DEFROST SEQUENCE OF OPERATION

These heat pumps have a unique “ambient modified” time- temperature defrost control that automatically adjusts to changes in the outdoor temperature. The defrost control shortens the defrost initiation time periods above 2°C (35°F) and extends the defrost initiation time periods below 2°C (35°F. The control is factory set to defrost at 110 minutes (T3), but it can be field adjusted to defrost at 80 minutes (T2) or 50 minutes (T1) in areas with high humidity.

The curve in Figure 10 shows how defrost initiation times are automatically compensated for changes in outdoor temperature.

EXAMPLE: If the timer is factory set on pin T3 (110 minutes at 2°C (35°F) outdoor) and the outdoor temperature climbs to 7°C (45°F), the time initiation cycle decreases to 100 minutes.

If the outdoor temperature drops to -12°C (10°F) where ice is less likely to form, the 110 minute interval increses to 150 minutes.

Two requirements must be met before a defrost cycle can be initiated.

1.The defrost time cycle must be complete.

2.The liquid line temperature must be less than -2°C (28°F).

Defrost terminates when the liquid line sensor reaches 13°C (55°F) or after 10 minutes. If one or both circuits defrosts, electric heat is energized.

The defrost time cycle restarts 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after three minutes.

During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 13mm (12in.) long, 5mm (316 in.) apart and are mounted on a white base. See Figure 11.

035-18895-000-A-0902

LOCKOUT CONTROL

Any one of four conditions put the system into a lock-out condition during the heating or cooling mode:

1.The discharge line temperature reaches 124°C (255°F) (102°C reset [215°F]) or,

2.The discharge pressure reaches 2,786 kPa (398 psig) (2,170 kPa reset [310 psig]) or,

3.The suction line freezestat equals -3°C (26°F) (3°C reset [38°F]), or

4.The low-pressure cut-out equals 49 kPa (7 psig) (154 kPa [22 psig]).

A lock-out energizes the emergency heat light on the thermostat and the red LED light on the unit relay board. Turning the thermostat switch to “off”, then back to “on” will reset the system.

NOTICE TO OWNER:

If a lockout occurs, check for the following problems before calling a serviceman:

1.Dirty filters.

2.Snow accumulation.

3.Leaf or debris blockage.

After eliminating the problem, attempt to restart the system as follows:

turn the system switch on the thermostat to its “OFF” position for 10 seconds.

turn it back to its original position.

If the unit doesn't start, call a service man.

NOTE: Models with an anti-cycle accessory have a five minute delay before restarting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-23

 

-17

 

-12

 

-7

 

-1

 

5

 

10

 

16

(-10)

 

(0)

 

(10)

 

(20)

 

(30)￿

 

(40)

 

(50)

 

(60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C (￿F)

FIG. 10 - DEFROST INITIATION TIMES

14

Unitary Products Group

Image 14
Contents Reference GeneralInspection Table of Contents Installation Condensate Drain Service AccessFixed Outdoor AIR Intake Damper CompressorsPower and Control Wiring Optional Electric HeatersEnthalpy Setpoint Adjustment Optional Economizer / Motorized Damper Rain HoodBasic Centrifugal Blower AccessoriesComponent Description Unit Size UnitReturn AIR Supply AIR Outdoor AIR Opening Hole Diameter Used forContd. Dimensions and Clearances Speed Turns ESP Downflow Duct Connections CFM B*CH180 UnitBlower Motor Airflow Pulley RPM OpenElectric Heat Options DescriptionWET Coil Economizer Option Sideflow Duct ConnectionsPreliminary Operation OperationCooling System Cooling Sequence of OperationChecking Supply Airflow Heater SETTING, Amps TH1 TH2Heat Anticipator Setpoint Belt Drive BlowerDefrost Sequence of Operation Lockout ControlT2 80 Minute Setting T3 110 Minute Setting MaintenanceNormal Maintenance Motors

B2CH180 specifications

The York B2CH180 is a notable addition to the world of commercial heating and cooling systems, designed to meet the demands of a wide range of applications. As part of a renowned legacy in HVAC (Heating, Ventilation, and Air Conditioning) solutions, the B2CH180 unit brings a combination of efficiency, reliability, and innovative technology to ensure optimal performance.

At its core, the York B2CH180 features a high-efficiency, two-stage compressor that significantly enhances its operational effectiveness. This design not only enables precise temperature control but also ensures quieter operation, making it suitable for various environments, including schools, offices, and retail spaces. The two-stage compressor operates at different capacity levels, allowing for better modulation of the system's output based on real-time demands.

One of the standout characteristics of the B2CH180 is its exceptional energy efficiency. With advanced SEER (Seasonal Energy Efficiency Ratio) ratings, this unit helps users to lower energy costs while minimizing their environmental footprint. The use of eco-friendly refrigerants, compliant with the latest regulations, further emphasizes York’s commitment to sustainability.

In terms of control technologies, the York B2CH180 integrates sophisticated smart controls that allow for seamless connection to building management systems. These controls facilitate remote monitoring and adjustment, providing facility managers with valuable insights into operational efficiencies. They can also enable predictive maintenance, alerting users to potential issues before they escalate.

Additionally, this model prioritizes ease of installation and maintenance. Its modular design and accessible components ensure that technicians can perform required services quickly, reducing downtime and enhancing system reliability. The durable construction of the B2CH180, including weather-resistant housing and corrosion-inhibiting coatings, contributes to its long lifespan and low maintenance needs.

The York B2CH180 is also compatible with various accessories and add-ons, allowing for customization based on specific heating and cooling needs. Its versatile application range makes it suitable not only for commercial spaces but also for industrial uses, where powerful performance is essential.

In conclusion, the York B2CH180 is a cutting-edge solution that embodies efficiency, innovative technology, and user-friendly features, making it a top choice for businesses looking to optimize their HVAC systems and enhance occupant comfort.