Installation and Operation |
|
INSTALLATION
Use Tables A & B to determine the proper size of fuse protection and the length and size of wiring required. Portable extension cords, if used, should be as short as possible to minimize voltage drop. Cords that are too long, or cords that are made of inadequate wire gauge, can cause the motor to fail.
|
| TABLE A | (WIRE SIZE) |
|
| ||
|
|
|
| DISTANCE |
| ||
| MOTOR | 25 FT |
| 50 FT |
| 100 FT | 200 FT |
|
|
|
|
|
| ||
982 | (1/3 | #18 GA | #16 GA | #12 GA | #10 GA | ||
986 | (1 | #14 GA | #14 GA | #12 GA | #10 GA | ||
996 | #14 GA | #14 GA | #12 GA | #10 GA |
|
| TABLE B | (FUSE SIZE) | |
| MOTOR |
| TYPE OF FUSE | |
| DUAL ELEMENT TIME DELAY | |||
|
|
|
|
|
982 | (1/3 | 15 |
| 12 |
986 | (1 | 15 |
| 12 |
996 | 20 |
| 15 |
6