York 2000 warranty Static Resistances, Heater / CFM Limitations

Page 10

036-21564-003-A-1005

STATIC RESISTANCES

EXTERNAL STATIC PRESSURE DROP

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

DESCRIPTION

 

 

 

 

CFM

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

Economizer1, 2

 

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

Electric Heaters1

 

5 - 15 KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

 

20 - 30 KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

 

 

Bottom Duct Connections1

 

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

1Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

HEATER / CFM LIMITATIONS

HEATER

 

UNIT MODEL SIZE, NOMINAL TONS

SIZE

VOLTAGE1

3

4

5

NOM. KW

 

MINIMUM SUPPLY AIR CFM

5

 

1,100

1,300

1,600

7

 

1,100

1,300

1,600

10

208 /

1,200

1,300

1,600

15

230-1-60

1,200

1,300

1,600

20

 

1,3002

1,3002

1,600

30

 

-

-

1,600

5

 

1,100

1,300

1,600

7

 

1,100

1,300

1,600

10

208 /

1,200

1,300

1,600

15

230-3-60

1,200

1,300

1,600

20

 

1,3002

1,3002

1,600

30

 

-

-

1,600

HEATER

 

UNIT MODEL SIZE, NOMINAL TONS

SIZE

VOLTAGE1

3

4

5

NOM. KW

 

MINIMUM SUPPLY AIR CFM

7

 

1,100

1,300

1,600

10

 

1,200

1,300

1,600

15

460-3-60

1,200

1,300

1,600

20

 

1,300

1,300

1,600

30

 

-

-

1,600

10

 

1,200

1,300

1,600

15

575-3-60

1,200

1,300

1,600

20

1,300

1.400

1,600

 

30

 

-

-

1,800

1208/230 and 460 volt heaters are UL approved. 208/230 and 575 volt heaters are CGA approved.

2CGA minimum is 1,400 CFM.

FIELD WIRING

CONTROL WIRING

2

124-volt thermostat with subbase: —2TH11700224 for manual changeover. —2TH11704124 for automatic changeover.

2Only required on units with supplemental electric heat.

2

3

4

TO REMOTE SENSOR 2TH04702224 IF USED

REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, THE WIRING AND OVERCURRENT PROTECTION

POWER WIRING

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE

DISCONNECT SWITCH, THE

WIRING AND OVERCURRENT

PROTECTION

10

Unitary Products Group

Image 10
Contents Single Package AIR-TO-AIR Heat Pumps FeaturesDescription 036-21564-003-A-1005Features Contd Table of ContentsPhysical Data Basic Units Sound Power RatingsRatings Capacity RatingsCooling Capacities 3 TON BCH036 Sensible Capacity Total Cooling Capacities 4 TON BCH048Air On Cap Input Entering Dry Bulb, FCooling Capacities 5 TON BCH060 2500 2250 2000 1750 1500CFM RET. AIR CAP Outdoor AIR TEMPERATURE, F 72% RH MBH Heating CapacitiesModel AIR Flow BCH CFM RPMBCH Speed CFM Model MotorMED Static Resistances Heater / CFM LimitationsBlower Circuit Size Breaker BCH PLY Motor Ampacity MIN MAX RLA LRA FLA AmpsSize Number Motor Amps Ampacity Breaker FLA MIN MAX RLA LRA FLA Amps2CE04511506 15.9 208-1-60 2CE04511006230-1-60 2CE04511006 10.6 2CE04512006 21.2Knockout Hole Size Used for DIA Control Wiring Side or Bottom Power WiringDirect-Drive Units Outdoor AIR EconomizerDetail a Unit Dimensions CONTD. BCH 3, 4 & 5 TONRear View Unit with Economizer RainhoodComponent Weights and Center of Gravity Roof Curb DimensionsCenter of Gravity Factory Installed Options FIELD--INSTALLED AccessoriesTypical ROOF-TOP Installation Typical ApplicationsMechanical Specifications Electric Heating Section Unit Operating CharacteristicsOther PRE--ENGINEERED Accessories Available Electrical RequirementsOther Factory Installed Options 036-21564-003-A-1005 Unitary Products Group 8QLWDU\3URGXFWV*URXS