Lochinvar SSS051 Domestic Water Piping for Distant Fixtures, Relief Valve Discharge Piping

Page 11

Installation & Operation Manual

3 Piping (continued)

Domestic Water Piping for Distant Fixtures

In some cases the furthest fixture may be quite distant from the tank. In such an installation the configuration shown in FIG. 3-5 would result in an unacceptable delay before hot water reaches these distant fixtures. Even if all the fixtures are relatively close to the tank, the building owner may want hot water at all fixtures as soon as they are opened.

A solution to this problem is that a pipe runs from the furthest fixture on each branch back to the return of the tank. A small bronze circulator is mounted in this line and is wired so as to run continuously. A check valve in this line permits flow towards the tank inlet only.

NOTICE

NOTICE

For proper operation of the T&P and to prevent the T&P from activating due to boiler water temperature, use a T&P relief

valve with extended element. The recommended element length is 8 inches.

The Lochinvar SSS series water heaters will absorb less than 200,000 Btu/hr when domestic water outlet temperature is 210°F and boiler water supply temperature is 240°F. Listed outputs are based on ASME Section VIII Interpretation VIII-1-86-136. Check with local codes for applicability.

When no fixtures are drawing water, the bronze circulator moves hot water from the tank to the end of the branch just below the last fixture, then back to the inlet of the tank via the return pipe. When a fixture is opened, hot water is already out in the branch very close to the fixture and hot water appears at it almost immediately. The check valve prevents cold water in the tank’s inlet pipe from passing around the tank and heading directly to the fixture.

Because hot water is always circulating in the hot water branch the entire branch should be insulated to prevent excessive heat loss.

Temperature & Pressure (T&P) Relief Valve

Standard Installation

Install the T&P relief valve in the connection marked “Relief Valve”.

T&P Relief Valve Discharge Piping

T&P relief valve discharge piping must be:

- made of material serviceable for a temperature of

250°F or greater.

- directed so that hot water flows away from all persons.

- directed to a suitable place for disposal.

- installed so as to allow complete draining of the T&P

relief valve and discharge line.

- terminated within 12" of the floor.

￿CAUTION

To reduce the risk of excessive pressures and temperatures in the water heater, install temperature and pressure protective equipment required by local codes, but no less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspections of production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22. This valve must be marked with a maximum working pressure of the water heater.

T&P relief valve discharge piping must not be:

-excessively long. Using more than two (2) elbows or 15 feet of piping can reduce discharge capacity.

-directly connected to a drain. Terminate discharge piping within 6" from drain. Refer to local codes.

-subject to freezing.

Do not install any valve between T&P relief ￿ WARNING valve and tank connection or on T&P relief

valve discharge piping. Improper placement and piping of T&P relief valve can cause severe personal injury, death or substantial property damage.

Every Lochinvar Indirect Water Heater must be protected with a T&P relief valve.

Determine T&P relief valve size by the following specifications, unless they conflict with local codes:

-SSS031/041 - 3/4" NPT with an AGA Rating of 100,000 Btu/hr.

￿CAUTION

T&P relief valve is not intended for constant duty, such a relief of pressure due to repeated normal system expansion. Correct this condition by installing a properly sized expansion tank in domestic water system. Refer to expansion tank manufacturer’s installation instructions for proper sizing.

-SSS051/081/119 - 3/4" NPT with an AGA Rating of 200,000 Btu/hr.

11

Image 11
Contents Save this manual for future reference Hazard definitions ContentsPlease read before proceeding When servicing the indirect water heaterComponent Material General InformationOperating Restrictions Recommended Clearances Pre-installationCharacteristic Min Max Locating the TankBoiler Side Piping Piping1Piping Diagram Zoned with Circulators 2Piping Diagram Zoned with Valves 3Knight Boiler Primary / Secondary Piping Domestic Side Piping Tank Piping with a Temperature Limiting ValveRelief Valve Discharge Piping Domestic Water Piping for Distant Fixtures5Recommended Domestic Water Piping Indirect Water Heater Sensor Setup Knight Boiler Wiring2Wiring for Zone Control IDW Controlled Using Aquastat and Zone Circulator / ValveStart-up and Check-out MaintenanceThis warranty also does not cover Limited Lifetime Indirect Water Heater WarrantyModel Number Serial Number Date of Installation Limited Lifetime Indirect Water Heater WarrantyPage

SSS119, SSS031, SSS041, SSS051, SSS081 specifications

Lochinvar is a well-regarded name in the heating and water heating industry, renowned for its innovative and efficient solutions. Among their notable products are the SSS031, SSS041, SSS119, SSS081, and SSS051, a series of high-efficiency condensing boilers designed for residential and commercial use.

The Lochinvar SSS series, which includes models like SSS031 through SSS119, showcases advanced technologies aimed at optimizing energy efficiency and performance. One of the standout features of these models is their stainless steel construction, which enhances durability and resistance to corrosion. This material choice not only extends the lifespan of the units but also contributes to their energy efficiency by ensuring consistent heat transfer.

In addition to stainless steel, Lochinvar incorporates cutting-edge condensing technology in the SSS series. This design allows the boilers to extract additional heat from the exhaust gases, making use of latent heat that would otherwise be lost in traditional models. As a result, the SSS series achieves impressive Annual Fuel Utilization Efficiency (AFUE) ratings, often exceeding 90%. This high efficiency not only reduces energy consumption but also lowers operating costs, making these boilers a smart investment for both residential and commercial applications.

Another key characteristic of the Lochinvar SSS series is its user-friendly control system. Equipped with a touchscreen interface, operators can easily monitor and adjust settings for optimal performance and comfort. The integration of smart technologies and connectivity features allows for remote monitoring and control, enhancing the user experience and enabling proactive maintenance.

Furthermore, safety is a paramount concern in the design of the SSS models. They are equipped with multiple safety features including modulating burners and a low-water cutoff system, which ensures safe operation under various conditions.

The SSS031, SSS041, SSS119, SSS081, and SSS051 models cater to a range of heating demands, from smaller homes to larger commercial spaces. Each model varies in capacity, allowing users to select the appropriate unit based on their specific heating requirements. This flexibility, combined with the series' robust features and efficiencies, underscores Lochinvar’s commitment to providing reliable and sustainable heating solutions that meet the evolving needs of modern energy consumers.