York 2000 warranty Heating Capacities, CFM RET. AIR CAP Outdoor AIR TEMPERATURE, F 72% RH MBH

Page 7

036-21564-003-A-1005

HEATING CAPACITIES

 

 

 

 

 

BCH036

 

 

 

 

 

CFM

RET. AIR

CAP

 

 

OUTDOOR AIR TEMPERATURE, °F (72% RH)

 

 

°F

& KW

-10

0

10

20

30

40

50

60

 

 

55

MBH

13.1

16.4

23.5

29.1

30.2

41.7

47.0

48.2

 

KW

2.9

3.0

3.2

3.3

3.5

3.7

3.8

3.9

 

 

1750

70

MBH

11.9

15.0

21.5

26.7

27.7

38.2

43.1

44.1

KW

3.0

3.1

3.4

3.4

3.6

3.8

3.9

4.1

 

 

 

80

MBH

10.9

13.6

19.6

24.3

25.2

34.8

39.3

40.2

 

KW

3.1

3.2

3.4

3.5

3.8

3.9

4.1

4.2

 

 

 

55

MBH

12.4

15.5

22.5

27.7

28.7

39.6

44.7

45.8

 

KW

2.7

2.9

3.0

3.1

3.3

3.5

3.6

3.7

 

 

1400

70

MBH

11.4

14.1

20.3

25.2

26.1

36.1

40.7

41.6

KW

2.9

3.0

3.2

3.3

3.5

3.7

3.8

3.9

 

 

 

80

MBH

10.4

13.1

18.0

23.2

24.2

33.3

37.6

38.5

 

KW

3.0

3.1

3.2

3.4

3.6

3.8

3.9

4.0

 

 

 

55

MBH

11.8

14.8

21.3

26.5

27.5

37.8

42.7

43.7

 

KW

2.7

2.8

3.0

3.1

3.3

3.4

3.5

3.6

 

 

1200

70

MBH

10.8

13.5

19.4

24.0

24.9

34.4

38.8

39.7

KW

2.9

3.0

3.1

3.3

3.4

3.6

3.7

3.8

 

 

 

80

MBH

9.9

12.4

17.8

22.0

22.9

31.5

35.6

36.5

 

KW

2.9

3.1

3.2

3.4

3.5

3.7

3.8

3.9

 

 

 

55

MBH

11.2

14.1

20.3

25.2

26.1

35.9

40.6

41.6

 

KW

2.6

2.7

2.9

3.0

3.3

3.3

3.5

3.5

 

 

1050

70

MBH

10.2

12.8

18.5

22.8

23.6

32.7

36.9

37.8

KW

2.8

2.9

3.0

3.2

3.3

3.5

3.6

3.7

 

 

 

80

MBH

9.3

11.7

16.7

20.7

21.5

29.8

33.6

34.4

 

KW

2.8

3.0

3.1

3.3

3.4

3.6

3.7

3.8

 

 

 

 

 

 

 

BCH048

 

 

 

 

 

 

55

MBH

12.3

17.3

22.5

28.2

36.3

44.5

53.8

61.6

 

KW

3.4

3.5

3.6

3.6

3.8

4.0

4.6

5.2

 

 

2000

70

MBH

11.8

16.6

21.6

27.1

34.9

42.8

51.7

59.2

KW

3.5

3.6

3.8

3.8

4.0

4.2

4.8

5.4

 

 

 

80

MBH

10.9

15.3

19.9

24.9

32.1

39.4

47.6

54.5

 

KW

3.6

3.7

4.0

4.0

4.1

4.4

5.0

5.7

 

 

 

55

MBH

12.1

17.0

22.0

27.7

34.5

42.3

51.2

58.6

 

KW

3.3

3.4

3.5

3.6

3.6

3.8

4.4

5.0

 

 

1600

70

MBH

11.6

16.3

21.2

26.6

33.2

40.7

49.2

56.3

KW

3.4

3.5

3.6

3.7

3.8

4.0

4.6

5.2

 

 

 

80

MBH

10.7

15.0

19.5

24.5

30.5

37.4

45.3

51.8

 

KW

3.5

3.6

3.8

3.9

4.0

4.2

4.8

5.4

 

 

 

55

MBH

10.9

15.3

19.9

24.9

31.7

38.9

47.0

53.8

 

