United States Stove 1200Q owner manual Installation

Page 13

Installation

Please see all methods of Installation in Appendix at the rear of this booklet.

This is a furnace, not a free standing stove. You must direct heated air from 12" outlet away from the furnace, or it will not function properly.

1.This installation must be done by a qualified heating equipment installer.

2.The installation is to be done in compliance with National Fire Protection Association installation standards: No. 89M, 90B, 211, 70 (National Electric Code) and Uniform Mechanical Code 913, 6-4, in the states where applicable. (Their code offers connecting smoke pipe connectors into chimney with other fuel burning appliances.)

3.Rooms large in comparison with size of the appliances:

a) A Wood Burning Furnace needs air for com- bustion and circulation to house.

b)Provision must be made to make up this air and not starve gas or oil furnace of combustion air.

c)Have "Authority Having Jurisdiction" determine that air is of adequate makeup. (Reference N.F.P.A. Nos. 30 & 54, Code for Installation of Gas & Oil Equipment)

4.Have "Authority Having Jurisdiction" to inspect all chimneys and installations for adequate venting and for compliance with standard and local codes and regula-

tions regarding installation of wood burning appli- ances.

5. Installation of Supplemental Heat Application to Existing Central System. (See Fig. 13 for typical in- stallation.)

a)Place Wood Burning Furnace so that the chimney connector will be as short as possible and avoiding unnecessary sharp turns in the smoke pipe connector and the installation of devices that would create excessive resistance to the flow of flue gases.

b)Locate the Wood Burning Furnace as close as practical to the existing central hot air heating system, maintaining clearances as stated on the label located on the side of the furnace.

c)Clearances from combustible materials must be complied with as stated on the label below the fuel door:

Unit to Combustible: Front: 48"

Back: 30"

Sides: 12"

Plenum to Ceiling: 6"

Pipe to Combustible:

Sides: 21"

Back: 18"

The installation must be made only on a noncombustible floor.

d) Install the smoke pipe connector to the chim- ney with 26-gauge pipe and elbows (to be purchased separately), maintaining the proper clearances for the specific model. Make sure that the proper clear- ances as stated on the label and earlier in this manual are maintained. Seal the smoke pipe in the chimney with

furnace cement. (The chimney connector shall be securely supported, and joints fastened with sheet metal screws or rivets.)

e) Install 8" diameter heat pipe to plenum of the central hot air furnace. Use 26-guage pipe and con- nectors (to be purchased separately). (See Fig. 14) If central air conditioning is installed in the plenum, install heat pipe above the air conditioning unit. Secure heat pipe connection with supports and sheet metal screws.

f)Connect electrical supply in the electrical junction box that is mounted on the back of the Wood BurningFurnace.SeeWiringDiagram(Fig.12). Remove the cover from electrical junction box connect power supply wires to wires designated, using wire nuts. The

power cord supplied may be used for installation, if permitted by local codes and regulations. If the power cord supplied cannot be used, the power supply wiring must be 90 degrees Centigrade in a metal cable and should be completed by a qualified installer complying with NFPA Standard No. 70 and local codes.

g)Optional Plenum Fan Control Switch (Part No. 11PCS) is available for installation on the plenum of central hot air heating furnace. The purpose of this switch is to activate the circulating fan of the central hot air heating furnace when the temperature in the plenum exceeds 120° Fahrenheit. The switch would activate the fan at 120° Fahrenheit, and would shut off the circulating fan when the temperature in the plenum is reduced to 100° Fahrenheit . This avoids overheating the plenum.

The electrical supply for operation of this fan control switch is to be obtained from same electrical supply as the central hot air heating system. (See Fig. 14) Follow the instructions of the wiring diagram (Fig. 15). Do not make connections across Limit Control in the furnace.

Make electrical connections in electrical junction box presently mounted on the furnace. Make electrical connections in accordance with NFPA Standard No. 70 and local codes in the power supply junction box (See Fig. 15). The wiring to complete the connections should

be 18 AWG minimum copper and 90° Centigrade in a cable.

NOTE: THE MAXIMUM STATIC PRESSURE AT THE CENTRAL OR COMBINED PLENUM MUST NOT

EXCEED 0.12 INCHES WATER COLUMN.

•DRAWINGS FOR ILLUSTRATION PURPOSES ONLY•

13

Image 13
Contents Model 1200Q Tools and Materials Needed CongratulationsSafety Rules for Safe Installation and Operation HOW the Furnace Functions Model 1200Q Dimensions Locating the Furnace Masonry Chimney Chimney ConnectionAdjusting Barometric Draft Regulator Rules for Connector Pipe InstallationAssembly of Furnace Blower & Component Assembly FIG Model 1200Q Wiring Diagram FIG Installation Power Failure Instructions Drawings for Illustration Purposes only Alternative Parallel Installation Wiring Diagram FIG Operating Instructions Adjusting Blower Limit Control SettingsChimney Maintenance Service HintsModel 1200Q Parts KEY PART# Description QTY Model 1200Q Parts ListAppendix Installation B Installation C Installation D Only Installation E Installation F Installation G Drawings for Illustration Purposes only Trouble Shooting Tips for Warm AIR Furnace Ussc

1200Q specifications

The United States Stove Company 1200Q is a versatile and efficient wood-burning stove that combines traditional craftsmanship with modern technology. Designed for both aesthetics and performance, this stove is a popular choice among homeowners seeking an effective heating solution for their spaces.

One of the standout features of the 1200Q is its compact design, making it suitable for various room sizes. Its efficient size does not compromise its heating capability, as it can produce a maximum heat output of around 70,000 BTUs. This makes it effective for heating areas up to 1,200 square feet, making it an ideal choice for both small homes and larger living spaces.

The 1200Q is constructed from heavy-duty steel, which ensures durability and longevity. The firebox is designed for optimal airflow, providing a robust flame while enhancing combustion efficiency. This efficient design allows the stove to burn less wood, resulting in lower fuel costs and minimal environmental impact due to reduced emissions. The unit features an exterior heat shield that helps radiate warmth into the room while minimizing heat loss.

Another key technology found in the 1200Q is its advanced air wash system, which keeps the glass door clean by directing air over the glass surface. This not only maintains visibility of the fire but also adds to the overall aesthetic appeal of the unit. The large, ceramic glass window allows users to enjoy the beauty of the flames while benefiting from high efficiency.

The stove also includes adjustable legs, allowing users to customize the height to fit their installation needs. The top loading and front loading options provide convenience and flexibility when it comes to adding fuel to the fire. Additionally, the 1200Q is designed to accommodate various types of wood and biomass fuels.

Safety is a priority with the United States Stove 1200Q, which comes with features such as a heat-resistant handle and an integrated safety latch that secures the door during operation. Overall, the United States Stove Company 1200Q is a reliable and energy-efficient heating option for those looking to add warmth and charm to their home environment. Its blend of traditional aesthetics with modern technologies makes it a standout choice in the market for wood-burning stoves.