Copper-fin II/IIE Boiler and Water Heater Service Manual

1 Service

Control modes

SH controlling sensor (boiler only)

The SH controlling sensor parameter selects the sensor the control will use to regulate the boiler firing rate. The sensor selections are as follows: The outlet sensor regulates the firing rate based on the outlet water temperature of the unit and the inlet sensor regulates the firing rate based on the inlet water temperature of the unit. If the outlet sensor is selected, and the optional system supply sensor is connected, the control will regulate the firing rate based on the system sensor temperature. If the inlet sensor is selected, and the optional system return sensor is connected, the control will regulate the firing rate based on the system return sensor. The default sensor is the Outlet Sensor.

Enable input (active / inactive)

The boiler or water heater can receive a call for heat in two different ways. First, an external contact (like a tank thermostat) or sensor (like a tank sensor) can generate a call for heat. Second, the 0-10Vdc voltage from a BMS can be used to generate the call for heat, as well as provide the setpoint or modulation level. On boilers, the external contact is connected to the Stage 1 input on the low voltage connection board. On water heaters, the external contact is connected to the Tank Thermostat input on the low voltage connection board. When a tank sensor is connected, the Tank Thermostat input is not used. When the call for heat comes from an external contact or tank sensor, the enable input must be set to active. When the call for heat comes from the 0-10Vdc input, the enable input must be set to inactive. The default setting is Active. Can only be set to inactive when BMS input is set to active.

BMS input (active / inactive)

When the building management input is enabled, the control modulates the unit or the cascade based on the voltage on the 0-10V input on the connection board. The 0-10V input may control either the modulation of the unit(s), or the setpoint. The default value is Inactive. See menu Section J to adjust the parameters that control the BMS operation.

Cascade (active / inactive)

Boilers or water heaters may be part of a group of units sequenced together. When so connected, each heater must be programmed to operate as part of the Cascade. This is done by setting the Cascade to Active. The default value is Inactive.

Sequencer (active / inactive) (boiler only)

The individual stages in the heater can be controlled separately with an external sequencer.

ModBus (active / inactive)

When the optional ModBus board is installed, the heater can be monitored and controlled by a Building Control System (BCS). If the heater is to be controlled through ModBus this parameter must be set to ACTIVE. The default value is Inactive.

ModBus timeout

When the heater is being controlled or is receiving temperature readings through ModBus, the information sent to the heater must be refreshed periodically. If the heater does not receive new information after a timeout, it will revert to local temperature readings and control. This prevents the heater from running for too long should the ModBus connection be lost. The range of this parameter is 0 to 120 seconds. The default value is 10 seconds.

22

Image 22
Contents Copper-fin II/IIE Boiler and Water Heater Models 402 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid Maintenance What is in this manual?Service TroubleshootingService Copper-fin displayControl inputs Control outputs How the control module operates General OperationHow the appliance operates Sequence of operationSequence of operation OUT 123.8F129HTR Postpurge Display panel menu access Display panel parameter access Parameter table a Boiler Operation OnlyAnti-cycle Time Anti Cycl Tm Parameter table B Water Heater Operation BMS Service Notification Pumps Temperature settings Viewable and changeable control parametersData logging FunctionsDHW settings Outdoor air reset boiler only Anti-cycling Control modes Building Management System BMS CascadeService Notification Circulation pumpsOwner maintenance Maintenance Maintenance and annual startupService technician See the User’s Information Manual for instructionsMaintenance Inspect/replace hot surface igniters Check relief valveInspect/replace hot surface igniter Inspect and clean burner Check all wiringCheck control settings Perform start-up and checks2Adjusting air shutter 399,999 750,000 Btu/ hr Models Adjusting combustion air pressure Checking manifold gas pressurePressure Regulator Chamber Adjustment Manifold Review with owner Inspect and clean the heat exchangerOiled bearing circulators Check control module fuses TroubleshootingBefore troubleshooting Check the followingOperation No DisplayNo Burner Unit DoesResistance Temperature Checking temperature sensorsTemperature Resistance Operation Boiler Pump System Pump NoisyNo Pump DHW PumpFlame Sequence Flow SwitchAnti-cycling HSI Current Low ErrorNo Flame Ign Flame CKTRunning Auto ResetNo Flame High LimitSensor Open Manual ResetInlet Low Sensor ShortedAPS Open Louver ProvingTank Open APS ClosedRem Ctrl Flt Temp O/ShootParameters Progr No Error Stored Service BlkWatch Dog Error Low Voltage
Related manuals
Manual 68 pages 54.37 Kb

402, 2072 specifications

Lochinvar 2072,502 is an innovative and robust water-heating solution tailored for residential and commercial applications. This model represents a significant advancement in energy efficiency and performance, catering to the dynamic heating requirements of modern buildings.

One of the standout features of Lochinvar 2072,502 is its advanced thermal efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, the unit delivers exceptional heat output while minimizing energy consumption. This not only reduces utility bills for homeowners and businesses but also supports sustainability efforts by decreasing carbon footprints.

The Lochinvar 2072,502 incorporates cutting-edge technologies that set it apart in the market. It is equipped with advanced control systems that allow users to precisely manage heating outputs, ensuring optimal comfort while conserving energy. The user-friendly digital display provides real-time data, allowing for efficient monitoring and control.

Another significant characteristic of the Lochinvar 2072,502 is its robust stainless-steel construction. This feature enhances the unit's durability and longevity, ensuring reliable performance even in challenging conditions. The high-quality materials also contribute to maintaining consistent water temperatures, which is essential for both residential and commercial heating needs.

The Lochinvar 2072,502 operates silently, making it ideal for installations in areas where noise is a concern. Its compact design allows for flexible installation options, fitting seamlessly into various spaces, whether it’s a utility room, basement, or outdoor area.

Furthermore, the unit supports multiple venting options, accommodating different building architectures and layouts. This versatility makes it an ideal choice for new builds and retrofitting existing systems.

Maintenance is streamlined with the Lochinvar 2072,502, as it features a self-diagnostics system that simplifies troubleshooting. Regular service check-ups are made easier with accessible components, allowing technicians to perform maintenance tasks efficiently.

In summary, the Lochinvar 2072,502 stands out for its high efficiency, advanced technology, durability, and flexible installation options. It is an ideal choice for those seeking a reliable and technologically advanced water-heating solution that meets the challenges of contemporary heating demands while promoting energy savings and environmental responsibility.