AIR FLOW DATA

 

 

 

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

 

 

060B12

 

 

 

080B12

 

Jumper Settings

High

 

Low

 

High

 

Low

 

COOL Tap

ADJ Tap*

1343

 

865

 

1320

 

882

 

A

B

1116

 

727

 

1093

 

755

 

B

B

1235

 

791

 

1203

 

810

 

A

A

1026

 

661

 

1001

 

693

 

B

A

1079

 

709

 

1080

 

730

 

A

C

889

 

590

 

880

 

641

 

C

B

900

 

599

 

910

 

642

 

B

C

787

 

531

 

803

 

585

 

D

B

814

 

542

 

836

 

597

 

C

A

712

 

490

 

738

 

557

 

D

A

725

 

499

 

749

 

561

 

C

C

641

 

456

 

682

 

529

 

D

C

080C16

 

 

 

100C16

 

Jumper Settings

High

 

Low

 

High

 

Low

 

COOL Tap

ADJ Tap*

1787

 

1171

 

1818

 

1192

 

A

B

1503

 

987

 

1545

 

1030

 

B

B

1620

 

1053

 

1661

 

1083

 

A

A

1405

 

914

 

1427

 

936

 

B

A

1462

 

964

 

1497

 

991

 

A

C

1217

 

785

 

1234

 

819

 

C

B

1245

 

818

 

1265

 

832

 

B

C

940

 

608

 

977

 

648

 

D

B

1091

 

702

 

1116

 

728

 

C

A

852

 

551

 

884

 

572

 

D

A

983

 

626

 

1019

 

666

 

C

C

764

 

544

 

791

 

519

 

D

C

100C20

 

 

 

120D20

 

Jumper Settings

High

 

Low

 

High

 

Low

 

COOL Tap

ADJ Tap*

2019

 

1290

 

2006

 

1397

 

A

B

1790

 

1174

 

1687

 

1131

 

B

B

1818

 

1195

 

1845

 

1282

 

A

A

1630

 

1068

 

1552

 

1050

 

B

A

1649

 

1082

 

1694

 

1157

 

A

C

1269

 

848

 

1502

 

1011

 

C

B

1432

 

956

 

1400

 

944

 

B

C

1078

 

704

 

1365

 

922

 

D

B

1169

 

770

 

1364

 

931

 

C

A

986

 

638

 

1232

 

808

 

D

A

1062

 

685

 

1225

 

808

 

C

C

866

 

576

 

1117

 

718

 

D

C

 

 

 

 

HIGH / LOW

HEAT CFM

 

 

 

060B12

 

 

 

80B12

 

Jumper Settings

High

 

Low

 

High

 

Low

 

HEAT Tap

ADJ Tap*

1364

 

843

 

1433

 

945

 

A

Any

1253

 

745

 

1320

 

887

 

B

Any

1102

 

660

 

1223

 

840

 

C

Any

1014

 

607

 

1134

 

768

 

D

Any

80C16

 

 

 

100C16

 

Jumper Settings

High

 

Low

 

High

 

Low

 

HEAT Tap

ADJ Tap*

1684

 

1095

 

1795

 

1171

 

A

Any

1542

 

1011

 

1585

 

1047

 

B

Any

1426

 

927

 

1420

 

929

 

C

Any

1289

 

832

 

1201

 

785

 

D

Any

100C20

 

 

 

120D20

 

Jumper Settings

High

 

Low

 

High

 

Low

 

HEAT Tap

ADJ Tap*

2194

 

1417

 

1937

 

1323

 

A

Any

1999

 

1290

 

1757

 

1199

 

B

Any

1799

 

1182

 

1594

 

1062

 

C

Any

1614

 

1062

 

1429

 

957

 

D

Any

All CFM’s are shown at 0.5”

w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c.

static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static

pressure is not recommended.

 

 

 

 

 

 

 

 

NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air clean-

ers. Consult the instructions for the electronic air cleaner for further details.

 

 

 

 

 

* The ADJ “D” tap should not be used.

 

 

 

 

 

 

 

 

Subject to change without notice. Printed in U.S.A.

 

 

 

 

444555-YTG-A-0209