Lochinvar 2072, 402 Adjusting combustion air pressure, Checking manifold gas pressure

Page 30

Copper-fin II/IIE Boiler and Water Heater Service Manual

2 Maintenance

Adjusting combustion air pressure

The following is a recommended method for setting the combustion air pressure. The following pressure settings are for installations up to 4000 feet altitude. Contact the factory for high altitude air pressure settings.

Upon removal of the upper front doors, locate the capped tee in the pressure tubing that connects between the inner top and the gas valves. Remove this cap and connect a hose from the tee to a manometer.

For 399,999 - 750,000 Btu/hr models (reference FIG. 2-2)

1.The combustion air chamber pressure for these models is typically 1.2 - 1.3 inches water column when the fan is at high speed.

2.If adjustment is necessary, slightly loosen the nuts connecting the fan to the inner top.

3.Adjust the air shutter located underneath the fan assembly to obtain the desired chamber pressure. Slide the shutter inward to decrease the chamber pressure or outward to increase the chamber pressure.

For 990,000 - 2,070,000 Btu/hr models (reference FIG. 2-3)

1.The combustion air chamber pressure for these models is typically 1.2 - 1.3 inches water column when the fan is at high speed.

2.If adjustment is necessary, slightly loosen the nut located on the air shutter arm.

3.Adjust the air shutter arm to obtain the desired chamber pressure. Slide the arm inward to decrease the chamber pressure or outward to increase the chamber pressure.

All models

4.Once the adjustment procedure is complete, tighten all connections, disconnect the manometer, and replace the cap at the tee.

5.Check all connections and test fire the unit.

6.Replace all panels.

Checking manifold gas pressure

The gas regulator on the combination gas valve is adjustable to supply the proper manifold pressure for normal operation. The gas valves are factory pre-set and should not need adjusting in most cases. Gas manifold pressures are listed in Table 2B.

Gas manifold pressures may be checked with the use of a manometer. Follow the steps in the Checking Combustion Air Pressure Section prior to checking the manifold pressures.

Checking manifold gas pressure

1.Turn the appliance power switch to the “OFF” position.

2.Remove the upper outer access panels.

3.Remove the 1/8" hex plug from the downstream side of the gas valve (see FIG. 2-4). Install a fitting in the tap and connect a hose from the tap to a manometer.

4.Connect a hose from the tee used to measure the combustion air pressure to the other side of the manometer.

5.Turn the appliance power switch to the “ON” position.

6.With the unit at high fire, check and record the manifold pressure of the valve. The manifold pressure will be the sum of the two pressure readings (reference Table 2B).

7.Repeat this process with each gas valve.

￿WARNING Overfire and underfire hazards! Possible fire, explosion, overheating, and component failure. Do not attempt to adjust firing rate of the appliance. The firing rate must be adjusted only by factory trained personnel.

If you must adjust the gas valve regulator pressure, follow the steps below:

1.Remove the cap covering the manifold pressure adjustment screw (see FIG. 2-4). Note: Once the cap is removed, the pressure shown on the manometer will change and the unit may turn off.

2.Make a slight adjustment to the manifold pressure adjustment screw. Turning the screw clockwise increases manifold pressure and counterclockwise decreases manifold pressure.

3.Replace the cap and check the manifold pressure. Note: Allow the unit to re-light if necessary.

4.Repeat the steps above to match the manifold pressures from Table 2B.

5.Once the adjustment procedure is complete, turn off the appliance, disconnect the manometer, replace and tighten all connections, and replace all panels.

6.Turn on the appliance and test fire the unit.

7.Repeat this process with each gas valve.

30

Image 30
Contents Copper-fin II/IIE Boiler and Water Heater Models 402 Contents Please read before proceeding Handling ceramic fiber materialsNiosh stated First Aid Maintenance What is in this manual?Service TroubleshootingService Copper-fin displayControl inputs Control outputs How the control module operates General OperationHow the appliance operates Sequence of operationSequence of operation OUT 123.8F129HTR Postpurge Display panel menu access Display panel parameter access Parameter table a Boiler Operation OnlyAnti-cycle Time Anti Cycl Tm Parameter table B Water Heater Operation BMS Service Notification Pumps Temperature settings Viewable and changeable control parametersData logging FunctionsDHW settings Outdoor air reset boiler only Anti-cycling Control modes Building Management System BMS CascadeService Notification Circulation pumpsOwner maintenance Maintenance Maintenance and annual startupService technician See the User’s Information Manual for instructionsMaintenance Check relief valve Inspect/replace hot surface ignitersInspect/replace hot surface igniter Inspect and clean burner Check all wiringCheck control settings Perform start-up and checks2Adjusting air shutter 399,999 750,000 Btu/ hr Models Adjusting combustion air pressure Checking manifold gas pressurePressure Regulator Chamber Adjustment Manifold Inspect and clean the heat exchanger Review with ownerOiled bearing circulators Check control module fuses TroubleshootingBefore troubleshooting Check the followingOperation No DisplayNo Burner Unit DoesChecking temperature sensors Resistance TemperatureTemperature Resistance Operation Boiler Pump System Pump NoisyNo Pump DHW PumpFlow Switch Flame SequenceAnti-cycling HSI Current Low ErrorNo Flame Ign Flame CKTRunning Auto ResetNo Flame High LimitSensor Open Manual ResetInlet Low Sensor ShortedAPS Open Louver ProvingTank Open APS ClosedTemp O/Shoot Rem Ctrl FltParameters Progr No Error Stored Service BlkWatch Dog Error Low Voltage
Related manuals
Manual 68 pages 54.37 Kb

402, 2072 specifications

Lochinvar 2072,502 is an innovative and robust water-heating solution tailored for residential and commercial applications. This model represents a significant advancement in energy efficiency and performance, catering to the dynamic heating requirements of modern buildings.

One of the standout features of Lochinvar 2072,502 is its advanced thermal efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, the unit delivers exceptional heat output while minimizing energy consumption. This not only reduces utility bills for homeowners and businesses but also supports sustainability efforts by decreasing carbon footprints.

The Lochinvar 2072,502 incorporates cutting-edge technologies that set it apart in the market. It is equipped with advanced control systems that allow users to precisely manage heating outputs, ensuring optimal comfort while conserving energy. The user-friendly digital display provides real-time data, allowing for efficient monitoring and control.

Another significant characteristic of the Lochinvar 2072,502 is its robust stainless-steel construction. This feature enhances the unit's durability and longevity, ensuring reliable performance even in challenging conditions. The high-quality materials also contribute to maintaining consistent water temperatures, which is essential for both residential and commercial heating needs.

The Lochinvar 2072,502 operates silently, making it ideal for installations in areas where noise is a concern. Its compact design allows for flexible installation options, fitting seamlessly into various spaces, whether it’s a utility room, basement, or outdoor area.

Furthermore, the unit supports multiple venting options, accommodating different building architectures and layouts. This versatility makes it an ideal choice for new builds and retrofitting existing systems.

Maintenance is streamlined with the Lochinvar 2072,502, as it features a self-diagnostics system that simplifies troubleshooting. Regular service check-ups are made easier with accessible components, allowing technicians to perform maintenance tasks efficiently.

In summary, the Lochinvar 2072,502 stands out for its high efficiency, advanced technology, durability, and flexible installation options. It is an ideal choice for those seeking a reliable and technologically advanced water-heating solution that meets the challenges of contemporary heating demands while promoting energy savings and environmental responsibility.