring Diagram D*NP Power SupplyTypical Wiring Diagram D*NP 060 208/230-1-60 Power Supply Wiring Typical Wiring Diagram D*NP 060 208/230-3-60 Power Supply Unitary Products Group Typical Wiring Diagram D*NP 060 460/575-3-60 Power Supply Typical Wiring Diagram Notes General DescriptionUnit Operating Characteristics 036-21366-007-A-1205 036-21366-007-A-1205