TABLE 18: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE060
|
|
| HEATER | SUPPLY |
| ELECTRIC HEATERS | TOTAL | MAX. | MAX. | ||
|
|
| AIR |
|
|
|
| ||||
MODEL | POWER | ACCESSORY |
|
|
|
| UNIT | FUSE | SIZE | ||
BLOWER |
|
|
| TOTAL | |||||||
DHE | SUPPLY | MODEL | kW |
| STAGES | AMPACITY | SIZE1 | HACR2 | |||
MOTOR |
| ||||||||||
|
|
| NUMBER |
|
|
| AMPS | AMPS | AMPS | AMPS | |
|
|
| FLA |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
| 2CE045005253 |
| 4.0 |
| 1 | 11.0 | 26.0 | 40 | 40 |
|
|
| 2CE045007254 |
| 5.6 |
| 1 | 15.6 | 26.9 | 40 | 40 |
|
| 2CE04501025 | 6.0 | 8.0 |
| 1 | 22.1 | 35.1 | 40 | 40 | |
|
| 2CE04501525 | 11.9 |
| 2 | 33.1 | 48.9 | 50 | 50 | ||
|
|
|
|
| |||||||
|
|
| 2CE04502025 |
| 15.9 |
| 2 | 44.2 | 62.7 | 70 | 70 |
|
|
| 2CE04503025 |
| 22.2 |
| 2 | 61.7 | 84.6 | 90 | 90 |
|
|
| 2CE045005254 |
| 5.3 |
| 1 | 12.7 | 26.0 | 40 | 40 |
|
|
| 2CE045007254 |
| 7.5 |
| 1 | 18.0 | 30.1 | 40 | 40 |
060 |
| 2CE04501025 | 6.0 | 10.6 |
| 1 | 25.5 | 39.4 | 40 | 40 | |
|
|
| 2CE04501525 |
| 15.9 |
| 2 | 38.2 | 55.3 | 60 | 60 |
|
|
| 2CE04502025 |
| 21.2 |
| 2 | 51.0 | 71.2 | 80 | 80 |
|
|
| 2CE04503025 |
| 29.6 |
| 2 | 71.2 | 96.5 | 100 | 100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2CE045007464 |
| 6.8 |
| 1 | 8.2 | 14.0 | 20 | 20 |
|
|
| 2CE045010464 |
| 10.1 |
| 1 | 12.1 | 18.9 | 20 | 20 |
|
| 2CE045015464 | 3.0 | 13.6 |
| 1 | 16.4 | 24.2 | 25 | 25 | |
|
|
| 2CE045020464 |
| 19.5 |
| 2 | 23.5 | 33.1 | 35 | 35 |
|
|
| 2CE045030464 |
| 28.8 |
| 2 | 34.6 | 47.1 | 50 | 50 |
1.Dual element, time delay type.
2.Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), refer to Table 17 for fuse block accessories available for field installation.
FIGURE 2 - FIELD POWER WIRING
COOLINGONLY(24VOLTTHERMOSTAT)
THERMOSTAT1 UNITTERMINAL
TERMINALS STRIPTB1
RVR
|
| 24VOLT |
YC | Y1 | TRANSFORMER |
|
| |
| Y2 |
|
GF
B
124VOLTTHERMOSTAT2TH07701024IFTHEUNITHASANECONOMIZER, REMOVEJUMPERJ1FROMTERMINALS8AND10ONTHERELAYBOARD TOPREVENTSIMULTANEOUSOPERATIONOFTHECOMPRESSORAND THEECONOMIZER.IFYOUWANTTOCONTROLTHEECONOMIZERONA SECONDSTAGEOFCOOLING,USETHETHERMOSTAT2TH04701224.
FIGURE 3 - CONTROL WIRING COOLING ONLY
16 | Unitary Products Group |