TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER
|
|
|
| MOTOR1 |
| ADJUSTABLE | FIXED |
| BELT |
| |||
| BLOWER |
|
|
| MOTOR PULLEY | BLOWER PULLEY |
| ||||||
|
|
|
|
|
|
|
| ||||||
MODEL | RANGE |
|
| FRAME | SERVICE | PITCH | BORE | PITCH |
| BORE | PITCH |
| DESIG- |
| (RPM) | HP | RPM | DIA. | DIA. |
| LENGHT |
| |||||
| SIZE | FACTOR | (in.) |
| (in.) |
| NATION | ||||||
|
|
|
| (in.) | (in.) |
| (in.) |
| |||||
|
|
|
|
|
|
|
|
|
|
| |||
DHE/DHG 036 | 780 - 1120 | 11/2 | 1,725 | 56 | 1.15 | 2.4 - 3.4 | 7/8 | 5.7 |
| 1 | 37.3 |
| A36 |
DHE/DHG048 | 790 - 1,120 | 11/2 | 1,725 | 56 | 1.15 | 2.4 - 3.4 | 7/8 | 5.7 |
| 1 | 37.3 |
| A36 |
DHE/DHG060 | 850 - 1,220 | 11/2 | 1,725 | 56 | 1.15 | 2.4 - 3.4 | 7/8 | 5.2 |
| 1 | 37.3 |
| A36 |
1.All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device
TABLE 14: ELECTRICAL DATA - BASIC UNIT
|
| VOLTAGE | COMPRESSOR | COND. | SUPPLY | TOTAL | MAX. | MAX. | |||
MODEL |
| LIMITATIONS1 | HACR | ||||||||
POWER |
|
| FAN | AIR | UNIT | FUSE | |||||
DHE/ | SUPPLY |
|
|
|
| MOTOR | AMPACITY | AMPACITY | SIZE2 | BREAKER | |
|
|
|
| ||||||||
DHG | MIN. | MAX. | RLA | LRA | SIZE | ||||||
| FLA | AMPS | AMPS | AMPS | |||||||
|
| AMPS | |||||||||
|
|
|
|
|
|
|
|
|
| ||
036 | 187 | 253 | 14.1 | 110 | 2.3 | 5.3 | 25.2 | 35 | 35 | ||
414 | 504 | 7.1 | 54 | 1.4 | 3.1 | 13.3 | 20 | 20 | |||
| |||||||||||
|
|
|
|
|
|
|
|
|
|
| |
048 | 187 | 253 | 10.0 | 110.0 | 2.3 | 5.2 | 23.9 | 35 | 35 | ||
414 | 504 | 5.2 | 54.0 | 1.4 | 2.6 | 12.4 | 15 | 15 | |||
| |||||||||||
|
|
|
|
|
|
|
|
|
|
| |
060 | 187 | 253 | 16.0 | 137.0 | 2.3 | 6.0 | 28.3 | 40 | 40 | ||
414 | 504 | 8.3 | 69.0 | 1.4 | 3.0 | 14.8 | 20 | 20 | |||
|
1.Rated in accordance with ARI Standard 110, utilization range “A”..
2.Dual element, time delay type.
14 | Unitary Products Group |