CONTACTOR
DISCONNECT
REFER TO ELECTRICAL
GROUND | DATA TABLES TO SIZE | |
LUG | ||
THE DISCONNECT | ||
| ||
| CONTACTOR |
GROUND
LUG REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT
SINGLE
PHASE
POWER
SUPPLY
DISCONNECT
THREE
PHASE
POWER
SUPPLY
FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM
TABLE 12: ELECTRICAL DATA
|
| VOLTAGE | COMPRESSOR | COND. | SUPPLY |
| MAX. | MAX. |
|
| |||
MODEL | POWER | LIMITATIONS1 | AIR | MINIMUM | HACR | UNIT | TRANSFORMER | ||||||
|
| FAN | FUSE | ||||||||||
DNA | SUPPLY |
|
|
|
| MOTOR, | BLOWER | CIRCUIT | SIZE, | BREAKER | POWER | SIZE (VA) | |
MIN. | MAX. | RLA | LRA | ||||||||||
|
| FLA | MOTOR | AMPACITY | AMPS2 | SIZE, | FACTOR |
| |||||
|
|
|
|
|
|
| FLA |
|
| AMPS |
|
| |
030 | 187 | 253 | 14.7 | 73 | 1.1 | 2.2 | 21.7 | 30 | 30 | 0.96 | 40 | ||
036 | 187 | 253 | 17.3 | 94 | 1.1 | 3.5 | 26.2 | 35 | 35 | 0.96 | 40 | ||
036 | 187 | 253 | 10.9 | 78 | 1.1 | 3.5 | 18.2 | 25 | 25 | 0.96 | 75 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
036 | 414 | 504 | 5.8 | 40 | 0.6 | 1.8 | 9.6 | 15 | 15 | 0.96 | 75 | ||
042 | 187 | 253 | 15.4 | 86 | 1.1 | 3.5 | 23.9 | 30 | 30 | 0.96 | 40 | ||
042 | 187 | 253 | 11.5 | 88 | 1.1 | 3.5 | 19 | 25 | 25 | 0.96 | 75 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
042 | 414 | 504 | 5.8 | 42 | 0.6 | 1.8 | 9.7 | 15 | 15 | 0.96 | 75 | ||
048 | 187 | 253 | 24.4 | 140 | 1.3 | 7 | 38.8 | 50 | 50 | 0.96 | 40 | ||
048 | 187 | 253 | 14.1 | 105 | 1.3 | 7 | 25.9 | 35 | 35 | 0.96 | 75 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
048 | 414 | 504 | 7.1 | 55 | 0.7 | 3.5 | 13.1 | 20 | 20 | 0.96 | 75 | ||
060 | 187 | 253 | 28.9 | 175 | 1.3 | 7 | 44.4 | 60 | 60 | 0.96 | 40 | ||
060 | 187 | 253 | 15.5 | 125 | 1.3 | 7 | 29.5 | 40 | 40 | 0.96 | 75 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
060 | 414 | 504 | 8.9 | 66.5 | 0.7 | 3.5 | 15.4 | 20 | 20 | 0.96 | 75 |
1.Utilization range “A” in accordance with ARI Standard 110.
2.Dual element, time delay type.
Johnson Controls Unitary Products | 15 |