York YCJD18 FC/MC/PC/UC18A3X, FC/MC/PC/UC18B3X, FC/MC/PC32A3X, FC/MC/PC35B3X, FC/MC/PC35C3X

Page 3

364834-YTG-C-0708

Additional R-410A Charge / Orifice Size for Various Matched Systems

Outdoor Unit

YCJD18

YCJD24

YCJD30

YCJD36

YCJD42

YCJD48

YCJD60

S41S1(H)

S41S1(H)

S41S1(H)

S41S1(H)

S41S1(H)

S41S1(H)

S41S1

 

 

 

 

 

 

 

 

 

Required Orifice or TXV 1,2

0.048 / 902

0.055 / 902

0.061 / 907

0.065 / 903

0.075 / 903

0.073 / 904

0.087 / 905

Factory Charge, lbs-oz

3 - 3

3 - 13

3 - 14

4 - 9

4 - 5

4 - 9

5 - 6

 

 

 

 

 

 

 

 

Indoor Coil3,4

 

 

Additional Charge, Oz

 

 

FC/MC/PC/UC18A3X

48 + 0

902 + 0

 

FC/MC/PC/UC18B3X

48 + 0

902 + 0

 

FC/MC/PC32A3X

55 + 4

61 + 0

902 + 4

907 + 0

 

FC/MC/PC35B3X

55 + 4

61 + 0

902 + 4

907 + 0

 

FC/MC/PC35C3X

55 + 4

61 + 0

902 + 4

907 + 0

 

FC/MC/PC/UC36A3X

55 + 0

902 + 0

 

FC/MC/PC/UC36B3X

55 + 0

902 + 0

 

FC/MC/PC/UC36C3X

55 + 0

902 + 0

 

FC/MC/PC37A3X

55 + 4

61 + 2

65 + 0

902 + 4

907 + 2

903 + 0

 

FC/MC/PC43B3X

55 + 4

61 + 2

65 + 0

75 + 0

902 + 4

907 + 2

903 + 0

903 + 0

 

FC/MC/PC43C3X

55 + 4

61 + 2

65 + 0

75 + 0

902 + 4

907 + 2

903 + 0

903 + 0

 

FC/MC/PC/UC48C3X

65 + 8

75 + 2

73 + 4

903 + 8

903 + 2

904 + 4

 

FC/MC/PC/UC48D3X

65 + 8

75 + 2

73 + 4

903 + 8

903 + 2

904 + 4

 

FC/MC/PC/UC60D3X

73 + 0

87 + 0

904 + 0

905 + 0

 

FC/MC62D3X

87 + 4

905 + 4

 

HC18A3X

48 + 0

902 + 0

 

HC30A3X

55 + 0

902 + 0

 

HC36B3X

55 + 4

61 + 0

902 + 4

907 + 0

 

HC42C3X

55 + 4

61 + 2

65 + 0

75 + 0

902 + 4

907 + 2

903 + 0

903 + 0

 

HC60D3X

87 + 0

905 + 0

 

AHP18B3X

48 + 0

902 + 0

 

AHP30B3X

55 + 4

61 + 0

902 + 4

907 + 0

 

AHP36C3X

61 + 2

65 + 0

907 + 2

903 + 0

 

AHP42C3X

65 + 0

75 + 0

903 + 0

903 + 0

 

Johnson Controls Unitary Products

3

Image 3
Contents Listed YCJD18 YCJD24 YCJD30 YCJD36 YCJD42 YCJD48 YCJD60 ModelFC/MC/PC35B3X FC/MC/PC/UC18A3XFC/MC/PC/UC18B3X FC/MC/PC32A3XFootnotes ProceduresSens Unit AIR HandlerCooling Rated NET MBH Model Seer EER CFMAHP42 AHP18AHP30 AHP36Cooling Unit Model CFM Range Rated NET MBH SEER1 FurnaceVariable Speed Cooling Unit Model Furnace Model MODEL1 RatedSeer AC with Variable Speed FURNACES2 FC/MC/PC48D FC/PC60CFC/MC/PC60D TBD AccessoriesCondensing TemperatureAIR Conditioner Model no Indoor Coil Model noMV12B FC/MC36B MA08B FC/MC35B FC/MC43B FC/MC/PC32 FC/MC/PC35 FC/MC/PC37 FC/MC/PC43FC/MC/PC35 FC/MC/PC37 FC/MC/PC43 AHP30 AHP36MV12B FC/MC35B MV16C FC/MC35C MA12B FC/MC43B FC/MC43C Indoor Coil Model no FC/MC/PC43 Condensing FC/MC/PC43 FC/MC/PC48AHP36 AHP42 AHP42 MV16C FC/MC43C MA16C FC/MC48C MV20D FC/MC48D MA14D Indoor Coil Model no FC/MC/PC48 Condensing FC/MC/PC/UC60D Indoor Coil Model no FC/MC/PC60 CondensingAHP/SHP60 AV/SV60 MV20D FC/MC60D MA20D FC/MC62D FC/PC/UC60CJohnson Controls Unitary Products York Drive Norman, OK