Lochinvar SSS03 operation manual Start-up and Check-out, Maintenance

Page 15

Installation & Operation Manual

5Start-up and Check-out

1.Make sure the system is free of leaks and that air is purged from the system.

4. Make sure that each zone valve or circulator operates when,

and only when, its thermostat calls for heat. Let each zone

operate long enough to purge any remaining air from the

CAUTION

Fix any leaks found before proceeding further. Leakage from the boiler piping can result in severe damage to the boiler.

system.

 

5. Set the

indirect water heater to the desired temperature.

Because hot water presents a scald hazard, it is best to set the

2.Many soldering fluxes contain Zinc Chloride which can cause severe corrosion damage to stainless steel. After completing all domestic water connections, flush the indirect water heater thoroughly before leaving the installation. This is particularly important if the indirect water heater will be unused for an extended period of time after installation. Flush the indirect water heater by drawing at least three times its volume from the tank.

3.Make sure that all electrical connections are made correctly and that no exposed high voltage wiring is present.

thermostat at 120°F or lower and raise it only if necessary to

provide adequate hot water.

6. Re-enable the burner and allow the boiler to operate. Make

sure that the boiler shuts down when the indirect water

heater is satisfied.

6Maintenance

The Lochinvar SSS series indirect water heater is an extremely simple device and as such requires very little maintenance. There are, however, several items which should be checked out on an annual or as needed basis to ensure a reliable supply of hot water:

*On an annual basis, remove the black cover over the hand hole and make sure the hand hole cover is leak-tight.

*Make sure that the rest of the boiler and domestic water piping is free of leaks.

*If there is an oil lubricated circulator in the system, make sure it is lubricated as called for by the circulator manufacturer.

*The indirect water heater depends upon the boiler for a source of heat and is therefore only as reliable as the boiler. Make sure that the boiler is maintained in accordance with the boiler manufacturer’s instructions.

*If a water treatment system is required to keep the water chemistry within the parameters shown in Table 2A (see Section 2 - Pre-Installation), make sure that this system is properly maintained.

15

Image 15
Contents Save this manual for future reference Hazard definitions ContentsPlease read before proceeding When servicing the indirect water heaterGeneral Information Operating RestrictionsComponent Material Recommended Clearances Pre-installationCharacteristic Min Max Locating the TankBoiler Side Piping Piping1Piping Diagram Zoned with Circulators 2Piping Diagram Zoned with Valves 3Knight Boiler Primary / Secondary Piping Domestic Side Piping Tank Piping with a Temperature Limiting ValveRelief Valve Discharge Piping Domestic Water Piping for Distant Fixtures5Recommended Domestic Water Piping Indirect Water Heater Sensor Setup Knight Boiler Wiring2Wiring for Zone Control IDW Controlled Using Aquastat and Zone Circulator / ValveStart-up and Check-out MaintenanceThis warranty also does not cover Limited Lifetime Indirect Water Heater WarrantyModel Number Serial Number Date of Installation Limited Lifetime Indirect Water Heater WarrantyPage