KW

3.1

3.2

3.3

3.4

3.5

3.7

4.2

4.8

 

 

1200

70

MBH

10.5

14.7

19.1

24.0

30.5

37.4

45.2

51.7

KW

3.2

3.3

3.4

3.5

3.6

3.8

4.4

5.0

 

 

 

80

MBH

9.6

13.5

17.6

22.0

28.1

34.4

41.6

47.6

 

KW

3.3

3.4

3.5

3.6

3.8

4.0

4.6

5.2

 

 

 

 

 

 

 

BCH060

 

 

 

 

 

 

55

MBH

18.2

24.7

31.1

38.4

45.6

55.4

64.7

75.6

 

KW

5.0

5.1

5.2

5.3

5.3

5.6

5.9

6.5

 

 

2500

70

MBH

17.5

23.7

29.9

37.0

43.9

53.3

62.2

72.7

KW

5.2

5.3

5.4

5.5

5.6

5.9

6.2

6.8

 

 

 

80

MBH

16.1

21.8

27.5

34.0

40.4

49.0

57.2

66.9

 

KW

5.4

5.6

5.7

5.8

5.9

6.0

6.5

7.2

 

 

 

55

MBH

18.0

24.4

30.8

38.1

45.0

54.7

63.9

74.7

 

KW

4.7

4.8

4.9

5.0

5.3

5.5

5.8

6.4

 

 

2000

70

MBH

17.3

23.5

29.6

36.6

43.3

52.6

61.4

71.8

KW

4.9

5.0

5.1

5.2

5.5

5.8

6.1

6.7

 

 

 

80

MBH

15.9

21.6

27.2

33.7

39.8

48.4

56.5

66.1

 

KW

5.1

5.3

5.4

5.5

5.8

6.1

6.4

7.0

 

 

 

55

MBH

16.2

22.0

27.8

34.3

41.4

50.2

58.7

68.6

 

KW

4.5

4.6

4.7

4.8

5.0

5.3

5.5

6.1

 

 

1500

70

MBH

15.6

21.2

26.7

33.0

39.8

48.3

56.4

66.0

KW

4.7

4.8

4.9

5.0

5.2

5.5

5.8

6.4

 

 

 

80

MBH

14.4

19.5

24.6

30.4

36.6

44.5

51.9

60.7

 

KW

4.9

5.0

5.1

5.2

5.5

5.8

6.1

6.7

 

 

Unitary Products Group

7

Image 7
Contents 036-21564-003-A-1005 FeaturesDescription Single Package AIR-TO-AIR Heat PumpsTable of Contents Features ContdCapacity Ratings Sound Power RatingsRatings Physical Data Basic UnitsCooling Capacities 3 TON BCH036 Cap Input Entering Dry Bulb, F Cooling Capacities 4 TON BCH048Air On Sensible Capacity Total2500 2250 2000 1750 1500 Cooling Capacities 5 TON BCH060Heating Capacities CFM RET. AIR CAP Outdoor AIR TEMPERATURE, F 72% RH MBHBCH CFM RPM Model AIR FlowBCH Speed CFM Model MotorMED Heater / CFM Limitations Static ResistancesMIN MAX RLA LRA FLA Amps Blower Circuit Size Breaker BCH PLY Motor AmpacitySize Number Motor Amps Ampacity Breaker FLA FLA Amps MIN MAX RLA LRA2CE04512006 21.2 208-1-60 2CE04511006230-1-60 2CE04511006 10.6 2CE04511506 15.9Outdoor AIR Economizer DIA Control Wiring Side or Bottom Power WiringDirect-Drive Units Knockout Hole Size Used forUnit with Economizer Rainhood Unit Dimensions CONTD. BCH 3, 4 & 5 TONRear View Detail aComponent Weights and Center of Gravity Roof Curb DimensionsCenter of Gravity FIELD--INSTALLED Accessories Factory Installed OptionsTypical Applications Typical ROOF-TOP InstallationMechanical Specifications Electrical Requirements Unit Operating CharacteristicsOther PRE--ENGINEERED Accessories Available Electric Heating SectionOther Factory Installed Options 036-21564-003-A-1005 Unitary Products Group 8QLWDU\3URGXFWV*URXS