Lochinvar SSS081, SSS051 Domestic Side Piping, Tank Piping with a Temperature Limiting Valve

Page 10

3Piping

Domestic Side Piping

Basic Domestic Piping

Figure 3-5 on page 12 shows typical domestic water piping for a tank. All components except the control are provided by the installer. The function of the components shown are as follows:

a.

Shut-off valves (recommended) - Use to isolate the

 

tank for servicing.

b.

Backflow Preventer (required by some codes) - Use to

 

prevent water from backing out of the tank in the event

 

that inlet water pressure drops.

c.

Expansion Tank (required when a backflow preventer is

Installation & Operation Manual

Tank Piping with a “Temperature Limiting Valve”

Usually, the maximum temperature of the outlet water will stay near the setting of the tank control. In some cases, however, hot water usage patterns can cause the outlet water temperature to rise significantly above the control setting.

The temperature of water going to the fixtures may be more carefully controlled through the use of a thermostatic mixing valve. This device blends a controlled amount of cold water with the hot water leaving the tank so that water at a more constant temperature exits the mixing valve. Anti-scald mixing valve piping is illustrated in FIG.’s 3-1 thru 3-3.

used) - This expansion tank absorbs the increased

volume caused by heating water. If a backflow

preventer is installed, this expansion tank is required

because the increased water volume will otherwise have

no place to go and the T & P valve will open.

Use an expansion tank designed for use on domestic

water systems.

Refer to the expansion tank

manufacturer’s literature for the proper size expansion

tank to use.

 

If an expansion tank is used, do not put NOTICE any valves between the expansion tank

and tank inlet.

￿WARNING

An anti-scald mixing valve does not eliminate the risk of scalding.

*Set the tank thermostat as low as practical.

*Feel water before bathing or showering.

*If anti-scald or anti-chill protection is required, use devices specifically designed for such service. Install these devices in accordance with their manufacturer’s instructions.

d.Unions (optional) - Use to disconnect the tank in the unlikely event that this is necessary.

e.Drain (required) - Used to drain the tank for inspection or servicing.

Multiple Tank Domestic Water Piping

Figure 3-4 illustrates the recommended method of piping the domestic water side of several tanks together. All tanks are piped in true parallel. Total domestic pipe lengths must be the same from point of tank exit to the common “T” to ensure an equal draw from each tank.

Each tank must have its own T&P valve. It is recommended that each tank be equipped with its own isolation valves, unions, and drains so that one tank may be removed from the system. If local codes require a backflow preventer, check with the appropriate authority to find out whether one backflow preventer may be used for tanks or each tank must be equipped with its own backflow preventer. If each tank must have its own backflow preventer, each tank must also have its own expansion tank. If a common backflow preventer is permitted, an expansion tank must be sized to accommodate the expansion volume of all tanks.

10

Image 10
Contents Save this manual for future reference Contents Hazard definitionsWhen servicing the indirect water heater Please read before proceedingOperating Restrictions General InformationComponent Material Locating the Tank Pre-installationCharacteristic Min Max Recommended ClearancesPiping Boiler Side Piping1Piping Diagram Zoned with Circulators 2Piping Diagram Zoned with Valves 3Knight Boiler Primary / Secondary Piping Tank Piping with a Temperature Limiting Valve Domestic Side PipingDomestic Water Piping for Distant Fixtures Relief Valve Discharge Piping5Recommended Domestic Water Piping Wiring Indirect Water Heater Sensor Setup Knight BoilerIDW Controlled Using Aquastat and Zone Circulator / Valve 2Wiring for Zone ControlMaintenance Start-up and Check-outLimited Lifetime Indirect Water Heater Warranty This warranty also does not coverLimited Lifetime Indirect Water Heater Warranty Model Number Serial Number Date of InstallationPage

SSS119, SSS031, SSS041, SSS051, SSS081 specifications

Lochinvar is a well-regarded name in the heating and water heating industry, renowned for its innovative and efficient solutions. Among their notable products are the SSS031, SSS041, SSS119, SSS081, and SSS051, a series of high-efficiency condensing boilers designed for residential and commercial use.

The Lochinvar SSS series, which includes models like SSS031 through SSS119, showcases advanced technologies aimed at optimizing energy efficiency and performance. One of the standout features of these models is their stainless steel construction, which enhances durability and resistance to corrosion. This material choice not only extends the lifespan of the units but also contributes to their energy efficiency by ensuring consistent heat transfer.

In addition to stainless steel, Lochinvar incorporates cutting-edge condensing technology in the SSS series. This design allows the boilers to extract additional heat from the exhaust gases, making use of latent heat that would otherwise be lost in traditional models. As a result, the SSS series achieves impressive Annual Fuel Utilization Efficiency (AFUE) ratings, often exceeding 90%. This high efficiency not only reduces energy consumption but also lowers operating costs, making these boilers a smart investment for both residential and commercial applications.

Another key characteristic of the Lochinvar SSS series is its user-friendly control system. Equipped with a touchscreen interface, operators can easily monitor and adjust settings for optimal performance and comfort. The integration of smart technologies and connectivity features allows for remote monitoring and control, enhancing the user experience and enabling proactive maintenance.

Furthermore, safety is a paramount concern in the design of the SSS models. They are equipped with multiple safety features including modulating burners and a low-water cutoff system, which ensures safe operation under various conditions.

The SSS031, SSS041, SSS119, SSS081, and SSS051 models cater to a range of heating demands, from smaller homes to larger commercial spaces. Each model varies in capacity, allowing users to select the appropriate unit based on their specific heating requirements. This flexibility, combined with the series' robust features and efficiencies, underscores Lochinvar’s commitment to providing reliable and sustainable heating solutions that meet the evolving needs of modern energy consumers.