York D2HE/D2HG060 warranty Motor and Drive Data BELT-DRIVE Blower, Electrical Data Basic Unit

Page 14

036-21216-003-A-0204

TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER

 

 

 

 

MOTOR1

 

ADJUSTABLE

FIXED

 

BELT

 

 

BLOWER

 

 

 

MOTOR PULLEY

BLOWER PULLEY

 

 

 

 

 

 

 

 

 

MODEL

RANGE

 

 

FRAME

SERVICE

PITCH

BORE

PITCH

 

BORE

PITCH

 

DESIG-

 

(RPM)

HP

RPM

DIA.

DIA.

 

LENGHT

 

 

SIZE

FACTOR

(in.)

 

(in.)

 

NATION

 

 

 

 

(in.)

(in.)

 

(in.)

 

 

 

 

 

 

 

 

 

 

 

 

DHE/DHG 036

780 - 1120

11/2

1,725

56

1.15

2.4 - 3.4

7/8

5.7

 

1

37.3

 

A36

DHE/DHG048

790 - 1,120

11/2

1,725

56

1.15

2.4 - 3.4

7/8

5.7

 

1

37.3

 

A36

DHE/DHG060

850 - 1,220

11/2

1,725

56

1.15

2.4 - 3.4

7/8

5.2

 

1

37.3

 

A36

1.All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device

TABLE 14: ELECTRICAL DATA - BASIC UNIT

 

 

VOLTAGE

COMPRESSOR

COND.

SUPPLY

TOTAL

MAX.

MAX.

MODEL

 

LIMITATIONS1

HACR

POWER

 

 

FAN

AIR

UNIT

FUSE

DHE/

SUPPLY

 

 

 

 

MOTOR

AMPACITY

AMPACITY

SIZE2

BREAKER

 

 

 

 

DHG

MIN.

MAX.

RLA

LRA

SIZE

 

FLA

AMPS

AMPS

AMPS

 

 

AMPS

 

 

 

 

 

 

 

 

 

 

036

208/230-3-60

187

253

14.1

110

2.3

5.3

25.2

35

35

460-3-60

414

504

7.1

54

1.4

3.1

13.3

20

20

 

 

 

 

 

 

 

 

 

 

 

 

048

208/230-3-60

187

253

10.0

110.0

2.3

5.2

23.9

35

35

460-3-60

414

504

5.2

54.0

1.4

2.6

12.4

15

15

 

 

 

 

 

 

 

 

 

 

 

 

060

208/230-3-60

187

253

16.0

137.0

2.3

6.0

28.3

40

40

460-3-60

414

504

8.3

69.0

1.4

3.0

14.8

20

20

 

1.Rated in accordance with ARI Standard 110, utilization range “A”..

2.Dual element, time delay type.

14

Unitary Products Group

Image 14
Contents Featuring Flexible Light Commercial UnitGeneral List of Tables Table of ContentsList of Figures Features DescriptionFACTORY-INSTALLED Option FIELD-INSTALLED AccessoriesCapacity Rating Cooling / Electric Heat RATING3 MBH SEER4 EER5Physical Data Basic Unit Sound Power RATINGS1Capacity Ratings Cooling / GAS Heating Total Sensible Capacity Power Temperature of AIR on Condenser CoilTotal Power Sensible CAPACITY3 EvaporatorTotal Power Sensible Capacity CFM MBH InputCooling Capacities Models DHE/DHG048 Total Power CAP.1 Entering DRY BULB, F CFM MBH InputTotal Power CAP.1 Evaporator Sensible CAPACITY3Total Power CAP.1 Entering DRY BULB, F Input CFM MBH Cooling Capacities Models DHE/DHG060Supply AIR Blower Performance -DHE/DHG036 RPM WattsWatts Accessory Static Resistance Motor and Drive Data BELT-DRIVE Blower Electrical Data Basic UnitElectric Heat Correction Factors DHE048 Fuse Block AccessoryElectrical Data COOLING/ELECTRIC Heat DHE036 Electrical Data COOLING/ELECTRIC Heat DHE060 Amps FLAControl Wiring Single Stage Hole Knockout Size DIAUnit Dimensions DHG Unit Clearances Rear Dimensions of DHE and DHG Units 3, 4 & 5 TON Units Unit and Curb Application Unit Corner WEIGHTS1 Weight DescriptionTypical Applications Equipment Mechanical SpecificationsGeneral Description Heating Section 036-21216-003-A-0204 036-21216-003-A-0204 036-21216-003-A-0204