York manual Physical Data, DJ 150 12-1/2 TON Capacity Ratings, Unit Voltage Limitations

Page 10

246695-YTG-C-0708

TABLE 2: PHYSICAL DATA

 

 

 

 

 

 

Component

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

DJ 150 (12-1/2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator

 

 

 

 

Blower, Centrifugal (Dia. X Wd. in.)

 

15 x 15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor, Standard (HP)

 

 

3

 

 

 

 

Blower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor, Optional (HP)

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator

 

 

 

 

 

Fins per Inch

 

 

15

 

 

 

Coil

 

 

 

 

 

 

Height (in.)

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Face Area (ft.2 each)

 

 

13.2

 

 

Condenser

 

 

 

 

 

Propeller Dia. (in., each)

 

24

 

 

 

Fan

 

 

 

 

 

 

Motor (HP, each)

 

 

1/3

 

 

 

(4 per Unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM, Nominal (each)

 

 

3500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

Rows (each)

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fins per Inch

 

 

15

 

 

 

Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height (in., each)

 

 

36

 

 

 

(2 per unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Face Area (ft.2 each)

 

 

11.88

 

 

Refrigerant

 

 

 

 

 

System 1 (lb./oz.)

 

 

2/0

 

 

 

Charge

 

 

 

 

 

System 2 (lb./oz.)

 

 

20/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressors

 

 

 

 

 

Quantity

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Filters

 

 

 

 

Size (Wd. x Ht. x Thickness in.)

 

25x20x2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number Per Unit

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 3: DJ 150 (12-1/2 TON) CAPACITY RATINGS

 

 

 

 

 

 

 

 

 

 

Cooling Capacity

 

 

Sound

Nominal

 

 

Gas Heat Capacity

 

 

Gas

 

Size

 

ARI Ratings1

 

 

Electric

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line

 

Model

 

 

 

CFM

 

Rating

Heat

 

 

 

 

 

 

 

(Tons)

 

 

 

 

 

 

 

 

 

 

Size

 

 

MBH

EER

IPLV

 

 

(dB)2

Capacity3

Input

 

Output

Seasonal

Temp.

 

 

 

 

 

 

 

 

(in. OD)

 

 

 

 

 

 

(kW)

(MBH)

 

(MBH)

Efficiency (%)

Rise (°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

-

-

 

-

-

-

 

-

 

 

Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric

150

11.35

12.3

3750

 

86

18, 24, 36

-

 

-

-

-

 

-

 

(12-1/2)

Heat

 

54

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat

 

 

 

 

 

 

-

180

 

144

80

10-40

 

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat

 

 

 

 

 

 

-

240

 

192

80

25-55

 

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.

2Rated in accordance with ARI 270 standard.

3See Table 8.

TABLE 4: UNIT VOLTAGE LIMITATIONS

POWER RATING

MIN.

MAX.

 

 

 

208/230-3-60

187

252

 

 

 

460-3-60

432

504

 

 

 

575-3-60

540

630

 

 

 

10

Johnson Controls Unitary Products

Image 10
Contents Technical Guide Table of Contents Features Johnson Controls Unitary Products Factory Installed Options Field Installed Accessories Low Limit / Compressor Lockout Kit Accessories Part Number Description WeightTon Model Number Nomenclature DJ 150 12-1/2 TON Capacity Ratings Physical DataUnit Voltage Limitations DJ 150 12 1/2 TON Cooling Capacity MBHElectrical Data DJ150 12-1/2 TON W/O Pwrd Convenience Outlet Electric Heat MultipliersBlower Performance 12-1/2 TON Side Duct 4900Blower Performance 12-1/2 TON Downshot Additional Static Resistance Indoor Blower SpecificationsPower Exhaust Specifications Electric Heat Minimum Supply AIR CFMModel Location lbs Unit WeightsModel Locations lbs Unit Dimensions Unit Clearances Detail CPredator Magnum Roof Curb Dimensions Bottom Duct Openings from Above Downflow Economizer Hood Detail Economizer Usage Application Description ModelField Installed Downflow Economizer W/POWER Exhaust Slab Economizer Downflow W/POWER Exhaust Cooling Unit with GAS Heat Wiring 230 V. Diagram Cooling Unit W/WO Electric Heat Wiring Diagram Cooling Unit with GAS Heat Wiring 460, 575 & 50 HZ Diagram General Indoor Evaporator FAN AssemblyOutdoor Condenser FAN Assembly DescriptionElectric Heating Section if Equipped Unit Operating CharacteristicsGAS Heating Section if Equipped Electrical RequirementsOther PRE-ENGINEERED Accessories AVAIL- Able Additional Factory Installed OptionsJohnson Controls Unitary Products York Drive Norman, OK
Related manuals