QuickSpecs
HP ProLiant BL25p Server Blade
Technical Specifications
Relative Humidity | Operating | 20% to 80% |
5% to 95% | ||
| ||
Wet Bulb | Operating | 82.4° F (28° C) |
Temperature | 101.7° F (38.7° C) | |
|
NOTE: Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper
Operating and
Performance Specifications for Power Enclosures
|
|
|
| |
Dimensions | Height | 5.25 in (13.34 cm) | 5.25 in (13.34 cm) | |
| Width | 27.15 in (68.96 cm) | 27.15 in (68.96 cm) | |
| Depth | 17.60 in (44.7 cm) | 17.60 in (44.7 cm) | |
Weights | No | 47.5 lb (21.55 kg) | 47.5 lb (21.55 kg) | |
| Power Supplies |
|
| |
| All | 99.5 lb (45.13 kg) | 125.5 lb (56.93 kg) | |
| Power Supplies |
|
| |
Input Requirements | Rated input voltage | 200 VAC to 240 VAC | 200 VAC to 240 VAC | |
|
|
| line to line | |
| Rated input frequency | 50 Hz to 60 Hz | 50 Hz to 60 Hz | |
| Rated input current | 24A | 24A per phase | |
| per side |
|
| |
| Rated input power | 5760 W | 9976 W | |
| per side |
|
| |
| Power cord | 1 NEMA | 1 NEMA | |
|
| side | side | |
Output Voltage | Rated output voltage | |||
Specifications | Rated output current | 99A | 170A | |
| ||||
| Rated output power | 4298 W | 8310 W | |
| Nominal power | 4158 W at 208 VAC | 7202 W at 208 VAC | |
Ambient Temperature | Operating | 50° to 95° F | 50° to 95° F | |
Range (See NOTE) |
| (10° to 35° C) | (10° to 35° C) | |
| Shipping | |||
|
| |||
Relative humidity, | Operating | 20% to 80% | 20% to 80% | |
5% to 95% | 5% to 95% | |||
(See NOTE) | ||||
|
|
| ||
Wet Bulb | Operating | 82.4° F (28° C) | 82.4° F (28° C) | |
Temperature | 101.7° F (38.7° C) | 101.7° F (38.7° C) | ||
|
NOTE: Operating temperature has an altitude derating of 34° F (1° C) per 1,000 ft (304.8 m). No direct sunlight. Upper operating limit is 10,000 ft (3,048 m) or 70Kpa/10.1 psia. Upper
DA - 12160 North America — Version 7 — June 27, 2005 | Page 43 |