Physical and Electrical Data
MODEL H*DA |
| 18 | 24 | 30 | 36 | 48 |
| 60 | 076 | ||
|
|
|
|
|
|
|
|
| |||
Unit Supply Voltage |
|
| 230 – 1 – 50 |
|
| 380/415 |
| ||||
|
|
|
|
|
|
|
|
| |||
Normal Voltage Range * |
| 216 to 252 |
|
|
|
| |||||
Minimum Circuit Ampacity | 12.4 | 16.2 | 18.4 | 8.1 | 12.0 |
| 12.7 | 20.2 | |||
|
|
|
|
|
|
|
|
|
| ||
Max. Overcurrent Device Amps † | 20.0 | 25.0 | 30.0 | 15.0 | 20.0 |
| 20.0 | 30.0 | |||
Compressor Type |
| Recip | Recip | Recip | Recip | Recip |
| Scroll | Scroll | ||
|
|
|
|
|
|
|
|
|
|
|
|
Compressor Amps | Rated Load | 9.2 | 12.2 | 13.4 | 5.8 | 7.5 |
| 9.5 | 14.7 | ||
|
|
|
|
|
|
|
|
| |||
Locked Rotor | 53.0 | 72.0 | 85.0 | 39.0 | 62.0 |
| 73.0 | 95.0 | |||
|
|
|
|
|
|
|
|
|
| ||
Crankcase Heater |
| No** | No** | Yes | Yes | Yes |
| No** | No** | ||
|
|
|
|
|
|
|
|
|
|
|
|
Fan Motor Amps | Rated Load | 0.9 | 0.9 | 1.4 | 0.8 | 0.8 |
| 0.8 | 1.0 | ||
|
|
|
|
|
|
|
|
| |||
Locked Rotor | 1.4 | 1.4 | 3.12 | 1.8 | 1.8 |
| 2.0 | 1.8 | |||
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| ||
Fan Diameter Inches | 18 | 18 | 18 | 18 | 18 |
| 24 | 24 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Rated HP | 1/8 | 1/8 | 1/4 | 1/4 | 1/4 |
| 1/4 | 1/3 |
|
|
|
|
|
|
|
|
|
|
| |
Fan Motor |
| Nominal RPM | 1075 | 1075 | 1100 | 1075 | 1075 |
| 850 | 940 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Rated Voltage | 230 | 230 | 230 | 460 | 460 |
| 460 | 415 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Face Area Sq. Ft. | 9.4 | 9.4 | 11.3 | 11.3 | 14.1 |
| 20 | 20.0 | |
|
|
|
|
|
|
|
|
|
|
| |
Coil |
| Rows Deep | 1 | 1 | 1 | 1 | 1 |
| 1 | 2 | |
|
|
|
|
|
|
|
|
|
|
| |
|
| Fin / Inches | 16 | 16 | 20 | 20 | 16 |
| 18 | 13 | |
|
|
|
|
|
|
|
|
|
|
| |
Liquid Line OD |
| 3/8 | 3/8 | 3/8 | 3/8 | 3/8 |
| 3/8 | 1/2 | ||
|
|
|
|
|
|
|
|
|
| ||
Vapor Line OD |
| 5/8 | 5/8 | 3/4 | 3/4 | 7/8 |
| 7/8 | |||
|
|
|
|
|
|
|
|
| |||
Operating Weight Lbs. | 124 | 134 | 135 | 140 | 176 |
| 210 | 285 | |||
|
|
|
|
|
|
|
|
|
|
|
|
*. Rated in accordance with ARI Standard 110, utilization range “A”. †. Dual element fuses or HACR circuit breaker.
** No crankcase heat required due to the compressor’s high pressure housing and internal design.
All dimensions are in inches. They are subject to change without
notice. Certified dimensions will be provided upon request. | 48" OVERHEAD | |||||
CLEARANCE | ||||||
|
|
|
|
|
| C |
|
|
|
| Refrigerant | B | |
Unit | Dimensions |
| ||||
Connection |
| |||||
Model |
| (Inches) |
| Line Size |
| |
H*DA | A | B | C | Liquid | Vapor |
|
|
| |||||
018 | 24 | 24 |
|
| AIR IN | |
| 5/8 | 4 SIDES | ||||
024 | 24 | 24 |
|
| ||
|
| A | ||||
030 | 24 | 24 | 3/8 | 3/4 |
| |
036 | 24 | 24 |
| |||
|
|
| ||||
048 | 24 | 24 |
| 7/8 |
| |
060 |
|
| ||||
|
|
| ||||
076 | 1/2 |
|
| |
VAPOR |
|
CONNECTION | |
LIQUID CONNECTION |
|
|
2 | Unitary Products Group |